WARNING
In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube exposed to the air stream.
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install sampling tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accomplished by using the
Install the sampling tube as follows:
1.Drill a
2.Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow. Secure the tube flange to the housing bushing with two #6
3.From inside the duct, couple the other sections of the
sampling tube to the section already installed using the
4.Trim the end of the tube protruding through the duct so that 1″ to 2″ of the tube extend outside the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
NOTE: An alternate method to using the
NOTE: Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch floor flange (available at most plumbing supply stores) may be used to fasten the sam- pling tube to the other side of the duct. When using the flange/connector mounting technique, drill a 1 to 11⁄4 inch hole where the flange will be used.
[5.4.3] Modifications of Sampling Tubes
There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis- sible to modify a sampling tube that is longer than neces- sary to span the duct width.
Use a
NOTE: This procedure should only be used as a temporary fix. It is not intended as a permanent substitute for ordering the correct length tubes.
[5.5] Install The Filters
To install the sampling tube filters, simply push the filters into the sampling and exhaust tube holes as shown in Figure 6. If a metal sampling tube is used, install the filter over the sampling tube.
Figure 6. Sampling tube filter installation:
WARNING
Filters require periodic cleaning or replacement, depend- ing on the amount of dust and dirt accumulated. Visually inspect the filters at least quarterly; inspect them more often if the dust accumulation warrants it. See Section [6] for more information. Replacement filters can be ordered from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. (Exhaust tube/intake tube filter P/N
[5.6] Field Wiring
Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having juris- diction. Proper wire gauges should be used. The conduc- tors used to connect smoke detectors to control panels and accessory devices should be
4 |