Features and Benefits

Two-Stage Compressor Widens the Application Range

Why Centrifugal Compressors Surge

Centrifugal compressors produce their pressure differential (head) by converting the kinetic energy of the gas leaving the impeller into static pressure. The velocity of this gas is the result of two components:

• The radial velocity component Vr, which is directly proportional to the refrigerant gas fl ow Q.

• The tangential velocity component Vt,which is a function of both impeller diameter D and the rotational speed rpm.

The length of the resultant vector V is proportional to the kinetic energy available for conversion to static pressure in the volute. Consequently, for a given compressor, Vt is fi xed and Vr varies with the cooling load. With the chiller unloading, the pressure differential between evaporator and

condenser decreases. The compressor matches the new load and the lower “head” by closing the inlet guide vanes.

This reduces the gas fl ow it draws in and modifi es its direction. Component Vr decreases accordingly, the vector diagram shifts and at some point, the balance of forces breaks down.

As pressurized gas rushes backwards through the impeller, the pressure in the gas passages falls, allowing the compressor to restore the balance of forces. If the process repeats itself, the compressor is said to surge.

Two-Stage Compressors Surge Less and Later

To produce the same head as a single-stage compressor, two-stage machines use two small diameter impellers. Component Vt is the same as on each stage, though Vr is the same as on a single-stage compressor. This results in a better balance of forces at low loads and produces a machine with a wider unloading capability.

In Trane centrifugal chillers, gas prerotation vanes ahead of the compression stage improve impeller aerodynamic effi ciency, resulting in smoother unloading and reducing power consumption.

The curves show that two-stage compressors surge less and later than single-stage machines. Intersection point B, when the load line meets the surge area, corresponds to a higher part load for the single-stage compressor than would be the case with a two-stage compressor. Two stage

 

machines, therefore, have a wider range of applications.

1

- Load Line

 

 

 

 

 

 

 

1

- Load Line

 

 

2

- Surge Line

 

 

 

 

2

- Surge Line

 

 

3

- A

 

3

- A

 

 

4

- B

 

4

- B

 

 

5

- 20%

 

5

- 40%

 

 

6

- 90°

 

6

- 90° Vanes

 

 

7

- 80°

 

7

- 100%

 

 

8

- 70° Vanes

 

8

- Compressor Head

 

 

9

- 100%

 

 

9

- Refrigerant Gas Flow

 

 

10 - Compressor Head

 

 

 

 

Typical single-stage compressor

 

Typical two-stage compressor

11 - Refrigerant Gas Flow

 

 

 

performance curve

 

performance curve

 

 

10

Image 10
Contents Centrifugal Water Chillers Model CvgfIntroducing Trane’s Model Cvgf Centrifugal Water Chiller IntroductionIntroduction Contents Features and Benefits Standard Cvgf FeaturesEnvironmental Features and Benefits Features and BenefitsAdditional Features and Benefits At-a-glance status Features and Benefits Tracer TU Interface CD-ROMFeatures and Benefits Tracer AdaptiViewTM Controller Building Automation and Chiller Plant ControlChiller-Tower Optimization Integrated Comfort System ICSWhy Centrifugal Compressors Surge Two-Stage Compressors Surge Less and LaterCondenser Water Limitations TemperatureApplication Considerations Water PumpsApplication Considerations Water TreatmentGeneral Data Table GD-1 Model Cvgf DescriptionGeneral Data 60 Hz SI Units and English UnitsShipment and Assembly Supply and Motor Lead Wiring and ConnectionsJobsite Connections Standard Features ControlsBase-Loading Control ControlsExtended Operation Package Hot-Water ControlStandard Protections Phase-Loss Protection Oil-Temperature ProtectionPhase-Unbalance Protection Phase Reversal/Rotation ProtectionCurrent Overload Protection High Motor-Winding Temperature ProtectionPower Factor and kW Measurement Surge Detection ProtectionShort-Cycling Protection Restart Inhibit Free StartsPhysical Dimensions 60 Hz SI English UnitsPhysical Dimensions Model Cvgf Water Connection Pipe SizeMechanical Specifications Condenser Mechanical SpecificationsUnit Control Panel Refrigerant and Oil Charge Compressor-Motor StarterIsolation Pads PaintingConversion Table PSI
Related manuals
Manual 24 pages 15.16 Kb

CVGF specifications

The Trane CVGF series is a revolutionary innovation in the world of commercial HVAC systems, designed to deliver unparalleled performance and energy efficiency. This air-cooled chiller line is specifically engineered to meet the demands of modern buildings, making it an ideal choice for various applications such as offices, hospitals, and educational institutions.

One of the standout features of the CVGF series is its use of the Trane Adaptive Control technology. This advancement provides the system with real-time data analytics, allowing it to automatically adjust cooling output based on environmental conditions and load requirements. This level of adaptability not only enhances occupant comfort but also contributes to significant energy savings, aligning with sustainability goals.

The CVGF chillers also incorporate a robust and efficient scroll compressor, which operates quietly and minimizes vibration. This design choice ensures reliability and longevity while reducing operational noise levels, making it suitable for installations in noise-sensitive environments. Furthermore, the scroll compressor's efficiency plays a crucial role in achieving a higher coefficient of performance (COP), which translates to lower energy costs.

In terms of environmental responsibility, the CVGF series is designed with an eco-friendly refrigerant that supports lower global warming potential (GWP). Committed to sustainability, Trane ensures that these chillers not only meet but exceed regulatory requirements, allowing businesses to operate with a reduced carbon footprint.

Another remarkable characteristic of the CVGF line is its modular design, which simplifies installation and maintenance. The units are compact and can be easily integrated into existing infrastructure, minimizing disruption during upgrades or replacements. The straightforward maintenance protocols further enhance the system’s uptime, ensuring users enjoy consistent and reliable cooling performance.

Moreover, the CVGF chillers are equipped with advanced monitoring capabilities, accessible through Trane’s proprietary software. This feature enables facility managers to oversee system performance from any location, facilitating proactive adjustments and timely maintenance interventions.

Overall, the Trane CVGF series stands out as a cutting-edge solution for effective and sustainable cooling in commercial applications. By combining innovative technologies, energy-efficient design, and user-friendly features, the CVGF offers a comprehensive approach to achieving optimal climate control while meeting the challenges of the future.