Ducane 2SA13B warranty Model Number Guide, Physical, Electrical, Performance

Page 2

Model Number Guide

2

SA

13

B

24

P - 1

A

2 - R22

Single Package A/C

13 - 13 SEER Nominal

Series

Minor Revision Code

Major Revision Code

Voltage

208-230V/60Hz/1Ph

Nominal Cooling 24 - 24,000 Btuh

Physical

 

 

Outside Fan

Indoor Blower

Refrigerant

 

 

 

Wheel

Weight

Model

 

 

 

Charge

Diameter

 

Nominal

dia. X width

(lbs.)

 

 

(oz.)

 

(in.)

 

RPM

(in.)

 

 

 

 

 

2SA13B24P

22

 

1075

10x6

104

370

2SA13B30P

22

 

1075

10x6

98

370

2SA13B36P

22

 

1075

10x8

101

390

2SA13B42P

26

 

825

10x10

122

500

2SA13B48P

26

 

825

10x10

146

510

2SA13B60P

26

 

825

10x10

165

510

Electrical

 

 

Normal

Min.

Max.

Compressor

 

Fan Motor

 

Indoor Blower

 

Voltage/Hz/

 

 

 

 

 

 

 

 

 

 

Rated

Locked

Rated

 

 

 

 

Rated

 

Model

Voltage

Circuit

Fuse/HACR

 

Rated

 

Nom.

Rated

Phase

Load

Rotor

Load

 

 

Load

 

 

Range

Ampacity

Brkr.

 

HP

 

RPM

HP

 

 

 

 

 

(amps)

(amps)

(amps)

 

 

 

 

(amps)

 

2SA13B24

208-230/60/1

197-253

17.0

20

10.4

45

1.1

 

1/5

 

1075

2.2

1/2

2SA13B30

208-230/60/1

197-253

21.0

25

14.1

68

1.1

 

1/5

 

1075

2.2

1/2

2SA13B36

208-230/60/1

197-253

21.0

25

14.4

77

1.1

 

1/5

 

1075

2.2

1/2

2SA13B42

208-230/60/1

197-253

29.0

35

19.2

104

1.6

 

1/4

 

825

3.6

3/4

2SA13B48

208-230/60/1

197-253

29.0

35

19.2

97

1.6

 

1/4

 

825

3.6

3/4

2SA13B60

208-230/60/1

197-253

30.0

40

19.9

137

1.6

 

1/4

 

825

3.6

3/4

Performance

Outdoor

SEER

EER

Rated

Rated

CFM

Model

ARI Capacity¹

Sensible Capacity

 

 

 

2SA13B24

13.00

11.50

23,000

17,700

800

2SA13B30

13.00

11.50

28,800

22,200

1000

2SA13B36

13.00

11.50

36,000

27,000

1200

2SA13B42

13.00

11.50

41,000

30,800

1400

2SA13B48

13.00

11.50

47,000

35,700

1600

2SA13B60

13.00

11.05

55,500

41,000

1800

1Certified in accordance with Unitary Air Conditioner Certification Program, which is based on ARI Standard 210/240.