Step 7ÐElectrical Controls and Wiring

There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies.

The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 11 for field wiring information and to Fig. 15 for unit wiring information.

NOTE: If the polarity is not correct, the STATUS LED on the control center will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the control center and flame sensing.

The 24-v circuit contains an automotive-type, 3-amp fuse located on the control center. (See Fig. 12.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a fuse of identical size.

With power to the unit disconnected, check all electrical connec- tions for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely.

Reconnect electrical supply to unit and observe unit through 1 complete operating cycle. Electrical controls are difficult to check without proper instrumentation; if there are any discrepancies in the operating cycle, contact your dealer and request service.

Step 8ÐTroubleshooting

For an explanation of status codes, refer to service label located on back of main furnace door or Fig. 16, and the Troubleshooting Guide.

The control center stores 1 status code (representing the last fault to occur) for a period of 48 hr or until the 115- or 24-v power is interrupted.

NOTE: Removing blower access panel will open blower access panel door switch and terminate 115-v power to control center. The status code will be erased. Look into blower access panel sight glass for current LED status BEFORE removing blower access panel.

The unit's component test is a useful troubleshooting tool since it displays the current status code of the furnace and functionally operates all furnace components except the gas valve. The com- ponent test and methods to initiate it are described below.

COMPONENT TEST SEQUENCE

NOTE: All components are functionally operated except the gas valve.

When component test is initiated, the following sequence of events occurs:

1.LED flashes a status code 4 times.

2.Inducer motor starts and continues to run for remainder of component test.

3.Hot surface ignitor is energized for 15 sec, then de-energized.

4.Main blower operates at cooling speed for 10 sec, then turns off.

5.Main blower operates at heating speed for 10 sec, then turns off.

6.Inducer motor stops.

Component test can be initiated by one of the following proce- dures.

INITIATING COMPONENT TEST AND RETRIEVING STA- TUS CODE BY REMOVING MAIN LIMIT SWITCH WIRE

NOTE: NO thermostat signal may be present at control center and all blower time delay off periods must be completed.

FIELD 24-V WIRING

FIELD 115-, 208/230-, 460-V WIRING

FACTORY 24-V WIRING

FACTORY 115-, 208/230-, 460-V WIRING

FIVE

WIRE

THREE-WIRE

HEATING

ONLY

115-V

SINGLE PHASE

115-V AUXILIARY FIELD-SUPPLIED J-BOX

DISCONNECT

NOTE 5

W C R G Y

W/W1

W2 NOTE

3

R

G

C

NOTE 1

THERMOSTAT TERMINALS

GND

GND

FIELD-SUPPLIED

DISCONNECT

208/230- OR

460-V THREE PHASE

GND

208/230-V

SINGLE

PHASE

GND

SWITCH

FURNACE

CONTROL

CENTER

Y/Y2

 

24-V

TWO WIRE

TERMINAL

BLOCK NOTES:

CONDENSING

UNIT

1.Connect Y or Y/Y2 terminal as shown for proper cooling operation.

2.Proper polarity must be maintained for 115-v wiring.

3.Use W2 with 2-stage thermostat when zoning.

4.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.

5.Some thermostats require a "C" terminal connection as shown.

A98325

Fig. 11ÐField Wiring

8

Image 8
Contents Service and Maintenance Instructions ÐMultipoise Orientations ÐCleaning and/or Replacing Air Filter ÐBlower Motor and Wheel MaintenanceÐCleaning Burners ÐSpeed SelectorÐCleaning Heat Exchangers Primary Heat ExchangersTube Routing ÐFlushing Collector Box and Drainage SystemÐGasket on Collector Box ÐServicing Hot Surface IgnitorÐElectrical Controls and Wiring ÐTroubleshootingÐControl Center ÐChecking Heat Tape Operation If Applicable→ ÐInducer Housing Drain Tube ÐWinterizing→ ÐWiring Diagram Service → Troubleshooting Guide A99123 Page Service Training
Related manuals
Manual 12 pages 2.11 Kb

58MXA specifications

The Carrier 58MXA is an advanced heating and cooling system that exemplifies Carrier's commitment to innovation, efficiency, and comfort. Designed with the modern homeowner in mind, this gas furnace boasts a range of features that make it stand out in today's market.

One of the primary characteristics of the 58MXA is its impressive efficiency ratings. With AFUE (Annual Fuel Utilization Efficiency) ratings reaching up to 80%, the furnace ensures that homeowners can enjoy warmth during the colder months without excessive energy consumption. This efficiency not only translates to lower utility bills but also contributes to a reduced carbon footprint, making it an eco-friendly choice for environmentally conscious consumers.

The 58MXA utilizes a two-stage heating system which allows for more precise temperature control. This feature enables the furnace to operate at a lower stage for most of the heating cycle, providing comfortable warmth while conserving energy. When temperatures plummet, the system seamlessly switches to a higher stage for added heating capacity, ensuring that homes remain cozy even in extreme cold.

Furthermore, the Carrier 58MXA is engineered with advanced airflow and quiet operation in mind. Its variable-speed blower motor allows for optimal airflow throughout the home, enhancing overall comfort by distributing heat evenly in each room. This system also operates at a significantly reduced sound level compared to standard furnaces, promoting a peaceful indoor environment.

The 58MXA comes equipped with an innovative smart thermostat option, allowing users to monitor and control their home's heating remotely. This capability provides convenience and the opportunity for additional energy savings, as homeowners can adjust settings on the go or set schedules to meet their specific needs.

Durability is another hallmark of the Carrier 58MXA. Constructed with high-quality materials and backed by a manufacturer’s warranty, this furnace is built to withstand the rigors of temperature fluctuations and heavy use. Regular maintenance is also simplified, allowing homeowners to ensure optimal performance over the years.

Overall, the Carrier 58MXA is a top-of-the-line heating solution that combines efficiency, comfort, and advanced technology. Its innovative features and robust design make it an excellent choice for homeowners seeking a reliable and effective heating system. Whether for new construction or upgrading an existing home, the 58MXA is poised to provide years of dependable service.