Delta Limited – Type H
Models 399B-899B
Model
NOTE: Pump location varies
based on model selected
SPECIFICATIONS
|
|
|
|
|
|
|
|
|
| Approx. |
| MBTUH | A | G | H | K | T | W | Amp. | Shipping | |
Model | Input | Output | Width | NPT | NPT |
|
|
| Draw* | Wt. (Lbs) |
399B | 399 | 335 | 43 | ¾ | 2 | 6 | 6 | < 6 | 445 | |
499B | 500 | 420 | 50 | 1 ¼ | 2 | 6 | 6 | 22 | < 6 | 545 |
649B | 650 | 546 | 60 ½ | 1 ¼ | 2 | 8 | 6 | < 6 | 590 | |
749B | 750 | 630 | 67 ½ | 1 ¼ | 2 | 8 | 6 | < 6 | 675 | |
899B | 900 | 756 | 78 | 1 ¼ | 2 | 8 | 6 | 36 | < 7 | 740 |
* Pump not included
Dimensions are in inches.
Rates shown are for natural or propane gas, and elevations up to 4,500 feet. For installation above 4,500 feet, please contact manufacturer.
Recommended natural gas supply pressure is 7 – 10.5” WC. Recommended propane gas supply pressure is 11 - 13” WC.
RATES OF FLOW AND PRESSURE DROPS
Model | 10°F ∆T | 20°F ∆T | 30°F ∆T | Min. Flow |
| Max. Flow |
| ||||||
GPM | ∆P (ft) | GPM | ∆P (ft) | GPM | ∆P (ft) | GPM | ∆P (ft) | ∆T | GPM | ∆P (ft) | ∆T | ||
399B | 68 | 5.4 | 34 | 1.5 | 22 | <1 | 20 | <1 | 34 | 90 | 10.0 |
| 7 |
499B | 85 | 9.2 | 42 | 2.3 | 28 | 1.1 | 21 | <1 | 40 | 90 | 10.5 |
| 9 |
649B | N/A | N/A | 55 | 4.0 | 36 | 1.8 | 28 | 1.1 | 40 | 90 | 10.7 |
| 12 |
749B | N/A | N/A | 64 | 5.5 | 42 | 2.5 | 32 | 1.6 | 40 | 90 | 11.0 |
| 14 |
899B | N/A | N/A | 76 | 8.5 | 51 | 3.8 | 38 | 2.2 | 40 | 90 | 11.8 |
| 16 |
Basis is 20 GPM or 40°F ∆T for minimum flow, 90 GPM for maximum flow.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 2000.461A | Effective: | Replaces: |