2.Wiring Instructions:
a.The appropriate power supply is 120 Volt single phase power supplied from a
b.Turn off main power to the circuit before wiring the smoke alarm.
c.There are three pigtail leads (black, white and yellow) coming from the AC QUICK CONNECTOR. The proper wire connection is as follows:
WIRES FROM QUICK CONNECTOR | CONNECT TO |
BLACK | "HOT" side of AC line |
WHITE | "NEUTRAL" side of AC line |
YELLOW | Interconnect wires of other units |
For units that are used as single smoke alarms, do not connect the yellow wire to anything. Insulate this wire (tape it) in place to make certain the yellow wire cannot contact any metal parts.
Interconnected units can provide earlier warning of fire than
Interconnected CO alarms will only respond if a CO alarm / event initiates the alarm. All other alarms remain silent.
Interconnected smoke alarms, heat alarms and relay modules will only respond if a smoke alarm / event or heat alarm / event initiates the alarm. All CO alarms remain silent.
Note that units without battery backup will not respond during an AC power failure. NOTE: Relay
INPUT:
120VAC
60HZ
.05A
The yellow wire is used only for multiple station operation with USI ELECTRIC Model alarms only. Connecting this yellow wire to any other circuits may result in damage. When alarms are interconnected, all units must be powered from a single AC branch circuit. If local codes do not permit be sure the neutral wire is common to both phases. The maximum wire run distance between the first and last alarm/device in an interconnected system is 1,000 feet. NOTE: Use standard household wire (18 gauge or larger, rated at least 300V, as required by local codes) available at all electrical supply/hardware stores.
The wiring to be used shall be in accordance with the provisions of Articles 210 and 300.3(B) of the National Electrical Code, ANSI/NFPA70. In addition, the resistance of the interconnecting wiring shall be a maximum of 10 Ohms.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke alarm installed in each separate sleeping area (in the vicinity of, but outside of, the bedrooms) and heat or smoke alarms in living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility storage rooms, basements and attached garages. Test the smoke alarm weekly to assure proper operation.
3.Attach the mounting plate to the electrical junction box.
4.To activate 9 volt battery and alarm, hold the QUICK DRAW(R) battery drawer closed, pull and remove the
5.Plug the AC QUICK CONNECTOR into the alarm base. Push and turn the alarm clockwise onto the mounting plate.
6.See "TAMPER LOCKING PIN."