COOLING CONSERVATION
To comfortably cool your home, your heat pump must remove both heat and humidity. Don’t turn your system off even though you will be away all day. On a hot day, your system may have to operate between 8 and 12 hours to reduce the temperature in your home to a nor- mal comfort level.
Keep windows closed after sundown. While the out- door temperature at night may be lower than indoors, the air is generally loaded with moisture which is soaked up by furniture, carpets and fabrics. This mois- ture must be removed when you restart your system.
The hotter the outside temperature, the greater the load on your system. Therefore do not be alarmed when your system continues to run after the sun has set on a hot day. Heat is stored in your outside walls during the day and will continue to flow into your home for several hours after sunset.
Use your kitchen exhaust fan when cooking. One sur- face burner on “High” requires one ton of cooling. Turn on your bathroom exhaust fan while showering to remove humidity. You can also help your system in the summer by closing drapes or blinds and lowering awnings on windows that get direct sunlight.
MAINTENANCE
Prior to any of the following maintenance pro- cedures, shut off all power to the unit.
In order to insure long and trouble free service from your system, we recommend periodic inspection, cleaning, lubrication and adjustment by your installing Dealer/Contractor. Be sure to ask about this service.
For those buildings with
LUBRICATION
Both the indoor blower motor and outdoor fan motor are permanently lubricated and require no mainte- nance.
FILTER CARE
Filters must always be used and must be kept clean. When filters become dirt laden, insufficient air will be
delivered by the blower, decreasing your units effi- ciency and increasing operating costs and
AIR FILTERS
3 THRU 6 TON
Units
THROWAWAY | QUANTITY | |
PER | ||
FILTER | ||
UNIT | ||
SIZES | ||
(Nom, Tons) | ||
(Inches) | ||
| ||
3 - 6 TON | ||
| ||
|
| |
14 x 20 | 2 | |
|
| |
14 x 25 | 1 | |
|
|
To install the filters, remove the filter access panel located to the left of the condensate drain connection as shown in Fig- ure 1.
NOTE: Filters must be installed with “Air Flow” arrows point- ing inward
Slide filters all the way into the filter racks provided. When more than one filter in a filter rack is required, they must butt each other when sliding into position. Replace the filter access panel.
(2)14" X 20"
FILTERS
(1)14" X 25"
FILTERS
3 - 6 TON
FIGURE 1 - END VIEW LESS FILTER ACCESS
PANEL 3 THRU 6 TON
Johnson Controls Unitary Products | 3 |