Table 7 – Electrical Data

 

 

VOLTS

 

OPERATING

 

UNIT

MAX WIRE

MAX FUSE/

 

FURNACE

 

VOLTAGE*

MAX UNIT

MIN WIRE

HERTZ

 

AMPACITY#

LENGTH}

CKT BKR{

 

MODEL

(VOLTS)

 

(AMPS)

GAGE

 

PHASE

 

 

(AMPS)

FT. (M)

(AMPS)

 

 

 

 

 

 

 

 

 

 

MAX

MIN

 

 

 

 

 

 

 

 

 

 

 

 

045

--- 08 / 024045

115---

60---

1

127

104

8.1

10.9

34 (10)

15

14

070

--- 16 / 048070

115---

60---

1

127

104

9.5

12.6

29 (9)

15

14

090

--- 16 / 048090

115---

60---

1

127

104

10.3

13.4

27 (8)

15

14

110

--- 20 / 060110

115---

60---

1

127

104

13.1

16.9

34 (10)

20

12

135

--- 20 / 060135

115---

60---

1

127

104

13.1

16.9

34 (10)

20

12

* Permissible limits of the voltage range at which the unit operates satisfactorily.

#Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.

{ Time---delay type is recommended.

} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

GAS

SUPPLY

MANUAL

SHUTOFF

VALVE (REQUIRED)

SEDIMENT TRAP

UNION

313A

A02035

Fig. 22 - Typical Gas Pipe Arrangement

ELECTRICAL CONNECTIONS

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access panel door switch opens 115-v power to control. No component operation can occur. Do not bypass or close switch with panel removed.

See Fig. 25 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.

Field-supplied wiring shall conform with the limitations of 63_F (35_C) rise.

!WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2008 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.

21

Image 21
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard IntroductionClearances to Combustibles Codes and StandardsVenting Electrostatic Discharge ESD Precautions ProcedureLocation GeneralCarbon Monoxide Poisoning Hazard Personal Injury AND/OR Property Damage Hazard Electrical Operation HazardFire Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Location Relative to Cooling EquipmentACH Combination of Indoor and Outdoor Air InstallationBottom Return Air Inlet Side Return Air InletLeveling Legs Downflow InstallationA08556 Suspended Furnace Support Opening Dimensions In. mmPlatform Furnace Support Roll-Out ProtectionAIR Ducts Filter Arrangement Carbon Monoxide and Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsUpflowdownflow Horizontal Horizontal Suspension with Straps Return Air Connections GAS Piping Fire or Explosion HazardFurnace Overheat Hazard Maximum Capacity of Pipe Air Delivery CFM With FilterUpflow Return Air Configurations and Restrictions Horizontal Return Air Configurations and Restrictions Electrical Data Electrical Connections Electrical Shock HazardElectrical Shock and Fire Hazard Furnace MAY not Operate WiringBOX Relocation Electrical Connection to J-BOXBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXAccessories VentingFurnace Control Masonry Chimney Requirements General Venting RequirementsSingle-Stage Furnace with Single-Speed Air Con Ditioner Humidfier Internal Area of Chimney Appliance Application RequirementsChimney Inspection Chart Additional Venting Requirements Burn HazardSidewall Venting Upflow Application-Vent Elbow Up See Notes 1,2,4,5,7,8,9 on See Notes 1,2,4,5,7,8,9 Venting Notes for Figures Using Tin Snips to Cut Tie PointsRounded End of Knockout START-UP, ADJUSTMENT, and Safety Check Fire and Explosion HazardFurnace Damage Hazard Canada Follow exclusively the National Fuel Gas CodeAltitude Derate Multiplier for U.S.A Gas Control Valve Check Safety Controls Speed SelectionFurnace Overheating Hazard Gas Rate Cu Ft./Hr ChecklistA08220 A08220A Electrical Controls and Wiring Electrical Shock Hazard Service and Maintenance ProceduresFIRE, INJURY, or Death Hazard Electrical SHOCK, Fire or Explosion HazardA08221 Service Cleaning AND/OR Replacing AIR Filter Care and Maintenance Fire or Explosion HazardCarbon Monoxide Poisoning Fire Hazard Filter Size Information In. / mmUnit Damage Hazard Cleaning Heat ExchangerIgniter Position-Side View Sequence of Operation Cleaning Heat Exchanger CellThermidistat Mode Cooling ModeContinuous Blower Mode Two-Speed CoolingWiring Diagrams TroubleshootingHeat pump Wiring Diagram Troubleshooting Guide Catalog No. II313AAV---03
Related manuals
Manual 12 pages 24.1 Kb

313AAV specifications

The Bryant 313AAV is a state-of-the-art air conditioning unit renowned for its reliable performance and energy-efficient design. Crafted for residential use, this model provides optimal cooling while ensuring low operational costs. Its standout feature is the variable-speed compressor, which adjusts its output based on the cooling needs of your home. This not only leads to more consistent temperatures but also enhances energy efficiency, allowing homeowners to save on their utility bills.

One of the key technologies employed in the Bryant 313AAV is the Infinity Control system. This smart thermostat allows users to manage their home's temperature remotely via a smartphone app. The system is compatible with Wi-Fi, enabling seamless connectivity and ease of use. Additionally, the unit's advanced communication technology enables it to monitor system performance and send alerts for maintenance, ensuring that the air conditioning system operates at its best.

The Bryant 313AAV is designed with sound reduction technology, which minimizes operational noise, making it an excellent choice for residential environments where peace and quiet are a priority. Its cabinet is constructed for durability and features enhanced insulation to further reduce noise levels.

Another impressive characteristic of the Bryant 313AAV is its SEER rating. With Seasonal Energy Efficiency Ratio (SEER) ratings of up to 20, this model exceeds the minimum efficiency standards set by the U.S. government, making it an environmentally friendly option. This high SEER rating means that the unit consumes less energy while providing superior cooling performance.

Installation is made straightforward thanks to the unit's compact size and flexible design. Additionally, the Bryant 313AAV is equipped with EcoWise refrigerant, which is designed to be more environmentally responsible while ensuring efficient cooling performance.

In summary, the Bryant 313AAV air conditioning unit stands out due to its energy efficiency, advanced technology features, and quiet operation. It is an ideal choice for homeowners looking to enhance their comfort while keeping energy costs in check. With its reliable performance and innovative characteristics, the Bryant 313AAV is well-equipped to meet the cooling demands of today's households.