White Rodgers 50A65-843 Timing Specifications, Electrical Ratings @ 77F 25C, Humidity Range

Page 2

SPECIFICATIONS

ELECTRICAL RATINGS [@ 77°F (25°C)]:

Input Voltage: 25 VAC 50/60 Hz

Max. Input Current @ 25 VAC: 0.45 amp

Relay Load Ratings:

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf

Ignitor Relay: 2.0 amp @ 120 VAC 50/60 Hz (resistive)

Flame Current Requirements:

Minimum current to insure flame detection: 1 µa DC*

Maximum current for non-detection: 0.1 µa DC*

Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead

OPERATING TEMPERATURE RANGE: -40° to 175°F (-40° to 80°C)

HUMIDITY RANGE:

5% to 93% relative humidity (non-condensing)

MOUNTING:

Surface mount multipoise

 

Timing Specs: (@ 60 Hz**)

 

 

maximum

Flame Establishing Time:

0.8 sec

Flame Failure Response Time:

2.0 sec

**At 50 Hz, all timing specifications should be increased by 20%

Gases Approved: Natural, Manufactured, Mixed, Liquified Petroleum, and LP Gas Air Mixtures are all approved for use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise)

 

50A65-843

 

 

PRE-PURGE

30

 

 

IGNITOR WARM-UP

20

 

 

IGNITION ACTIVATION

1

PERIOD

 

 

 

TRIAL FOR IGNITION

4

PERIOD

 

 

 

RETRIES

2 times

 

 

VALVE SEQUENCE PERIOD

12

 

 

INTERPURGE

60

 

 

POST-PURGE

15

 

 

LOCKOUT TIME

300

 

 

HEAT DELAY-TO-FAN-ON*

30, 45

 

 

HEAT DELAY-TO-FAN-OFF*

60/90/

120/180

 

 

 

COOL DELAY-TO-FAN-ON

5

 

 

COOL DELAY-TO-FAN-OFF*

45, 90

 

 

AUTO RESET

60 minutes

 

 

HUMIDIFIER

YES

 

 

ELECTRONIC AIR CLEANER

YES

 

 

*These times will vary depending on option switch position. The control is factory-set at 30 seconds heat delay- to-fan-on, 180 seconds heat delay-to- fan-off and 45 seconds cool delay-to- fan-off. See OPERATION section for further information.

2

Image 2
Contents Contents Installation InstructionsPrecautions DescriptionElectrical Ratings @ 77F 25C SpecificationsTiming Specifications Humidity RangeInstallation Mounting and WiringTypical System Wiring Diagram Typical System Wiring Table Terminal System Component Type ConnectionCool Mode Operation Option SwitchesHeat Mode Manual FAN on ModeDiagnostic Features System Lockout Diagnostic FeaturesSystem Lockout Features Mounting Hole Template For Mounting Hole Locations

50A65-843 specifications

The White Rodgers 50A65-843 is a sophisticated and reliable universal gas valve designed for gas-fired heating systems. It is widely praised for its versatility and performance across a variety of residential and commercial applications. One of its main features is its ability to accommodate both natural gas and propane, allowing homeowners and installers flexibility in fuel choice. The 50A65-843 also supports various types of heating systems, including furnaces, boilers, and other gas appliances.

A key technological highlight of the White Rodgers 50A65-843 is its microprocessor-based control. This advanced technology enables precise regulation of gas flow and enhanced ignition control, ensuring optimal efficiency and safety in operation. The valve is equipped with an integrated flame sensing system, which continuously monitors the flame presence and adjusts gas flow accordingly. This not only improves the unit's reliability but also contributes to energy savings and reduced emissions.

The valve is designed with user-friendly features that simplify installation and maintenance. The standardized dimensions and connection configurations make it compatible with a wide range of existing systems, reducing the need for extensive retrofitting. Additionally, color-coded wiring and clear labeling facilitate quick and easy electrical connections, making it an ideal choice for HVAC technicians.

The 50A65-843 also boasts a high level of durability and robustness. It is built with premium materials that can withstand harsh operating conditions, ensuring a long service life. The unit has been rigorously tested for performance and reliability, meeting or exceeding industry standards.

Moreover, the White Rodgers 50A65-843 includes safety features such as a redundant safety shut-off. This feature is critical in preventing gas leaks and ensuring user safety by shutting off gas flow in the event of a malfunction.

In summary, the White Rodgers 50A65-843 gas valve is a versatile and highly efficient component that is easy to install and maintain. Its advanced control technologies, safety features, and robust construction make it a preferred choice for both professionals and homeowners looking for reliable heating solutions. With its proven performance and adaptability, the 50A65-843 continues to set a high standard in the HVAC industry.