White Rodgers FG9, G9T service manual Furnace Control Event Schedule

Page 7

035-19592-001 Rev. C (0204)

Never bypass pressure switch to allow furnace opera- tion. To do so will allow furnace to operate under poten- tially hazardous conditions.

Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

CONTINUOUS FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.

2 FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indi- cate a faulty pressure switch or miswiring.

3 FLASHES: This indicates the normally open pressure switch contact did not close at the beginning of the heat cycle. This could be caused by a number of problems faulty inducer, blocked vent pipe, broken pres- sure switch hose or faulty pressure switch.

4 FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.

5 FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.

6 FLASHES: This indicates that after the unit was operating, the pres- sure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode it will complete it, and any subsequent delay off period. The vent motor continues to operate until the pressure switch re-closes or a call for heat is removed.

7 FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, faulty hot surface ignitor or burner problem may cause this.

8 FLASHES: This fault is indicated if the flame is lost 5 times (4 recy- cles) during the heating cycle. This could be caused by low gas pres- sure or faulty gas valve.

9 FLASHES: Indicates reversed line voltage polarity. Both heating and cooling operations will be affected. Check polarity at furnace and branch.

11 FLASHES: This fault will be indicated if the rollout jumper wire con- nection soldered into the board is broken. If this fault occurs the control will have to be replaced. This fault may also occur in installations where an improper ground is present. Prior to replacing control, verify that unit is properly grounded.

STEADY ON: This fault occurs if the gas valve is energized when there is no call for heat. If this happens the vent motor is energized and will remain energized for 5 seconds or until the fault clears itself at which point the vent motor de-energizes. This failure is counted as a recycle. Check the gas valve and control for proper operation.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 1,6,7,8 and Steady On will be reset. This provides protection to an unoccupied structure if a temporary con- dition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and provide heat for the house.

NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.

IGNITION CONTROL (P/N 031-01972-001) Normal flame sense current is approximately 3.7 microamps DC (µa)

Low flame signal control lockout point is

0.9 microamps DC (µa)

Thermostat Calling for Heat

(Seconds)

0 2

17

22

52

Fan on Delay 30 Seconds

ON

THERMOSTAT

OFF

ON

INDUCER

OFF

ON

Thermostat Satisfied

0

OFF

 

15 Sec.

OFF

Post

 

Purge

 

IGNITOR OFF

MAIN VALVE

OFF

HUMIDIFIER

OFF

ELECTRONIC

AIR CLEANER

OFF

CIRCULATING

BLOWER OFF

OFF

ON

ON

OFF

ON

OFF

ON

OFF

OFF

OFF

OFF

OFF

60, 90, 120, 180 SEC. OFF Selectable Fan Off Delay

FIGURE 8: Furnace Control Event Schedule

Unitary Products Group

7

Image 7
Contents Contact Information Table of ContentsSafety Section I USER’S InformationFire or Explosion Hazard Instructions for Examining the Furnace InstallationTo Turn Off the Appliance HOW Your GAS Furnace WorksSTART-UP and Shutdown Instructions Operating InstructionsFurnace Maintenance Section Section II Service and Maintenance ManualFurnace User Maintenance Safety SectionSequence of Operation Troubleshooting Furnace Cleaning SectionFurnace Control Diagnostics Furnace Control Event Schedule Section III Replacement Parts List Description Field Installed Accessories Electrical Field Installed Accessories NON-ELECTRICALWiring Diagram Section IV Wiring DiagramUnitary 5005 Norman Products York Group Drive 73069 Exclusions