Connection Above the Fireplace
In this installation, the chimney connector enters the fireplace flue through a thimble located above the fireplace. (Fig. 6) The liner of the fireplace chimney should extend at least to the point at which the chimney connector enters the chimney. Follow all the guidelines for installing a chimney connector into a freestanding masonry chimney, and pay special attention to these additional points:
•The stove and chimney connector clearances to combustible mantel and trim materials are the same as clearances to combustible walls. If necessary, use a combination of mantel, trim, and connector heat shields to provide the required clearances. Refer to Page 12.
•
•The fireplace damper must be closed and sealed to prevent room air from being drawn up the flue which could reduce performance. However, it must be possible to reopen the damper to inspect or clean the chimney.
•Floor protection requirements also apply to fireplace installations.
Wall Pass-throughs
Whenever possible, design the installation so that the connector does not pass through a combustible wall. If you must include a wall
Consult with your dealer regarding special connection components available for use as wall
U.S. Requirements:
The National Fire Protection Association (NFPA) has established guidelines for use in the United States for passing chimney connectors through combustible walls. Many building code inspectors follow these guidelines.
Vermont Castings Madison
Chimney Connector |
|
|
| ||
* |
| ||||
Heat Shield |
| ||||
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note clearance |
|
* requirement on | * |
pages |
Mantel
ST244a
Fig. 6 If the clearance between the chimney connector and either the ceiling or the mantel is inadequate, a protective heat shield is required.
Fire clay | Min. 2” (51mm) Chimney clear- | ||
liner | ance to brick and combustibles | ||
A | Masonry |
| Min. 12” |
Chimney | Flue | (305 mm) | |
| constructed |
| |
|
|
| |
| to NFPA 211 | Chimney | Chimney |
|
| connector | |
|
|
| |
|
|
| Fire clay |
A |
|
| liner |
A = Minimum 12” (305 mm) brick con- | |||
| struction between liner and combustible | ||
| framing materials | ST272 | |
|
|
|
Fig. 7 Masonry Wall Pass-through with single wall chimney connector.
Figure 7 shows one NFPA-approved method. All com- bustible material in the wall is cut away to provide 12” (305mm) clearance to the connector. Brick and mortar are used to enclose the clearance area.
Alternate methods approved by the NFPA:
• Using a section of |
(229mm) clearance to combustibles. (Fig. 8) |
Solid insulated, listed factory- built chimney length set flush
with flue
Min. 9” 230mm
Masonry
Chimney constructed to NFPA 211
| Min. 2” | |
| (51mm) | |
| Min. 9” | |
| (230mm) | |
Flue | Chimney | |
Connector | ||
Chimney | ||
Air Space | ||
|
• Placing a chimney connector pipe inside a steel |
rated from combustibles by 6” (152mm) of fiberglass |
insulating material. (Fig. 9) |
|
| 24 ga.Sheet | ||
| Sheet Steel | Steel Sup- | ||
| tory cement | ports | ||
ST273 | Supports | |||
|
|
Fig. 8 Wall Pass-through using factory-built insulated chimney section.
30001453 | 7 |