Page 2 of 2 | 14 Cell Louver, 90% Downlight, 10% Uplight |
| 48" Length 2 Lamp T5/T8, 96" Length 2 Lamp T5/T8 in Tandem |
Model No. EYS414FR232UNVHI
LER = FP - 67.3 IW - 59.7 BF - 0.87 Comparative yearly lighting energy cost per
1000 lumens = $3.58
Report Number: G2005315
Catalog Number: EYS414FR232UNVHI
Lamps: F32T8
Luminaire:
Ballast:
Report is based on 2850 Lumens per lamp.
Efficiency: 80.6% |
|
|
|
|
|
| |||
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.1 |
|
| 1.2 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 48.000 |
| 9.000 | |||||
Height of Side: |
|
| 3.960 |
| 3.960 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 86 | 82 | 78 | 74 | 71 | 69 | 69 | 67 | 65 |
02 | 78 | 71 | 66 | 65 | 61 | 57 | 61 | 57 | 54 |
03 | 71 | 62 | 56 | 57 | 52 | 48 | 53 | 49 | 46 |
04 | 65 | 55 | 48 | 50 | 45 | 41 | 47 | 43 | 39 |
05 | 60 | 49 | 42 | 45 | 39 | 35 | 43 | 38 | 34 |
06 | 55 | 44 | 37 | 41 | 35 | 31 | 39 | 34 | 30 |
07 | 51 | 40 | 33 | 37 | 31 | 27 | 35 | 30 | 26 |
08 | 47 | 37 | 30 | 34 | 28 | 24 | 32 | 27 | 24 |
09 | 44 | 34 | 27 | 31 | 26 | 22 | 30 | 25 | 21 |
10 | 41 | 31 | 25 | 29 | 23 | 20 | 27 | 23 | 19 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. |
| ||
45 | 3735. | 3507. | 4266. |
55 | 3049. | 3429. | 4063. |
65 | 2041. | 2839. | 3388. |
75 | 1377. | 1887. | 1951. |
85 | 635. | 929. | 287. |
CANDELA DISTRIBUTION0 |
|
| ||
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 1547 | 1547 | 1547 |
|
5 | 1534 | 1526 | 1542 | 146 |
15 | 1425 | 1428 | 1434 | 403 |
25 | 1241 | 1242 | 1268 | 575 |
35 | 1034 | 1034 | 1205 | 674 |
45 | 797 | 872 | 1211 | 729 |
55 | 545 | 753 | 1058 | 678 |
65 | 283 | 522 | 776 | 513 |
75 | 130 | 269 | 372 | 271 |
85 | 30 | 90 | 42 | 78 |
90 | 4 | 60 | 13 |
|
95 | 19 | 32 | 15 | 32 |
105 | 35 | 70 | 56 | 62 |
115 | 48 | 90 | 103 | 86 |
125 | 61 | 121 | 120 | 93 |
135 | 73 | 129 | 149 | 91 |
145 | 84 | 115 | 116 | 72 |
155 | 94 | 104 | 117 | 49 |
165 | 102 | 102 | 106 | 29 |
175 | 105 | 98 | 98 | 10 |
180 | 100 | 100 | 100 |
|
|
|
|
|
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
1124 | 19.7 | 24.5 | |
1798 | 31.5 | 39.2 | |
3206 | 56.2 | 69.8 | |
4067 | 71.4 | 88.6 | |
180 | 3.2 | 3.9 | |
274 | 4.8 | 6.0 | |
437 | 7.7 | 9.5 | |
525 | 9.2 | 11.49 | |
4592 | 80.6 | 100.0 |
Model No. EYS414FR254UNVPG
LER = FP - 69.1 IW - 118.5 BF - 1.00 Comparative yearly lighting energy cost per
1000 lumens = $3.48
Report Number: G2005307
Catalog Number: EYS414FR254UNVPG
Lamps: FP54/835
Luminaire:
Ballast:
Report is based on 4400 Lumens per lamp. Efficiency: 93.3%
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.1 |
|
| 1.1 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 48.000 |
| 9.000 | |||||
Height of Side: |
|
| 3.960 |
| 3.960 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 99 | 95 | 91 | 86 | 83 | 81 | 81 | 79 | 77 |
02 | 90 | 83 | 76 | 75 | 70 | 66 | 71 | 67 | 64 |
03 | 82 | 72 | 65 | 66 | 60 | 55 | 62 | 57 | 53 |
04 | 75 | 64 | 56 | 59 | 52 | 47 | 55 | 50 | 46 |
05 | 69 | 57 | 49 | 52 | 46 | 41 | 50 | 44 | 39 |
06 | 64 | 51 | 43 | 47 | 41 | 36 | 45 | 39 | 35 |
07 | 59 | 46 | 38 | 43 | 36 | 31 | 41 | 35 | 31 |
08 | 55 | 42 | 35 | 39 | 33 | 28 | 37 | 32 | 27 |
09 | 51 | 39 | 31 | 36 | 30 | 25 | 35 | 29 | 25 |
10 | 48 | 36 | 29 | 33 | 27 | 23 | 32 | 26 | 22 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. | |||
