System Sensor DH500 specifications Installation for Ducts More Than 8 Feet Wide

Page 4

Figure 4. Tube mounting configurations with varying air flow direction and orientation of detector housing. Vertical as well as horizontal mounting is acceptable.

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

AIR FLOW

DIRECTION

DIRECTION

 

DETECTOR HOUSING

INLET

TUBE

DETECTOR

HOUSING

A.

 

B.

EXHAUST

EXHAUST

INLET

TUBE

TUBE

TUBE

HORIZONTAL MOUNTING OF HOUSING

EXHAUST

 

TUBE

DETECTOR

 

 

HOUSING

 

EXHAUST

 

 

AIR FLOW

TUBE

 

AIR FLOW

 

 

 

 

DIRECTION

 

 

DIRECTION

 

 

INLET

INLET

 

 

DETECTOR

TUBE

TUBE

D.

H0109-00

HOUSING

C.

 

VERTICAL MOUNTING OF HOUSING

WARNING

In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube exposed to the air stream.

B. Installation for Ducts More Than 8 Feet Wide

NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accom- plished by using the ST-10 inlet sampling tube.

Install the inlet tube as follows:

1.Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube.

2.Slide the inlet tube with the flange into the right housing bushing. Position the tube so that the arrows point into the air flow. Secure the tube flange to the housing bush- ing with the two #6 self-tapping screws.

3.From inside the duct, couple the other section of the inlet tube to the section already installed using the 1/2- inch conduit fitting supplied. Make sure the holes on both of the air inlet tubes are lined up facing the air flow.

4.Trim the end of the tube protruding through the duct so that 1 to 2 inches of the tube extends outside the duct. Plug this end with the tube end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.

5.Any tube (over 3 feet long) that doesn’t protrude through the duct (on the side opposite the housing) must be sup- ported by other means.

NOTE: An alternate method to using the ST-10 is to use two ST-5 inlet tubes. Remove the flange from one of the tubes and install as described above. After the installation, use electrician’s tape to close off some of the sampling holes so that there are a total of 12 holes spaced as evenly as possible across the width of the duct.

NOTE: Air currents inside the duct may cause excessive vibration. This vibration can slowly open the seal around the tube and permit air to escape. To prevent this from occurring, a 3-inch floor flange, available at most plumbing supply houses, may be used. This flange/connector mounting technique makes the initial installation easier because a 1- inch to 1-1/4-inch hole may be drilled where the flange/connector will be used. It is easier to push the inlet tube through the larger hole.

Modification of Inlet Sampling Tubes

There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis- sible to modify an inlet sampling tube that is longer than necessary to span the duct width.

Use a 0.193-inch diameter (#11) drill and add the appro- priate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12. Space the additional holes as evenly as possible over the length of the tube.

D500-08-00

4

I56-512-07R

Image 4
Contents Specifications Before InstallingContents of the Duct Detector Housing Kit Electrical Ratings for DH500Mount Duct Housing Installation SequenceDrill the Mounting Holes Installation for Ducts Less Than 8 Feet Wide Install the Inlet TubeTube Outside Duct Width Installation for Ducts More Than 8 Feet Wide Modification of Inlet Sampling TubesField Wiring Wiring Installation GuidelinesWiring Instructions Install the FiltersRTS451/RTS451KEY Alarm Tests RTS451/RTS451KEY Remote Test StationMOD400 Sensitivity Test Trouble TestPhoto Units Ionization UnitsAccessories Both Types Of UnitsD500-08-00 Three-Year Limited Warranty Detector Test LOG

DH500, Intelligent Air Duct Smoke Detector Housing specifications

The System Sensor DH500 is an advanced intelligent air duct smoke detector housing designed to effectively monitor and detect smoke within HVAC ducts. As smoke detection in air handling systems is critical to ensuring the safety of occupants, the DH500 utilizes cutting-edge technology to provide reliable performance and early warning capabilities.

One of the main features of the DH500 is its intelligent detection capabilities. The device employs photoelectric sensing technology, which is well-suited for detecting the slow-burning fires that often generate more smoke than flames. This technology allows for prompt detection of smoke particles while minimizing false alarms caused by dust or other non-threatening particles. The DH500 is designed to operate efficiently in various environments, making it ideal for commercial and industrial settings.

The DH500 is equipped with a low-profile design, providing ease of installation and a more aesthetically pleasing appearance that blends seamlessly with existing ductwork. The housing is made from durable materials, ensuring long-lasting performance and resilience against environmental factors.

Another significant characteristic of the DH500 is its ability to accommodate multiple detectors. The housing can integrate with a variety of smoke detectors, allowing for installation flexibility depending on specific needs and applications. This modularity is particularly advantageous in large buildings where multiple air ducts may need simultaneous monitoring.

The device also incorporates advanced communication options, allowing for compatibility with various fire alarm control panels. This enables real-time monitoring and integration into broader building safety systems, enhancing overall emergency response capabilities. Moreover, the DH500 features an intuitive status indicator that provides visual confirmation of operational performance, making maintenance and monitoring straightforward.

In terms of maintenance, the DH500 is designed for easy access to the smoke detectors, ensuring they can be inspected and cleaned regularly, optimizing their efficiency and longevity. Regular maintenance plays a crucial role in the reliability of smoke detection systems, and the DH500's user-friendly design supports this essential function.

In summary, the System Sensor DH500 intelligent air duct smoke detector housing stands out for its intelligent detection technology, low-profile design, compatibility with multiple detectors, and advanced communication capabilities. Its durable construction and focus on ease of maintenance further enhance its appeal for commercial and industrial applications, making it a reliable choice for effective smoke detection in air handling systems.