Calculite® HID Lensed Downlight C12E28FL-PL
Page 1 of 3
| 20" (508 mm) to 30" (762 mm) | |
| 11" | |
| (280 mm) | (273 mm) |
13" (330 mm) |
Top View
Ceiling Cutout: 12 9/16” (256 mm) Dia.
12" Aperture, ED28 (Enclosed), Metal Halide, Prismatic or Fresnel Lens
10 | 8 | 4 | 5 | 1 | 2 | 3 | 7 | 6 | 11 | 9 |
(349 mm)
Vertical Adjustment: 5/8" (16 mm 2 7/8" (73 m
12" (305 mm) Dia. |
|
|
| 2" (50 mm) max. |
|
| |||
|
|
|
| Ceiling Thickness |
| ||||
|
|
|
|
|
Reflector Trim |
|
| Lamp (Enclosed, Coated) | |||
C12E28PLWHW | Prismatic Lens, White Step Baffle. | C1217MHPU Magnetic, 120V/277V Pulse Start | 175W | ED28, BT28 PS MH | ||
C12E28FLWHW | Fresnel Lens, White Step Baffle. | C1225MHPU Magnetic, 120V/277V Pulse Start | 250W | ED28, BT28 PS MH | ||
C1232MHPU Magnetic, 120V/277V Pulse Start | 320W | ED28, BT28 PS MH | ||||
|
| |||||
|
| C1240MHPU Magnetic, 120V/277V Pulse Start | 400W | ED28, BT28 PS MH | ||
|
| C1217MHU | Magnetic, 120V/277V | 175W | ED28, BT28 MH | |
|
| C1225MHU | Magnetic, 120V/277V | 250W | ED28, BT28 MH | |
|
| C1240MHU | Magnetic, 120V/277V | 400W | ED28, BT28 MH | |
|
|
|
|
|
| |
Features |
|
| Electrical (Cont.) |
|
|
1.Reflector: Specular anodized aluminum, 16 ga. Removable from inside fixture for access to splices and ballast.
2.Lens: Prismatic (C12E28PLWHW) or Fresnel (C12E28FLWHW) lens. Regressed 2 1/4" from ceiling line.
3.
4.Torsiontite Springs: Permit removal of lens assembly without tools.
5.Socket Cup: Heat dissipating
6.Mounting Frame: 0.048"
7.Mounting Ring:
8.Vertical Adjustment Mechanism: accommodates mounting to virtually any ceiling system using mounting bars (provided, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be preset prior to installation.
9.Mounting Bars: 0.048"
10.Ballast: Dual voltage (120V/277V) magnetic. Assembly is accessible from below without tools for inspection and replacement.
11.Junction Box: 0.048" (18ga.) galvanized steel. UL listed for maximum of (8) No. 12 AWG, 90°C through branch circuit conductors; allows inspection from below
12.Thermal Protector: (not shown) Meets NEC and UL requirements. Do not install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted, CWA or Super CWA (pulse start) circuit type, high power factor, sound rating “B” (175W and 250W PS)/sound rating “C” (others),
Ballast | ANSI Code | Voltage | Max. Amps | Input Watts | |
175W | PS MH | M137 | 120/277 | 2.20/0.90 | 205 |
250W | PS MH | M138 | 120/277 | 2.80/1.20 | 290 |
320W | PS MH | M132 | 120/277 | 3.40/1.50 | 370 |
400W | PS MH | M135 | 120/277 | 4.10/1.80 | 465 |
175W | MH | M57 | 120/277 | 2.00/0.90 | 205 |
250W | MH | M58 | 120/277 | 2.60/1.10 | 290 |
400W | MH | M59 | 120/277 | 3.90/1.70 | 460 |
Options and Accessories
Auxiliary: Add suffix A to
Emergency: Add suffix E to Reflector Trim and
Slope Ceiling Adapters: See Specification Sheet SCA.
Fuse (magnetic ballast): Add suffix F1 or F2 to Frame in Kit (F1=120V, F2=277V).
Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Wet Locations), CSA (magnetic ballast only), I.B.E.W. For 320W/400W, install fixtures with minimum spacing: 4 feet from
Job Information | Type: |
Job Name:
Cat. No.:
Lamp(s): Notes:
Lightolier a Genlyte Thomas Companywww.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508)
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504