TROUBLESHOOTING GUIDE

START

Is red LED status light on?

YES

NO

Is there 115v at L1 and L2?

NO

 

 

 

 

 

 

 

YES

 

 

 

 

NO

 

 

Is there 24v at SEC-1 and SEC-2?

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Replace control center.

 

 

 

 

 

 

 

 

 

 

Is door switch closed?

YES

Is there 115v going to switch?

YES

Replace door switch.

Replace transformer.

NO

NO

Close door switch and go to start.

Is circuit breaker closed?

 

NO

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Close circuit breaker and

 

 

go back to start.

 

 

 

 

 

 

 

 

 

 

Ð10Ð

Is red LED status light blinking

YES

Check for correct line voltage

 

rapidly without a pause?

 

 

polarity. If units are twinned,

 

 

 

 

 

 

check for proper low-voltage

 

 

NO

 

 

 

 

 

 

(24v) transformer phasing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for previous fault by

 

Is red LED status light blinking

 

 

momentarily shorting the TEST

 

ON/OFF slowly with a

NO

terminal and the C terminal until

 

combination of short and long

 

 

the LED goes out. LED will flash

 

flashes?

 

 

the status code of any previous

 

 

YES

 

 

fault or the code No. 11 (1 short

 

 

 

 

and 1 long flash) if no previous

 

 

 

 

 

 

 

 

 

 

 

 

fault. After the control repeats the

 

Determine status code. The

 

 

 

 

 

code 3 times, the control will go

 

status code is a 2 digit number

 

 

 

 

 

through a brief component test

 

with the first digit determined by

 

 

 

 

 

sequence. The inducer will start

 

the number of short flashes and

 

 

 

 

 

and run for the entire component

 

the second digit by the number of

 

 

 

 

 

test. The HSI, blower motor heat

 

long flashes.

 

 

 

 

 

speed, and blower motor cool

 

Once status code is determined,

 

 

 

 

 

speed will run for 10-15 sec each.

 

the control will go through a brief

 

 

 

 

 

 

 

 

component test sequence. The

 

 

 

 

 

inducer will start and run for the

 

 

 

 

 

entire component test. The HSI,

 

 

 

 

NO

blower motor heat speed, and

 

 

Was there a previous fault code

blower motor cool speed will run

 

 

other than No. 11?

 

for 10-15 sec each.

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section with status code

 

 

 

 

 

determined.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does control respond to W, Y, or G 24-vac thermostat signals?

YES

Run system through a heating or cooling cycle to check operation. Status codes are erased after 48 hrs or whenever power (115v or 24v) is interrupted.

NO

Check for continuity in wire from circuit breaker to furnace.

Check room thermostat or interconnecting cable.

NO

Is 24 vac present at W, Y, or G terminals on the control?

YES

Replace control if it does not respond to 24-vac signal at W, Y, or G screw terminals.

Image 10
Contents Electrostatic Discharge ESD Precautions Ð1ÐÐ2Ð Air Filter ArrangementÐ3Ð Blower Motor and Wheel→ ÐModel 373LAV Downflow Cleaning Heat Exchanger→ ÐModel 383KAV Upflow Ð4ÐElectrical Controls and Wiring Ð5ÐTroubleshooting Ð6Ð→ ÐHeating and Cooling Application Wiring Diagram Ð7Ð→ ÐWiring Diagram Ð8ÐÐService Label Ð9ÐTroubleshooting Guide Ð11Ð Service Training