Johnson Controls 8000 Installation Options and Effect Water Characteristics, Operating Modes

Page 4

INSTALLATION OPTIONS AND EFFECT OF

WATER CHARACTERISTICS

Your Steam Humidifier can be installed to operate using 120 Volts, 208 Volts or 240 Volts.. The higher the voltage, the higher the potential output:

Voltage

Rated Output

 

 

120 Volts

4 lbs../hour (11..5 gallons/day maximum)

 

 

208 Volts

7 lbs../hour (20..5 gallons/day maximum)

 

 

240 Volts

8 lbs../hour (23..3 gallons/day maximum)

 

 

It may take several days for the humidifier to reach rated capacity depending on the input voltage and the electrical conductivity of the water. 120 volt systems take longer to reach rated capacity than 240 volt systems.. The humidifier should always be plumbed to cold water but the water can be softened or unsoftened.. “Hard” water, which has a high mineral content, and softened water generally has higher conductivity than naturally soft water.. Systems plumbed to higher conductivity water will reach capacity sooner than systems plumbed to low conductivity water.. As the humidifier operates, minerals build up in the canister, which increases the conductivity of the water.. With a new canister, allowing the humidifier to operate continuously (along with the indoor unit blower) will allow it to reach rated capacity in the shortest amount of time..

OPERATING MODES

When the humidifier is powered and turned on, the “On/Off” light is illuminated green..

When the canister is being filled or replenished with water, the “Fill” light illuminates green..

When the canister is being drained, the “Drain” light illuminates green..

During initial start up with a new canister, the humidifier may run through a series of fill/drain cycles until the conductivity of the water is in a range that allows normal operation.. During this time, the “Steam” light illuminates green.. If the humidifier cannot produce steam at the rated level after trying for 168 hours, the “Steam” light illuminates yellow.. The humidifier continues to operate in this state until the rated output is reached..

The conductivity of naturally soft water, hard water, and softened water changes as the water heats up, but the internal controller adjusts the water level to maintain a nominal current between the electrodes.. Over the life of the canister, minerals that build up on the electrodes will reduce their effective surface area and affect the resistance between them.. The operating water level will increase with use until it reaches the high water

level probe.. At that point, the “Service” light will flash red indicating that the canister needs to be replaced.. The humidifier will continue to operate but with reduced output..

When the humidifier begins a drain cycle, the fill valve opens to introduce cold water into the canister.. This is done to prevent hot water from entering the drain.. The drain valve remains open for four minutes to allow all water to drain from the canister..

Any time power is disconnected or humidifier is turned off, the internal timer for start-up and drain cycles is reset..

If the humidifier has operated 168 hours without a drain cycle, the drain valve will open and drain the canister.. Normal operation will continue..

If the humidifier is operating and a power failure occurs, once power is restored, the “On/Off” light will flash green for one minute, then the humidifier will turn on..

End of Season/Period of Inactivity Shut-down

If the humidifier does not receive a call to operate in 72 hours, the humidifier controller drains the canister.. The drain light will remain on until there is a humidity call or 24 hours has elapsed.. The humidifier will resume normal operation when a call for humidity is made..

DISPLAY PANEL

TABLE 1 – Display Panel

Indicator

Light

Function

 

 

 

 

 

 

 

 

 

 

Off

Humidifier is turned off or not receiving power..

 

 

 

 

 

 

 

 

 

 

Solid

Humidifier is turned on..

 

 

 

 

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Humidifier is preparing to turn on.. Occurs if power is

 

 

 

 

disconnected, then restored with switch ON.. Flashes

 

 

 

 

Green

 

 

 

 

for one minute..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid

Normal Operation.. Fill valve is energized allowing

 

 

 

 

water to flow into canister via fill cup.. (Does not

 

 

 

 

Green

 

 

 

 

illuminate when tempering water during drain cycle..)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Fill and Drain Valves are pulsing to dislodge mineral

 

 

 

 

Green

build-up in canister.. Flashes 10 times in four seconds..

 

 

 

 

 

 

 

 

 

 

Solid

Fault Mode.. Indicates canister needs water but

 

 

 

 

 

 

 

 

cannot fill.. Humidifier shuts down.. (Occurs if high

 

 

 

 

Red

water probe does not detect water after fill valve is

 

 

 

 

 

energized for 40 minutes..)

 

 

 

 

 

 

- 6 -

- 7 -

Image 4
Contents Johnson Controls Steam Unitary Products Safety Cautions Table of ContentsPrinciples of Operation IntroductionSequence of Operation Installation Options and Effect Water Characteristics Operating ModesDisplay Panel Display PanelOutdoor Temperature/Indoor Relative Humidity Outside Temperature Recommended RHHumidifier Control & Operating Instructions YellowMaintenance To Service Fill ValveCheck the Humidifier Operation Additional informationLimited warranty Humidifiers and AIR Cleaners Parts
Related manuals
Manual 2 pages 49.27 Kb

8000 specifications

Johnson Controls, a global leader in building technology and energy solutions, offers a range of advanced air handling units designed to maximize efficiency and air quality. The models 8000, 6000, 4000, 7000, and 5000 cater to diverse building complexities and climate requirements, embodying the company’s commitment to innovation and sustainability.

The Johnson Controls 8000 series stands out with its high capacity and flexibility, making it suitable for large commercial buildings and industrial applications. This series incorporates advanced microprocessor controls that optimize energy usage and enhance operational performance. It also features ECM (Electronically Commutated Motors), which improve efficiency while reducing noise levels. The modular design allows for easy customization and quick installation, catering to specific building needs.

The 6000 series is engineered for medium-sized commercial spaces, combining efficiency and affordability. Its unique design incorporates high-efficiency heat exchangers and robust insulation that reduce energy consumption while providing comfort. With a focus on intelligent controls, the 6000 series can seamlessly integrate with existing building management systems, offering real-time data and performance monitoring.

For smaller commercial applications, the 4000 series provides an effective solution without compromising on features. This unit is compact yet powerful, delivering high airflow while maintaining low energy costs. Its simple installation and maintenance procedures make it an ideal choice for businesses looking for a cost-effective air handling solution. The 4000 series also includes advanced filtration options to ensure high indoor air quality.

The 7000 series is particularly noted for its application versatility, suited for both light commercial and industrial environments. This series employs advanced technologies such as variable speed drives, which adjust motor speeds based on demand, resulting in significant energy savings. Its robust build quality and efficient thermal performance make it an enduring solution for diverse operating conditions.

Lastly, the 5000 series is designed to meet the needs of educational and healthcare facilities, where indoor air quality is paramount. This series includes HEPA filtration options and UV-C light systems to significantly reduce airborne pathogens, ensuring a safe and healthy indoor environment. Its user-friendly controls and smart technology integration provide ease of operation, enabling facility managers to maintain optimal performance with minimal effort.

In summary, Johnson Controls' air handling unit offerings encompass a range of models with advanced features, cater to various application needs, and underline the company's dedication to energy efficiency and improving indoor environments for better health and comfort.