INSTALLATION AND MAINTENANCE INSTRUCTIONS
2100AT Photoelectronic
Smoke Detector with Fixed Heat
and Integral | 3825 Ohio Avenue, St. Charles, Illinois 60174 |
Figure 1. Wiring diagram for the 2100AT detector:
IMPORTANT: OBSERVE POLARITY
Polarity must be observed on the power and remote annunciator connections.
+
INITIATING | EOL | |
LOOP | ||
– | ||
|
|
| + P |
| ||
|
| + |
| W |
|
| + | – | R |
| |
| A+ |
|
| ||
UL LISTED | – | A- |
|
| |
COMPATIBLE |
|
|
|
|
|
CONTROL | RA400Z |
|
|
|
|
PANEL |
|
|
|
| |
REMOTE |
|
|
|
| |
|
|
|
|
| |
| ANNUNCIATOR |
|
| NOT |
|
|
|
|
|
| |
|
|
|
| USED |
|
| OPTIONAL CLASS A WIRING |
| |||
NOTE: Only one detector per zone shall be used, unless when in alarm the panel switches |
| ||||
the zone to a reverse polarity, |
| ||||
detector shall not be mixed with other | |||||
|
|
|
|
| |
|
|
|
|
|
|
Specifications |
|
|
|
|
|
Diameter: | 5.5 inches (140 mm) |
|
|
|
|
Height (including mounting bracket): | 2.05 inches (52 mm) |
|
|
|
|
Weight: | 7.5 oz. (210 g) |
|
|
|
|
Operating Temperature Range | 32° to 100° F (0° to 38° C) |
| |||
Operating Humidity Range: | 10% to 93% Relative Humidity, Noncondensing |
| |||
Latching Alarm: | Reset by momentary power interruption |
| |||
Audible Signal: | 85 dBA minimum when in alarm or with supply polarity reversed |
| |||
Heat Sensor: | 135° F Fixed Temperature Electronic Thermistor |
| |||
Electrical Ratings |
|
|
|
|
|
System Voltage (nominal): | 12 or 24 VDC |
|
|
|
|
Minimum: | 8.5 VDC |
|
|
|
|
Maximum: | 35 VDC |
|
|
|
|
Maximum Ripple Voltage: | 30% of nom. Voltage (peak to peak) |
| |||
Standby Current: | 50 ∝A average, 100 ∝A maximum |
| |||
Alarm Ratings: | 29 mA typical at 12 VDC, 63 mA typical at 24 VDC, 100 mA maximum |
| |||
| (If used, the RA400Z Remote Annunciator operates within the specified detector | ||||
| alarm currents.) |
|
|
|
|
Reset Voltage: | 1.8 VDC minimum |
|
|
|
|
Reset Time: | 0.6 seconds maximum |
|
| ||
30 seconds maximum (after 60 sec. reset) |
| ||||
EOL Relay: |
|
|
|
| |
Special Considerations: | NOTE: Only one detector per zone shall be used, unless when in alarm the panel | ||||
| switches the zone to a reverse polarity, |
panels that do not provide this feature, a reversing relay, such as System Sensor’s
The 2100AT detector shall not be mixed with other
1 |