45 | 7075. | 6411. | 7788. |
55 | 5812. | 6348. | 7722. |
65 | 3952. | 5619. | 5760. |
75 | 2617. | 3186. | 3976. |
85 | 1377. | 1734. | 614. |
CANDELA DISTRIBUTION0
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 2847 | 2847 | 2847 |
|
5 | 2820 | 2805 | 2811 | 266 |
15 | 2644 | 2579 | 2561 | 731 |
25 | 2318 | 2220 | 2059 | 1013 |
35 | 1937 | 1730 | 2164 | 1197 |
45 | 1510 | 1594 | 2211 | 1330 |
55 | 1039 | 1394 | 2011 | 1274 |
65 | 548 | 1033 | 1319 | 935 |
75 | 247 | 454 | 758 | 502 |
85 | 65 | 168 | 90 | 150 |
90 | 6 | 112 | 19 |
|
95 | 22 | 66 | 23 | 52 |
105 | 43 | 58 | 26 | 65 |
115 | 52 | 179 | 112 | 128 |
125 | 55 | 259 | 258 | 185 |
135 | 57 | 259 | 329 | 174 |
145 | 59 | 192 | 296 | 116 |
155 | 60 | 127 | 186 | 58 |
165 | 64 | 73 | 92 | 22 |
175 | 61 | 50 | 48 | 5 |
180 | 53 | 53 | 53 |
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
2010 | 22.8 | 24.5 | |
3207 | 36.4 | 39.0 | |
5810 | 66.0 | 70.7 | |
7398 | 84.1 | 90.1 | |
256 | 2.9 | 3.1 | |
441 | 5.0 | 5.4 | |
731 | 8.3 | 8.9 | |
816 | 9.3 | 9.9 | |
8214 | 93.3 | 100.0 |
Ordering Information
Explanation of Catalog Number. Example: EYS414FR232UNVHI
EY |
| S |
|
|
|
|
|
| F | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
R |
| 2 | ||
|
|
|
|
|
S= Solid | Fixture | 14= 14 Cell | Finish: | |
Suspended/ | Sides | Length: | Louver | F= Flat |
Surface |
| 4=48" | 1 Row | White |
Fluorescent |
| 8=96" | 28= 28 Cell |
|
Luminaire |
|
| Louver |
|
|
|
| 2 Rows |
|
Options/Accessories
Stem and Canopy Sets: Suspends fixture 6", 12", 18" or 24" from surface.
Catalog Number: ASC6 CSP (6"), ASC12 CSP (12"), ASC18 CSP (18"),
ASC 24 CSP (24").
Fusing: Internal fast blow fusing: SUFFIX: GLR. Internal slow blow fusing: SUFFIX: GMF.
Emergency Pack:
charger and inverter. SUFFIX: LP400 (T8). LP550 (T5).
Cable Hangers: Adjustable
R= 10% Uplight | Lamp | Lamp Type: |
Reflector | Quantity: | (By Others) |
| 2=2 Lamp | 32=T8 |
| 2 Lamps in | 28=T5 |
| Tandem | 54=T5 |
| for 96" Units | (Nominal 48") |
Voltage: |
|
|
|
|
|
|
|
|
| Options: | |||
120, 277 or |
|
|
| Add appropriate | ||
|
|
| suffix to catalog | |||
|
|
|
|
| no., ie: (GLR) | |
Ballast |
| Type: |
| <10THD | ||
|
| |||||
|
|
|
| <20THD | ||
SO * | HI * | |||||
O4 * | H4 * | |||||
– | PI † | |||||
– | †PG †† | |||||
– | †PV †† | |||||
LOL T8 Dimming | PS * | – |
Other dimming options. Consult factory.
†*Instant Start Standard
††Instant Start (120V or 277V only) ††Program Rapid Start (UNV only)
NOTE:
For T8 UNV, you must use HI, H4 Ballast Code.
Single Cable and Canopy: Catalog Number: WC60.
Single Cable, Straight Cord and Canopy: Catalog Number: WCC60**.
Single Cable, Coil Cord and Canopy: Catalog Number: WCCC60**.
Chain Hanger Kits: Catalog Number: AH5 CSP.
**Cord,
Specifications
Materials: Housing is
Fixture Ends: 18 gauge cold rolled steel.
Louver: 22 gauge cold rolled steel.
Side Reflectors: Solid 22 gauge cold rolled steel.
Finish: Post painted white acrylic baked enamel.
Specifications (continued)
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed.
Job Information | Type: |
|
|
Lightolier a Genlyte company | www.lightolier.com |
Technical Information: (978) | |
631 Airport Road, Fall River, MA 02720 • (508) | |
We reserve the right to change details of design, materials and finish. | |
© 2005 a Genlyte company | Section 5/Folio |