PVI Industries PV500-45C manual Single Unit Installation Suggested Pipe Size, Inches

Page 16

Use this corrected total distance from the meter for determining the suggested pipe size in the “Single Unit Installation Suggested Gas Pipe Size” table.

 

 

 

SINGLE UNIT INSTALLATION SUGGESTED PIPE SIZE

 

Equivalent Feet

 

 

Maximum Capacity for Natural Gas*

 

 

 

MBTU/HR Based on 0.5" W.C. Pressure Drop**

 

From Meter

 

 

 

 

1-1/4"

1-1/2"

2"

2½"

3"

4"

 

 

25

 

860

1320

2475

3900

7000

-

40

 

660

990

1900

3000

5300

-

60

 

-

810

1520

2400

4300

-

80

 

-

690

1300

2050

3700

-

100

 

-

620

1150

1850

3250

6700

125

 

-

-

1020

1650

2950

6000

150

 

-

-

950

1500

2650

5500

175

 

-

-

850

1370

2450

5000

200

 

-

-

800

1280

2280

4600

*Multiplier for Propane: 1.57

**Multiplier for alternate pressure drops: 0.3" W.C. 0.77; 1.0" W.C. 1.41; 2.0" W.C. 2.00; and 4.0" W.C. 2.82.

MULTIPLE UNIT INSTALLATIONS GAS PIPING SIZE CHART

Maximum Capacity of Pipe in Thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025BTU’s per Cubic

Foot of Gas and 0.60 Specific Gravity).

Nominal Iron

 

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

Pipe Size,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inches

10

20

30

40

50

60

70

80

90

100

125

150

175

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

256

210

200

179

164

49

138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3300

3000

2720

2500

2340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

23500

16100

13100

11100

10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.6Appliance Isolation during Gas Supply Piping Pressure Test

1.The appliance and its provided manual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ PSI (3.5 kPa).

2.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSI (3.5 kPa).

3.The appliance and its gas connection must be leak-tested before placing it in operation.

16

PV500-45C 06/12

Image 16
Contents Installation & Maintenance Manual Table of Contents Operating and Safety Controls Troubleshooting Guide Replacement PartsTemptrac Electronic Controller Panel Remote Connections Terminal StripSafety Considerations Product Safety InformationBelow scalding temperatures Standard Features and Equipment Series Series Series Water Heater Installation Checking Equipment Before You InstallCodes Electrical RequirementsService Clearances Clearances To Combustible SurfacesGeneral Piping Guidelines Inlet and Outlet ConnectionsPV500-45C 06/12 PV500-45C 06/12 Optional Condensate Neutralization System Inlet Pressure NAT. GAS GAS Supply and PipingConvert Fittings to Equivalent Straight Pipe Single Unit Installation Suggested Pipe Size Multiple Unit Installations GAS Piping Size ChartNominal Iron Length of Pipe in Straight Feet InchesCombustion and Ventilation AIR Duct Fitting Equivalent Length Duct Pipe Vertical or Horizontal Remote Air Duct TerminationVenting the Tricon VentingMaximum Category IV Vent Length Equivalent Length Vent Fitting Equivalent Length Vent Pipe Combining Category IV VentsOperating and Safety Controls Temperature and Pressure Relief Valve sCathodic Protection High Water Temperature Limit ControlElectronic Low Water Cut-Off Optional Temptrac Electronic Controller Panel SETDown ClockTo Change The Setpoint To View The SetpointTo Change Other Parameters LED Display Alarm Messages Alarm Cause Results of Alarm Condition MessageRecommended Action Remote Connections Terminal StripSequence of Operation Incoming 120VACLoss of Flame Signal LED Indication Fault ModeInitial Startup Turn-on main gas shutoff valve PV500-45C 06/12 Gas Train Illustration for Models 40 through Gas Train Illustration for Models 65 throughTroubleshooting Guide Problem Probable Cause Corrective ActionReplacement Parts Replacement PartsControl Panel Contact factory for more information Burner Assembly Optional components may or may not be shown Contact factory for more information Item No Qty PVI Part No DescriptionPeriodic Maintenance PV500-45C 06/12 Recommended Maintenance Schedule PV500-45C 06/12 PV500-45C 06/12

PV500-45C specifications

PVI Industries has positioned itself as a leader in power generation solutions, and among its remarkable offerings is the PV500-45C, a sophisticated generator that caters to a wide array of industrial applications. The PV500-45C is notable for its robust design and cutting-edge technology, aligning perfectly with the demands of both commercial and residential projects.

One of the standout features of the PV500-45C is its high-performance engine, which ensures reliable power delivery even in the most challenging environments. The unit is equipped with a powerful 500 kW engine that operates efficiently, offering significant output while minimizing fuel consumption. This engine is built for longevity and durability, providing users with peace of mind and lower maintenance costs over time.

The PV500-45C employs advanced sound attenuation technology, making it one of the quietest generators in its class. This feature is particularly beneficial for applications in noise-sensitive areas, such as hospitals, schools, and residential neighborhoods. The generator is designed to meet strict emissions regulations, making it an environmentally friendly choice that adheres to local and international standards.

Another hallmark of the PV500-45C is its intelligent control system. The generator is outfitted with a state-of-the-art digital control panel that allows for seamless integration with existing power systems. This panel features real-time monitoring and diagnostics capabilities that help operators keep track of performance metrics and address potential issues before they escalate.

In terms of connectivity, the PV500-45C offers versatile options, including remote monitoring features that let users manage the generator from anywhere. This is particularly advantageous for businesses that require constant power availability, as it enables quicker responses to any technical difficulties.

The PV500-45C's design also prioritizes ease of maintenance. Key components are easily accessible, reducing downtime for repairs or servicing. The generator’s robust construction ensures it can withstand harsh environments, making it suitable for various applications including construction sites, agricultural tasks, and emergency power supply.

Overall, the PVI Industries PV500-45C is an exemplary model of modern generator technology, offering a blend of power, efficiency, and user-friendly features that cater to a diverse range of needs. Its performance and reliability make it an ideal choice for those seeking a high-quality power generation solution.