3-3-9 When the compressor does not operate

1)Inspection items

(1)Is the COMP A under the operating conditions? (cooling operating of A, B(C) room)

(2)Is the power voltage normal? (the rating voltage ±10% range)

(3)Are the connector connection of COMP A(RY 72, 73) and B(RY 71) good?

(4)The COMP A(B) is operated on and off in accordance with the operating conditions of indoor unit of A (B. C) room.

2) Inspection sequence

Apply the outdoor power and operate the indoor unit A(B, C)

in the cooling mode.

 

 

 

NO

Is the comp A under the operating condition?

 

 

 

YES

 

 

 

Has 3 minutes passed COMP A(B) after the power initial

NO

and COMP on/off

 

 

YES

 

 

 

Is comp A (B) on?

 

 

 

YES

 

 

 

 

 

 

 

NO *Refer to the power measuring terminal

 

 

 

 

Normal (comp A (B) off)

Keep Comp A (B) off

Normal

Is the voltage (the rating voltage ±10% range) shown across the terminal of Comp A(B) power applied?

YES

Defect of comp A (B) and running condenser

Replace

 

NO

 

Is the voltage of pin no. 14, 13( 15) at low

YES

 

(DC 0.7V)?

 

 

NO

 

 

 

Is the voltage of pin no. 50, 51 (52) of IC 04 (micom) at

YES

 

high (DC 5V)?

 

 

NO

 

 

 

Is comp A (B ) under the operating condition?

YES

 

 

 

NO

 

 

 

 

 

 

Defect of Ry 72, 73 (Comp B) and Ry 71(comp A)

contact and coil → Replace

Defect of IC 06 output

Replace

Defect of Ic 04 (micom)

Replace

Normal (comp A (B ) off)

*Comp A (B ) operating conditions

(1)Comp A : Comp on /off control in accordance with the A room during the heating and cooling indoor unit operation

(2)Comp B : Comp on /off control in accordance with the B(C) room during the heating and cooling

indoor unit operation

BLK

 

(3) RY72 (4)

BLK

* Comp A(B ) power measuring terminal

WHT

 

(1)

Comp A measuring ; RY 73 (4) ´ RY 72 (4)

(3) RY71 (4)

(3) RY73

WHT

(2)

Comp B measuring ; RY 71 (4) ´ RY 72 (4)

(4)

 

 

RED

 

(3)

Power input ; RY 72 (3) ´ RY 73(3)

 

RED

19

Image 20
Contents Room AIR Conditioner Installation Refrigerant Refill ProcedurePump down Procedure Disassembly and Reassembly Indoor UnitDo 1above Outdoor Unit Troubleshooting Items to be checked firstDisplay Self Diagnosis Standard Checking and Testing Operations Outdoor Unit Outdoor UnitIf the lamp is not flickering, check as follows Display Explanation Remark Fault Diagnosis by Symptom No Power completely dead-Initial diagnosisWhen the power voltage is not available Indoor unit on whenNo Power Outdoor unit Is the display of PCB shownWhen the fan of indoor unit does not operate When the outdoor unit fan does not operate Is operating lamp blinking? LCD display status of Remocon normal? When the 4 way valve A,B is not operating When the compressor does not operate Normal comp a B off Keep Comp a B offSet up the Model option Method for Setting up the model option with remoconCase of ex -1700b7 Table of the option code Memo Exploded Views and Parts List Parts List 1 UD26B1C2 UD26B1C2 2 UD18B1C2 ’TY Description Specification Remark ASS’Y Control in DB93-01223ARefrigerating Cycle Block Diagram Indoor Unit Outdoor Unit Schematic Diagrams Outdoor Unit Electronics
Related manuals
Manual 54 pages 30.52 Kb

AD26B1C13, AD18B1C09, UD18B1C2, UD26B1C2 specifications

The Samsung AD18B1C09 is an exceptional air conditioning unit that brings together cutting-edge technology and user-friendly design to create a comfortable environment in your home or office. This model stands out for its efficient performance and robust features tailored to meet various climate control needs.

One of the primary highlights of the AD18B1C09 is its impressive cooling capacity. It is designed to deliver rapid cooling even in large spaces, ensuring that every corner of the room reaches the desired temperature quickly. This makes it an ideal choice for areas that experience high temperatures, providing instant relief during hot summer months.

Energy efficiency is another hallmark of the AD18B1C09. With a high Energy Efficiency Ratio (EER), this air conditioner helps users save on electricity bills while minimizing their carbon footprint. The unit is equipped with advanced inverter technology, which adjusts the compressor speed based on the cooling demand. This not only enhances efficiency but also ensures quieter operation compared to traditional air conditioning systems.

The Samsung AD18B1C09 comes with a range of user-friendly features that enhance convenience. Its remote control functionality allows users to operate the unit from a distance, adjusting settings such as temperature, fan speed, and mode with ease. Additionally, smart features like programmable timers and sleep modes optimize energy use and enhance comfort without constant oversight.

Moreover, the unit is designed with a multi-stage filtration system that improves indoor air quality. This system effectively removes dust, allergens, and other impurities from the air, making it a great choice for individuals with allergies or respiratory concerns. The filters are easily accessible for maintenance, ensuring that the air quality remains consistently high.

In terms of design, the Samsung AD18B1C09 features a sleek and modern aesthetic that blends seamlessly with any interior decor. Its compact dimensions allow for versatile installation options, whether mounted on walls or placed in window units, providing flexibility to meet different spatial requirements.

Overall, the Samsung AD18B1C09 air conditioner combines powerful cooling capabilities, exceptional energy efficiency, and user-centric design, making it a top choice for those seeking reliable climate control solutions. This model truly embodies Samsung's commitment to innovation and quality in the realm of home appliances.