System Sensor DH400ACDCP specifications Alarm RED Common

Page 7

Figure 7. Wiring diagram for duct detector systems equipped without a control panel (see Figure 8 for wiring of additional optional accessories):

SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION.

FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER’S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER.

2 ALARM

RED

1 COMMON

 

AVAILABLE POWER INPUTS

 

1

 

2

12

13

 

14

 

24V

 

 

120

 

 

 

 

 

 

VAC

 

 

 

 

 

 

220/240

 

 

 

 

 

VAC

 

 

ALARM AUXILIARY CONTACTS

 

FOR FAN SHUTDOWN, ETC.

 

15

16

17

 

18

19

20

N.C.

C.

N.O.

 

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.

ALARM INITIATION CONTACTS

8

N.O.

9

 

 

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

5

(+) ALARM SIGNAL

 

6

(–) AUX POWER

 

POWER INPUTS ACCEPT

24 VDC, 24 VAC 50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR.

ALARM AUXILIARY CONTACT RATINGS 10A @ 30 VDC

10A @ 250 VAC

500mA MINIMUM @ 24 VDC

NOT INTENDED FOR CONNECTION TO CONTROL PANELS.

ALARM INITIATION CONTACT RATING 2.0A @ 30 VAC/DC (0.6 POWER FACTOR)

GRN.

FIELD INSTALLED JUMPER

7

(+) AUX POWER

 

10

TROUBLE

TROUBLE CONTACT RATING 0.3A @ 32 VAC/DC

TROUBLE CONTACTS CLOSED IN STANDBY AND ALARM. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS

3 POWER

APA451

AUDIBLE PIEZO ALERT WITH ALARM AND POWER (TROUBLE) LEDS. FOR STAND ALONE APPLICATIONS ONLY. APA451 RECOMMENDED FOR COMPLIANCE TO NFPA 90A. LOCATE IN NORMALLY OCCUPIED AREA OF PREMISES.

11 CONTACTS

DH400ACDCP

DUCT DETECTOR

EXTINGUISH OPTIONAL APA451 GREEN “POWER” LED TO INDICATE TROUBLE CONDITION.

H0253-00

D400-13-00

7

I56-555-09R

Image 7
Contents General Description Before InstallingTable of Contents List of Tables and FiguresStep Contents Of The Duct Detector KitInstallation Sequence Limitations Of Duct DetectorsOutside Duct Width Inlet Tube Required Install The InletDrill The Mounting Holes Inlet tubes required for different duct widthsAir duct detector inlet sampling tube Tube mounting configurations with varying air flow directionModifications Of Inlet Sampling Tubes Install the inlet tube as followsField Wiring Installation Guidelines Wiring InstructionsFor wiring Alarm RED Common Perform Detector Check Install The FiltersInstall The Cover Duct Detector Maintenance And Test ProceduresSmoke Response Filter ReplacementAlarm Tests 2.1 M02-04-00 Magnet Test Smoke Entry Tests Air FlowPhoto Heads Detector Cleaning ProceduresSensitivity Tests 3.1 MOD400R Sensitivity Test Air FiltersPhoto head exploded view ReinstallationDescription Test FeaturesMechanical Specifications AccessoriesElectrical Ratings Electrical SpecificationsD400-13-00 D400-13-00 Detector Test LOG Test Results and Maintenance Data

DH400ACDCP specifications

The System Sensor DH400ACDCP is a cutting-edge addressable smoke and heat detector specifically designed for commercial and industrial applications. Its advanced detection capabilities ensure a high level of safety in various environments, making it an essential component of modern fire alarm systems.

One of the standout features of the DH400ACDCP is its dual-sensing technology. This device combines both smoke and heat detection in a single unit, allowing for a more comprehensive approach to fire safety. The smoke detection is performed using a photoelectric sensor, which effectively identifies smoldering fires that produce a large amount of smoke, while the heat detector is designed to respond to rapid temperature increases and fixed temperature thresholds. This dual functionality ensures early notification in the event of a fire, enabling timely response.

The DH400ACDCP also incorporates System Sensor’s innovative analytics technology. This feature utilizes advanced algorithms to minimize false alarms while maintaining sensitivity to actual fire threats. By analyzing environmental conditions and historical data, the detector can distinguish between normal activities and potential fire indicators, thus reducing unnecessary interruptions.

In terms of installation and maintenance, the DH400ACDCP is designed for ease of use. It features a robust addressable communication system, which allows for straightforward integration into existing fire alarm panels. The unit can be easily configured through the panel, providing flexibility in customizing notifications and response protocols. Its durable construction ensures reliability, while routine diagnostics capabilities help monitor device health and facilitate maintenance efforts.

Another significant characteristic of the DH400ACDCP is its compatibility with system monitoring and control platforms. The detector can report its status and any potential issues directly to centralized monitoring stations, enabling rapid response to emergencies or maintenance needs. By integrating with modern building management systems, the DH400ACDCP contributes to an overall intelligent safety infrastructure.

Overall, the System Sensor DH400ACDCP offers a cutting-edge solution for fire safety in various environments, combining advanced detection technology, ease of integration, and robust performance. With its focus on minimizing false alarms while ensuring reliable detection, the DH400ACDCP stands as a critical asset for maintaining safety in commercial and industrial spaces.