Weil-McLain SB0002 warranty Subject Gold Oil Boiler Primary Burner Controls #60200-02

Page 1

Number: SB0002 (Page 1 of 2)

Date: February 2, 2000

Subject: GOLD Oil Boiler Primary Burner Controls #60200-02

In an effort to provide the industry with the best available technology for clean efficient combustion of fuel oil, Weil-McLain has standardized the GOLD Oil boiler burner control offering to include the Carlin 60200-02 primary control and 14,000 volt solid state ignitor. Listed below are some helpful tips for understanding these new controls.

Carlin 60200-02 Primary Control Standard Features / Benefits:

Interrupted Duty – Turns off the ignition ignitor once the flame is established reducing energy consumption and minimizing component wear.

Self-Diagnostic Check – On each call for heat, control performs a 4-second check of internal circuitry. Helps prevent burner runaway in the event of a welded set of motor contacts.

10 Second Valve-On-Delay (Prepurge) – Allows the burner motor and fuel oil pump to come fully up to speed and pressure prior to opening the oil solenoid valve and igniting the oil which provides cleaner startups.

10 Second Motor-Off-Delay (Postpurge) – Closes solenoid valve cutting off fuel supply while keeping the motor and blower on to complete combustion process, virtually eliminating smoke on shutdown.

15 Second Trial For Ignition – If oil fails to ignite in the first 15 seconds, control will lock out reducing potential for oil soaked chambers.

Flame Stabilization Period – Ignitor / spark remains on for 10 seconds after trial for ignition period ends.

Recycle – If control detects a flame failure, the burner will shut off in 1.3 seconds after loss of flame and then automatically commence with a 65-second recycle period after which control will go through another trial for ignition cycle.

Latch up – If control sees 3 consecutive lock-outs on the same call for heat, control will enter latch-up potentially eliminating flooded chambers from repeated homeowner attempts of pushing reset button.

Alarm Contacts – Close when control is in a lock-out or latch-up condition. Control may be connected to a separate security system for notification of a no heat situation.

Warranty – 3 years.

Primary Control Sequence of Operation:

1.Call for heat initiated.

2.Microprocessor performs a 4-second diagnostic self-check of internal control circuitry.

3.1-second pre-ignition (ignitor energized with spark on).

4.10-second valve-on-delay (prepurge).

5.Solenoid valve is energized allowing fuel to flow to nozzle and spark.

6.15-second trial for ignition. If no flame is established, control will lock out after 15 seconds.

Image 1
Contents Subject Gold Oil Boiler Primary Burner Controls #60200-02 Warranty 3 years Primary Control Sequence of OperationPrimary Control LED Status Indicators Technical Services Bulletin No SB0002 Page 2Warranty 3 years Does Not Weaken Over Time either works or it doesn’t