Bryant 580JP Product Data and Manual for High-Efficiency Heating and Cooling Systems

Page 1

580J***(D,F)

SINGLE PACKAGE ROOFTOP

GAS HEATING/ELECTRIC COOLING UNIT

TWO STAGE COOLING CAPACITY CONTROL WITH NOVATIONt COIL SIZES 08, 12, 14 WITH PURONR (R-410A) REFRIGERANT

Submittal Data

®

This product has been designed and manufactured to meet Energy Starcriteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and effi- ciency. Installation of this product should follow all manufacturer’s refrigerant charging and air flow in-

structions. Failure to confirm proper charge and air flow may reduce energy efficiency and short- en equipment life.

DESCRIPTION

580J***(D,F) units are high-efficiency, single-packaged electric cooling, gas heating units that are pre-wired and pre-charged with PuronR (R-410A) HFC refrigerant. Units utilize an all aluminum flat micro-channel tube with louvered fins condenser coil—NOVATIONt. The units are factory tested in both heating and cooling modes. These units meet the ASHRAE 90.1-2007 and Energy Star minimum efficiency levels as well as also meeting 2010 efficiency standards.

STANDARD FEATURES

Base Unit

SPuron (R-410A) HFC refrigerant

SARI certified efficiency levels up to 11.1 EER S Rated in accordance with ARI Standard 360

S Designed in accordance with Underwriters’ Laboratories Std 1995 and listed by UL and UL, Canada

S Two-stage cooling capacity control

S Non-corrosive composite sloping design; side or center drain condensate pan. Meets ASHRAE Standard 62

S Standard cooling operating range from 40_F up to 115_F (4_C up to 46_C). Field installable accessory extends the minimum down to -20_F (-29_C).

S Convertible from vertical to horizontal airflow for slab mounting S Two-inch disposable return air filters

S Thru-the-bottom power and gas entry capability S Single point gas and electric connections

S 24-volt control circuit protected with resettable circuit breaker and 75-VA transformer

S Belt drive, constant torque, permanently lubricated evaporator–fan motor

S Totally enclosed condenser motors with permanently lubricated bearings

S Low-pressure and high-pressure switches

S Full perimeter base rail with built-in rigging adapters and fork truck slots

S Centralized Terminal Board for component and unit wiring connections

Cabinet

SAccess panels with easy grip handles and NO-STRIP screw collar

SPre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection

SFully insulated cabinet

STool-less filter access door

Refrigerant System

SAcutrolt refrigerant metering system S Liquid line filter drier

S Scroll compressors with internal line-break overload protection S Copper tube, aluminum fin evaporator coil

S NOVATION all aluminum condenser coil

S Removable gauge line plugs for reading refrigerant pressure with unit panels in place

Gas Heat

SIGC solid-state gas heat exchanger control for on-board diagnostics, anti-cycle protection, LED error code designation, burner control logic and energy saving indoor fan motor delay

SGas efficiencies up to 82%

SDesigned in accordance with ANSI Z21.47 (design and test standard for gas furnaces) and ANSI Z233.1 (National Fuel Gas

code relating to appliance installation requirements)

SInduced draft combustion

SRedundant gas valve, with up to 2 stages of heating S Flame roll-out safety protector

S Solid-state electronic direct spark ignition system

Image 1