TROUBLESHOOTING GUIDE
START
Is red LED status light on?
YES
NO
Is there 115v at L1 and L2? | NO | |||
|
| |||
|
|
|
| |
| YES |
|
| |
|
| NO | ||
|
| |||
Is there 24v at | ||||
|
| |||
|
|
|
| |
| YES |
|
| |
|
|
|
| |
Replace control center. |
|
| ||
|
|
|
| |
|
|
|
|
Is door switch closed?
YES
Is there 115v going to switch?
YES
Replace door switch.
Replace transformer.
NO
NO
Close door switch and go to start.
Is circuit breaker closed? |
| NO | ||
|
|
| ||
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
| Close circuit breaker and | ||
|
| go back to start. | ||
|
|
|
|
|
|
|
|
|
|
Ð10Ð
Is red LED status light blinking | YES | Check for correct line voltage |
| ||||
rapidly without a pause? |
|
| polarity. If units are twinned, |
| |||
|
|
|
|
| check for proper |
| |
| NO |
|
|
| |||
|
|
| (24v) transformer phasing. |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check for previous fault by |
| |
Is red LED status light blinking |
|
| momentarily shorting the TEST |
| |||
ON/OFF slowly with a | NO | terminal and the C terminal until |
| ||||
combination of short and long |
|
| the LED goes out. LED will flash |
| |||
flashes? |
|
| the status code of any previous |
| |||
| YES |
|
| fault or the code No. 11 (1 short |
| ||
|
|
| and 1 long flash) if no previous |
| |||
|
|
|
|
|
| ||
|
|
|
|
| fault. After the control repeats the |
| |
Determine status code. The |
|
|
| ||||
|
| code 3 times, the control will go |
| ||||
status code is a 2 digit number |
|
|
| ||||
|
| through a brief component test |
| ||||
with the first digit determined by |
|
|
| ||||
|
| sequence. The inducer will start |
| ||||
the number of short flashes and |
|
|
| ||||
|
| and run for the entire component |
| ||||
the second digit by the number of |
|
|
| ||||
|
| test. The HSI, blower motor heat |
| ||||
long flashes. |
|
|
| ||||
|
| speed, and blower motor cool |
| ||||
Once status code is determined, |
|
|
| ||||
|
| speed will run for |
| ||||
the control will go through a brief |
|
|
| ||||
|
|
|
|
| |||
component test sequence. The |
|
|
|
|
| ||
inducer will start and run for the |
|
|
|
|
| ||
entire component test. The HSI, |
|
|
|
| NO | ||
blower motor heat speed, and |
|
| Was there a previous fault code | ||||
blower motor cool speed will run |
|
| other than No. 11? |
| |||
for |
|
|
| YES |
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Go to section with status code |
|
|
|
|
| ||
determined. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Does control respond to W, Y, or G
YES
Run system through a heating or cooling cycle to check operation. Status codes are erased after 48 hrs or whenever power (115v or 24v) is interrupted.
NO
Check for continuity in wire from circuit breaker to furnace.
Check room thermostat or interconnecting cable.
NO
Is 24 vac present at W, Y, or G terminals on the control?
YES
Replace control if it does not respond to