System Sensor 2100AT specifications Specifications, Electrical Ratings

Page 1

INSTALLATION AND MAINTENANCE INSTRUCTIONS

2100AT Photoelectronic

Smoke Detector with Fixed Heat

and Integral Temp-3 Sounder

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Figure 1. Wiring diagram for the 2100AT detector:

IMPORTANT: OBSERVE POLARITY

Polarity must be observed on the power and remote annunciator connections.

+

INITIATING

EOL

LOOP

 

 

 

+ P

 

 

 

+

 

W

 

 

+

R

 

 

A+

 

 

UL LISTED

A-

 

 

COMPATIBLE

 

 

 

 

 

CONTROL

RA400Z

 

 

 

 

PANEL

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

ANNUNCIATOR

 

 

NOT

 

 

 

 

 

 

 

 

 

 

USED

 

 

OPTIONAL CLASS A WIRING

 

NOTE: Only one detector per zone shall be used, unless when in alarm the panel switches

 

the zone to a reverse polarity, noncurrent-limited power supply. The 2100AT

 

detector shall not be mixed with other 2-wire detector types on the same zone.

A78-2336-15

 

 

 

 

 

 

 

 

 

 

 

Specifications

 

 

 

 

 

Diameter:

5.5 inches (140 mm)

 

 

 

 

Height (including mounting bracket):

2.05 inches (52 mm)

 

 

 

 

Weight:

7.5 oz. (210 g)

 

 

 

 

Operating Temperature Range

32° to 100° F (0° to 38° C)

 

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

 

Latching Alarm:

Reset by momentary power interruption

 

Audible Signal:

85 dBA minimum when in alarm or with supply polarity reversed

 

Heat Sensor:

135° F Fixed Temperature Electronic Thermistor

 

Electrical Ratings

 

 

 

 

 

System Voltage (nominal):

12 or 24 VDC

 

 

 

 

Minimum:

8.5 VDC

 

 

 

 

Maximum:

35 VDC

 

 

 

 

Maximum Ripple Voltage:

30% of nom. Voltage (peak to peak)

 

Standby Current:

50 ∝A average, 100 ∝A maximum

 

Alarm Ratings:

29 mA typical at 12 VDC, 63 mA typical at 24 VDC, 100 mA maximum

 

 

(If used, the RA400Z Remote Annunciator operates within the specified detector

 

alarm currents.)

 

 

 

 

Reset Voltage:

1.8 VDC minimum

 

 

 

 

Reset Time:

0.6 seconds maximum

 

 

Start-up Time:

30 seconds maximum (after 60 sec. reset)

 

EOL Relay:

A77-716B, 12/24 VDC

 

 

 

 

Special Considerations:

NOTE: Only one detector per zone shall be used, unless when in alarm the panel

 

switches the zone to a reverse polarity, non-current limited power supply. For

panels that do not provide this feature, a reversing relay, such as System Sensor’s RR-2, may be used. When utilized with the 2100AT, it allows for more than one de- tector to be utilized on a loop. Some panels may require the use of programmable outputs. Refer to System Sensor literature for further information on the RR-2.

The 2100AT detector shall not be mixed with other 2-wire detectors on the same zone.

–Due to the built-in temporal pattern, use this detector only with a non-coded power source.

D200-69-00

1

I56-1145-05R

Image 1
Contents Electrical Ratings SpecificationsTamper-resistant Feature Before InstallingWiring Installation Guidelines General DescriptionTesting InstallationMaintenance Removal of cover and screen for cleaning