Emerson 50A55 manual 3A3F, 3C YES, 3I YES

Page 4

INTEGRATED FURNACE

 

TROUBLESHOOTING

CONTROL MODULE

 

GUIDE

 

 

 

 

 

 

 

 

 

 

CHART 3

3A3F

Inducer Draft Motor

Call for heat.

and

Thermostat

Pressure Switch

contacts

Check

R & W close.

 

 

 

Is induced

YES

 

draft motor

 

 

 

energized?

 

 

NO

 

 

3B

 

NO

Is diagnostic

 

LED flashing 2

 

 

 

 

times?

 

3C YES

Disconnect

electric power

at fuse or

circuit breaker.

3D

Test for

continuity across pressure switch.

Is diagnostic

LED flashing 3

times?

YES

3G

Jumper

pressure

switch.

3H

Does ignitor

glow?

3I YES

Place incline manometer in series with pressure switch tubing.

NO

NO

Check inducer

wiring. If OK,

repair or replace

inducer motor.

Check operation.

Replace pressure switch. Energize system. Check operation.

 

3E

 

3J

 

 

 

 

 

Is

NO

 

Is pressure

 

pressure

 

 

greater than

 

switch welded

 

 

pressure switch

 

 

closed?

 

 

 

specs?

 

 

 

 

 

 

YES

3K

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove vent

 

 

 

 

connector

 

 

 

from furnace

 

 

 

 

flue collar.

 

 

 

 

 

YES

Replace pressure

switch. Check

 

 

operation.

TECHNICAL HELP

!WARNING

If diagnostic indicator (LED)

shows continuous flashing, turn off gas supply at source before disconnecting electrical power!

3L

Is

 

Correct blocked

pressure

YES

or incorrectly

greater than

 

installed vent.

pressure switch

 

 

Check operation.

specs?

 

 

 

NO

Repair leaks in

inducer assembly or

replace induced

draft motor. Check

operation.

262

www.white-rodgers.com

Image 4