Hi Delta FlexGas – Type H
Models 302BD-902BD
Model
NOTE: Pump location varies based on model and application
SPECIFICATIONS
|
|
|
|
|
|
|
|
|
|
|
| Approx. |
| MBTUH | A | B | G | H | K | T | W | Amp. | Shipping | ||
Model | Input | Output | Width |
| Nat | Pro | NPT |
|
|
| Draw* | Wt. (Lbs) |
302BD | 300 | 252 | 36 | 41 | 3/4 | 2 | 5 | 6 | 18 | 6 | 405 | |
402BD | 399 | 335 | 43 | 41 | 3/4 | 2 | 6 | 6 | 6 | 470 | ||
502BD | 500 | 420 | 50 | 3/4 | 2 | 6 | 6 | 22 | 6 | 570 | ||
652BD | 650 | 546 | 3/4 | 2 | 8 | 6 | 6 | 615 | ||||
752BD | 750 | 630 | 2 | 8 | 6 | 6 | 700 | |||||
902BD | 900 | 756 | 78 | 2 | 8 | 6 | 36 | 7 | 765 |
* Without pump
RATES OF FLOW AND PRESSURE DROPS
Model | 10°F ∆T | 20°F ∆T | 30°F ∆T |
| Min. Flow |
| Max. Flow |
| |||||||
GPM | ∆P (ft) | GPM | ∆P (ft) | GPM | ∆P (ft) | GPM | ∆P (ft) |
| ∆T | GPM | ∆P (ft) |
| ∆T | ||
302BD | 51 | 3.2 | 25 | <1.0 | N/A | N/A | 20 |
| <1 |
| 25 | 90 | 9.8 |
| 6 |
402BD | 68 | 5.4 | 34 | 1.5 | 22 | <1 | 20 |
| <1 |
| 34 | 90 | 10.0 |
| 7 |
502BD | 85 | 9.2 | 42 | 2.3 | 28 | 1.1 | 21 |
| <1 |
| 40 | 90 | 10.5 |
| 9 |
652BD | N/A | N/A | 55 | 4.0 | 36 | 1.8 | 28 |
| 1.1 |
| 40 | 90 | 10.7 |
| 12 |
752BD | N/A | N/A | 64 | 5.5 | 42 | 2.5 | 32 |
| 1.6 |
| 40 | 90 | 11.0 |
| 14 |
902BD | N/A | N/A | 76 | 8.5 | 51 | 3.8 | 38 |
| 2.2 |
| 40 | 90 | 11.8 |
| 17 |
Basis is 20 GPM or 40°F ∆T for minimum flow, 90 GPM for maximum flow.
NOTES:
1.Dimensions are in inches
2.Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.
3.Required natural gas supply pressure is 7 - 10.5” WC. Required propane gas supply pressure is 11 - 13” WC.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 2000.303A | Effective: | Replaces: |