HTR Ð Heater

*AFS1 deenergizes control circuit if loss of outdoor air occurs. ²Factory-supplied option.

Fig. 35 Ð Major Component Identi®cation (Typical 12-Zone Unit Shown).

When OAT is open, ®nal stage heating element in all zone modules is inactive. When OAT is closed, ®nal stage heating element in a zone module may be energized whenever second- stage thermostat for that zone module calls for heat as follows:

UNITS WITH 2-ELEMENT HEATERS

First-Stage Heat Ð One element energized

Second-Stage Heat

OAT Open Ð One element energized

OAT Closed Ð Two elements energized

UNITS WITH 3-ELEMENT HEATERS

First-Stage Heat Ð One element energized

Second-Stage Heat

OAT Open Ð Two elements energized

OAT Closed Ð Three elements energized

Optional Glycol Heating Coils Ð Start up glycol solution supply system in accordance with equipment manu- facturer's instructions. Solution supply temperature must not exceed 200 F. Maximum solution ¯ow through each zone module heating coil is 6 gpm.

Zone Air¯ow Adjustment Ð Adjust each zone duct balancing damper to provide required air¯ow to each zone. Increasing or decreasing air¯ow to one zone may cause a change in the air¯ow to other zones. After initial damper settings have been made, repeat the adjustment procedure, as required, to be sure ®nal desired air¯ows are achieved. Do not go below 600 cfm or above 1200 cfm per zone module.

Be sure that temperature rise is within range shown on unit instruction plate and Table 1 (48MA only).

Sequence of Operation Ð When unit power is on and no zone thermostat is calling for cooling or heating, the evaporator fan and crankcase heater(s) are on. The outdoor- air dampers are at the pre-set position.

COOLING Ð On a call for cooling from a zone thermostat, compressor no. 1, with unloader(s), starts; the liquid line so- lenoid for that zone evaporator coil opens; and condenser- fan motor no. 1 starts. Compressor will load or unload in response to suction pressure as required. As additional cool- ing is required (i.e., more zones call for cooling), compres- sor no. 2 (no unloaders) will be energized (024-040 units only). If required, compressor no. 1 will unload when com- pressor no. 2 (024-040 units only) is energized. As cooling requirements decrease, capacity control pressurestats pre- vent compressor no. 1 from shutting down while compres- sor no. 2 (024-040 units only) is in operation. Compressor no. 1 will fully load up after compressor no. 2 (024-040 units only) shuts down as required to match heat load.

If heat load is not sufficient to maintain operation of com- pressor no. 1 in an unloaded condition, hot gas bypass valve will meter hot gas to outdoor air evaporator coil to supply additional load. On 48MA and 50ME040, hot gas is intro- duced into evaporator whenever required to eliminate un- loader short-cycle operation.

The Motormaster head pressure control device will vary speed of condenser-fan motor no. 1 to regulate air¯ow across condenser coil. As required, condenser-fan motor no. 2 (no. 2 and 3 on 3-fan units) will cycle on and off in response to head pressure via a cycling pressurestat. See Head Pres- sure Control section on page 40.

38

Image 38
Contents Installation, Start-Up Service Instructions ContentsSafety Considerations InstallationBase Unit Physical Data and Dimensions 48MA Units Base Unit Physical Data and Dimensions 50ME Units Removing Shipping Shields Fig Roof Curb DetailPhysical Data Roof Curb Physical Data and Dimensions 48MA Units Roof Curb Physical Data and Dimensions 50ME Units Shipping Shield Locations Units Shown Suggested Gas Piping 48MA Unit 48MA Electrical Data Unit 50ME Electrical Data Unit 50ME Electrical Application Data Field Control Wiring ECTZone Control Board Component Location Cooling Cooling Stage 1 Ð First stage of modules 1, 2, Cooling Stage 1 Ð First stage of modules 1, 2, 3, Cooling Stage 1 Ð Modules 1 and 3 Stage 2 Ð Modules 2 Cooling Modules Setting Stage 1 Ð First stage of modules 1 Cooling Stage 1 Ð First stage of modules 1, 2, Cooling 50ME Two-Stage Heat, One-Stage Cool Ð 4 Module Joint Control Cooling Stage 1 Ð Modules 1 and 3 Stage 2 Ð Modules 2 Cooling Modules Setting HA1 HA2 START-UP APSGas Heat Lighting Procedure 48MA AdjustmentPressure Adjustment Natural GAS MGVSpoiler Screw Location Units with 2-ELEMENT Heaters Units with 3-ELEMENT HeatersCabinet Panels and Grilles ServiceAir¯ow Switches Condenser and OUTDOOR-AIR Cooling CoilsTo ADD or Remove OIL Compressor Capacity Control UnloadersHead Pressure Control LOW ChargeFAN Shaft Bearing Removal Condenser FansEvaporator Fans and Motor Pulley Removal Forced-Draft Blower 48MAOptional Economizer Ð See Fig OperationEconomizer and Exhaust Damper Assemblies, Exploded View Page Page Packaged Service Training Page PRE-START-UP OUTDOOR-AIR TemperatureRETURN-AIR Temperature Model no Serial no Date Technician

48MA/50ME016-040 specifications

The Carrier 48MA/50ME016-040 series represents a significant advancement in the field of commercial HVAC systems, designed to provide reliable, efficient, and effective climate control solutions for various applications. These units are widely recognized for their durability and performance, making them a top choice for building owners and managers seeking optimal comfort and energy efficiency.

One of the main features of the Carrier 48MA/50ME series is its advanced scroll compressor technology. The scroll compressors are known for their reliability and efficiency, which leads to reduced energy consumption and lower operating costs. This high-efficiency design not only contributes to significant energy savings but also minimizes noise levels, enhancing the overall comfort of the environment.

The units are equipped with a unique microprocessor-based control system that offers precise temperature control and flexibility. This technology allows for easy integration with building management systems, enabling users to monitor and control their HVAC systems remotely, thereby optimizing performance and energy use. The programmable thermostats help to tailor the operation of the units to meet the specific needs of the users, ensuring maximum comfort at all times.

In addition to its robust performance features, the Carrier 48MA/50ME series also boasts a comprehensive line of options for customization. These options include various cooling capacities ranging from 16 to 40 tons, allowing the equipment to cater to different building sizes and requirements. The series is also designed with a compact footprint, making it suitable for rooftop installations where space is at a premium.

Another important characteristic of the series is its environmentally friendly refrigerant options. Carrier prioritizes the use of refrigerants with low global warming potential, contributing to a more sustainable approach to HVAC solutions. This commitment to environmental responsibility not only complies with regulations but also meets the increasing demand for greener technologies.

Furthermore, the robust construction of the Carrier 48MA/50ME series ensures long-lasting performance in even the harshest conditions. The units are designed to withstand various environmental factors, making them ideal for both commercial and industrial applications. Overall, the Carrier 48MA/50ME016-040 series stands out as a reliable choice for efficient and effective heating and cooling solutions, equipped with innovative technologies that prioritize performance, sustainability, and user comfort.