Replace
board.
Turn on 
power to unit.
Is blower running?
NO
Jumper across screws R & G.
Is
blower running
on cooling
speed?
YES
Is
NO115VAC across 
& COM?
| 
 | 
 | 
 | 
 | START | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | Disconnect all thermostat | |||
| 
 | 
 | 
 | 
 | wires from board. | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| YES | Is 24VAC | YES | |||||
| 
 | 
 | 
 | 
 | across screws | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | ||
R & C?
 NO
 NO
Check/Replace:
1.Limit switch
2.Limit shield (if used)
3.Fuse link
4.Auxillary limit switch (if used)
5.Wire harness
Is
NO115VACNO across HI &
COM?
YES
Replace
blower motor
and/or start
capacitor.
| Is 24VAC | YES | 
 | |
| across screws | 
 | ||
| 
 | 
 | ||
| W & C or | 
 | 
 | |
| G & C? | 
 | 
 | |
| 
 | NO | 
 | 
 | 
| 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
Is
115VACYES across L1 &
L2?
 NO
 NO
Check/Replace:
1.Unit power
2.Door switch
3.Power harness
Turn off 
power to unit.
 NO
 NO
Are
all thermostat wires to board disconnected?
YES
Replace
board.
YES
Is
24VAC
across screws
R & C?
 NO
 NO
Check/Replace:
1.
2.Transformer
YES
Remove
R & G jumper.
Check pressure tube for leak or crimp; otherwise, replace pressure switch
YES
Is
24VAC
across 
NO
| NO | Replace | ||
| 
 | 
 | 
 | board. | 
| 
 | 
 | 
 | 
 | 
NODoes blower turn
off?
YES
Is heat
exchangerYES pressure drop greater 
than 
wc?
NO
YES
Is 24VAC
across pressure
switch N/O contact
&screw C on board?
 NO
 NO
Repair wire
harness.
Jumper across screws R & W.
Is
inducer motor
on?
NO
Check/Replace:
1.Vent systems
2.Induce wheel
3.Flue choke
4.Inducer voltage
5.Inducer motor bearings
| YES | Is | NO | 
| 
 | unit lit? | 
 | 
 YES
YES
Is 24VAC
across pressure
switch N/O contact
&screw C on board?
 NO
 NO
Is
24VAC across gas
valve?
| YES | Check/Replace: | ||||
| 
 | 
 | 
 | 1. | Draft safeguard switch | |
| 
 | 
 | 
 | |||
| 
 | 
 | 
 | 2. | Wire harness | |
| 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | ||
| YES | Check/Replace: | ||||
| 1. | Pilot | ||||
| 
 | 
 | 
 | |||
| 
 | 
 | 
 | 2. | Thermocouple | |
| 
 | 
 | 
 | 3. | Gas valve | |
| 
 | 
 | 
 | 
 | 
 | |
Replace
YES
Is
115VAC across
Is
blower running NO on heat speed 45
Is
115VAC across
| YES | Replace | |
| blower motor | ||
| 
 | 
inducer motor.
NO
Check/Repair wire harness; otherwise, replace pressure switch.
inducer motor
connector?
NO
Is
24VAC across 
YES
Replace
board.
NO
sec after unit
lights?
YES
Is
115VAC
across 
& COM?
YES
Remove
R & M jumper.
inducer motor
connector?
NO
Is
24VAC across
NO
Repair wire
harness.
| 
 | 
 | 
 | 
 | and/or start | ||
| 
 | 
 | 
 | 
 | capacitor. | ||
| YES | 
 | 
 | 
 | 
 | ||
| 
 | Replace | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | board. | 
 | |
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | Check/Replace | 
 | 
 | 
| 
 | 
 | 
 | 
 | thermostat | 
 | |
| 
 | 
 | 
 | 
 | and/or | 
 | |
| 
 | 
 | 
 | thermostat wiring. | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
NO
After
turn off?
| 
 | 
 | 
 | NO | 
| 
 | 
 | 
 | 
 | 
| Reconnect all | 
 | Does unit | |
| thermostat wires. | 
 | operate? | |
NOTE: After replacing any component, verify correct operating sequence as indicated by bold arrows.
| YES | 
| END OF TEST. | 
A91253