Raypak Finned Water-Tube Water Heaters Source Quality Control, Part 3 Execution, Installation

Page 4

inlet temperature is not achieved within the 7-minute time frame.

2.The cold water start system shall be configured with a modulating three-way valve that is controlled by a system-matched PID controller. The PID controller temperature sensor shall be located in the inlet header of the water heater.

3.The control shall have a temperature setting dial located on the face of the board. The temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat.

4.The cold water start system shall be completely wired and mounted at the factory.

5.The control shall have the following diagnostic LED’s:

a.Call for heat

b.Start-up mode

c.Inlet temperature error

d.Sensor out of range

6.The controller shall have the capability to add optional alarm contacts.

O.Cold Water Run System

1.The water heater(s) shall be configured with a cold water run automatic proportional bypass system that ensures the water heater will experience inlet temperatures in excess of 105ºF within 7 minutes to avoid damaging condensation. The unit will automatically shut down if the inlet temperature is not achieved within the 7-minute time frame.

2.The cold water run system shall be configured with a variable speed pump that is controlled by a system-matched PID control that injects the correct amount of cold water directly into the water heater loop to maintain a minimum inlet temperature. The PID controller temperature sensor shall be located in the inlet header of the water heater.

3.The control shall have a temperature setting dial located on the face of the board. The temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat.

4.The cold water run system shall be completely wired and mounted at the factory.

5.The control shall have the following diagnostic LED’s:

a.Call for heat

b.Start-up mode

c.Inlet temperature error

d.Sensor out of range

6.The controller shall have the capability to add optional alarm contacts.

2.3SOURCE QUALITY CONTROL

A.The water heater(s) shall be completely assembled, wired, and fire-tested prior to shipment from the factory.

B.The water heater(s) shall be furnished with the sales order, ASME Manufacturer’s Data Report, inspection sheet, wiring diagram, rating plate and Installation and Operating Manual.

PART 3 - EXECUTION

3.1INSTALLATION

A.Must comply with:

1.Local, state, provincial, and national codes, laws, regulations and ordinances

2.National Fuel Gas Code, NFPA 54/ANSI Z223.1 – latest edition

3.National Electrical Code, ANSI/NFPA 70 – latest edition

4.Canada only: CAN/CSA B149 Installation Code and CSA C22.1 CEC Part I

5.Manufacturer’s installation instructions, including required service clearances and venting guidelines

B.Manufacturer’s representative to verify proper and complete installation.

3.2START-UP

A.Shall be performed by Raypak factory-trained personnel.

B.Test during operation and adjust if necessary:

Project Name / Date

Division 23 52 33.13 - 4

Image 4
Contents Finned WATER-TUBE Water Heaters Part 1 General Part 2 ProductsPage Page Installation Source Quality ControlPart 3 Execution START-UPTraining END of Section

Finned Water-Tube Water Heaters specifications

Raypak Finned Water-Tube Water Heaters are renowned for their efficiency, durability, and advanced technology, making them a preferred choice for both residential and commercial applications. These heaters are designed to provide hot water consistently and reliably, catering to a wide range of temperature requirements.

One of the primary features of Raypak Finned Water-Tube Water Heaters is their unique finned-tube design. This design increases the surface area of the heat exchanger, allowing for maximum heat transfer and improved thermal efficiency. The finned tubes facilitate superior heat exchange with the water flowing through them, ensuring that hot water is readily available even during periods of high demand.

Raypak integrates advanced technologies in their water heaters to enhance performance and energy efficiency. The units are equipped with advanced control systems that allow for precise temperature regulation, reducing energy consumption and preventing overheating. Additionally, many models feature modulating burners, which adjust the firing rate based on the heating demand, ensuring optimal efficiency and reduced emissions.

Durability is another hallmark of Raypak's engineering. The water-tube construction is designed to withstand high pressures and temperatures, making these heaters suitable for high-demand applications. The units are constructed with high-quality materials that resist corrosion and wear, ensuring a long operational life with minimal maintenance.

Raypak also prioritizes safety in their heater designs. Features such as automatic shut-off valves, flame detection systems, and pressure relief valves are incorporated to ensure safe operation in various conditions. These safety mechanisms protect both the user and the equipment, adding peace of mind to the investment.

Energy efficiency ratings for Raypak Finned Water-Tube Water Heaters are typically high, qualifying for energy rebates and incentives in many areas. This efficiency translates to lower operating costs and environmental benefits, aligning with the global shift towards sustainable practices.

In summary, Raypak Finned Water-Tube Water Heaters stand out for their innovative design, advanced technology, and robust safety measures. They provide exceptional heating performance suited for myriad applications, making them a reliable choice for consumers looking to invest in high-quality water heating solutions. With ongoing advancements in technology, Raypak continues to lead the way in delivering efficient and effective water heating systems that meet modern demands.