Weil-McLain Electric Water Heater instruction manual Start-up

Page 11

PLUS Line Instruction Manual Supplement

PLUS & PLUS WATER HEATERS WITH GAS-FIRED WATER BOILERS

4 Start-up

Follow Boiler Manual procedures

1.Follow all procedures in the boiler manual to start up and verify operation of the boiler.

Set space heating operation

Verify space heating mode

1.Press the “Mode” button until the display shows “Para.” This is the parameter mode.

2.Press the “Step” button until the display first digit shows “3.”

3.The last digit must show “1.” If any other number displays, press the “+” button until “1” shows in the right-hand digit. Press the “Store” button to save this setting.

Set space heating target temperature

1.Press the Ultra control panel “Step” button until the display first digit shows “4.” The right 3 digits show the outlet water temperature setting.

2.Press the “+” or “-” button to change the setting to the desired outlet water temperature. (The factory default setting is 190 °F.)

a.Outdoor sensor installed — Setting is the target temperature for outdoor temperature at or below 32 °F. At higher outside temperatures, the Ultra PhD control module calculates the target temperature. (See Ultra Control Supplement for detailed discussion of outdoor reset.)

When a summer/winter switch is used, closing the switch will disable the boiler (space heating) circulator during summer operation.

b.Outdoor sensor not installed — Setting is the target temperature at all times.

3.Press the “Store” button to save the setting.

PLUS water heater operation

1.The PLUS water heater thermostat must be connected to low voltage terminal strip terminals 3 and 4 as shown on page 10.

2.When the water heater thermostat calls for heat, the module shuts down the boiler circulator, activates the water heater circulator and immediately sets target outlet water temperature to 190°F. This provides automatic priority heat allocation to the indirect water heater for maximum response and recovery.

3.The water heater circulator continues for 30 seconds after the heating cycle to deliver the most possible heat.

Check PLUS operation setup

1.Go to step 2 if the control is in Parameter mode already. Press the “Mode” button until the display shows “Para” (parameter mode).

2.Press the “Step” button until the display first digit shows “2.”

3.The last digit must show “1.” If any other number displays, press the “+” button until “1” shows in the right-hand digit. Press the “Store” button to save this setting.

4.The Ultra PhD control module turns on the PLUS circulator when the indirect water heater operating control closes. The control module shuts off the boiler circulator (stops space heating) during calls for DHW heating.

Verify operation — space heating

NOTE: “[ _ _ _ _ ]” in the following indicates the characters that should show on the Ultra display panel. “180” in the right 3 places means the display shows the measured boiler water temperature. The number shown will not necessarily be 180.

1.Turn down aquastat on PLUS tank. If necessary, turn off power and remove one of the PLUS aquastat wires to ensure boiler will not receive a DHW heat call.

2.Turn off power to boiler at service switch.

3.Wait a few seconds, then turn on power to boiler.

[A180] (self-checkon power-up, for a few seconds)

[0180] (no call for heat)

4.Raise room thermostat to call for heat.

[5180] (blower/circulator on) The blower and boiler circulator energize and the control checks for air flow.

[1180] (prepurge) After a few seconds delay (control self- check), blower speed will increase to ignition speed. The blower will run in prepurge for 10 seconds.

[2180] (ignition) After prepurge, the control module opens the gas valve and starts ignition spark.

a.If burner flame proves within 4.5 seconds, burner continues to fire. Burner will fire at start-up rate

— 50% of maximum input — for about 10 seconds to allow flame to stabilize.

b.If burner flame does not prove within 4.5 seconds, control module attempts ignition sequence again. Flame must prove within 5 attempts or control will lockout (display will show [E 02]).

c.Verify flame failure operation by closing boiler manual gas cock to prevent gas flow. Open manual gas valve after testing.

Part number IWHA016A/1103

11

Image 11
Contents Plus Line Hazard definitions ContentsSizing space heat system piping Install system water piping space heatingSystem water piping methods Boiler circulatorConnect boiler to system as shown in Figure Zoning with zone valvesCirculator zoning plus optional Zoning with circulatorsDedicated water-heating only applications Install boiler-to-water heater pipingCombined space heating/water heating applications First hour ratings in Tables 1 and 2 are based on Tables 1Wiring Plus circulator Field wiringInstallation must comply with Wiring boiler circulatorLow voltage connections Fig Wiring a system circulatorRouting line voltage wiring Outdoor temperature sensorLow voltage field wiring connections Start-up Lower room thermostat to stop call for heat Verify operation Plus water heaterOperating information Replace boiler jacket front door

Electric Water Heater specifications

The Weil-McLain Electric Water Heater is a standout choice for homeowners seeking reliable hot water solutions with a blend of efficiency and advanced technology. Designed for residential applications, this electric water heater offers a variety of features that cater to both comfort and energy conservation.

One of the key features of the Weil-McLain Electric Water Heater is its robust insulation. This high-density insulation minimizes heat loss, ensuring that the water maintains its temperature for longer periods, which can lead to energy savings over time. The design also features a durable tank, ensuring longevity and reliability, even in harsh water conditions.

Equipped with innovative heating elements, the Weil-McLain Electric Water Heater heats water quickly and efficiently. These elements are designed to provide a consistent flow of hot water, meeting the demands of modern households. Additionally, the heater includes an advanced testing thermostat that provides precise temperature control, ensuring that the water heater operates at optimal levels.

Safety is paramount, and Weil-McLain has incorporated several safety features into its electric water heater. These include an automatic reset function that prevents overheating and various pressure relief mechanisms to ensure the system remains safe under high-pressure conditions.

Moreover, installation of the Weil-McLain Electric Water Heater is designed to be straightforward. The unit is compact, making it suitable for a variety of installation spaces, and its lightweight design aids in transportation and setup. The versatility of this water heater is further enhanced by its compatibility with both standard and alternative energy sources, allowing it to fit into a range of homes and preferences.

The Weil-McLain Electric Water Heater also comes with an impressive warranty, providing peace of mind for homeowners. The warranty covers essential components, ensuring that customers receive reliable service throughout its operational life.

In conclusion, the Weil-McLain Electric Water Heater stands out due to its combination of efficiency, safety, and ease of installation. It is designed to meet the hot water needs of modern homes, while also prioritizing energy savings and long-term reliability. For those in search of a dependable hot water source, the Weil-McLain Electric Water Heater is an excellent choice.