Desa (V)V36PA(1) installation manual Connecting Fireplace to GAS Supply, Checking GAS Connections

Page 20

20

FIREPLACE INSTALLATION

Connecting Fireplace to Gas Supply Checking Gas Connections

FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

To Gas Supply

(Natural)Equipment

Shutoff Valve

To External

Control Valve

Regulator

(Propane/LP)

 

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34, for propane/LP or Fig- ure 35, page 21, for natural gas). Apply noncorrosive leak de- tection fluid to all joints. Bubbles forming show a leak. Cor- rect all leaks at once.

Flexible Gas Line Do NOT Kink

Equipment

Open

Shutoff

 

Valve

 

Figure 32 - Connecting Flexible Gas Line to Millivolt Valve

Closed

Figure 33 - Equipment Shutoff Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

Propane/LP

Equipment

Supply Tank

Shutoff

 

Valve

 

Gas Valve

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

For..com

111252-01B

Image 20
Contents For Your Safety What to do if YOU Smell GAS OWNER’S Operation Installation ManualFor Your Safety Table of Contents Safety InformationSafety Information Product Identification Local CodesLocation and Space Requirements Product FeaturesPRE-INSTALLATION Preparation Clearances Framing and FinishingLocation of Termination CAP Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Horizontal Termination InstallationInstalling Horizontal Vent Cap Noncombustible Exterior Horizontal Termination Configurations Ground Floor InstallationCorner Installation Venting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationVertical Termination Configurations High Altitude Installation Number DescriptionDesa Terminations Desa Venting AccessoriesDesa Elbows Fireplace Installation Installing Optional Blower AccessoriesModel BK Installation Check GAS TypeModel BKT Installation Blower Wiring DiagramInstalling GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Installation Items NeededPressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Remote Receiver Installing Optional Wall Mount Switch GWMS2Pressure Testing Fireplace Gas Connections Removing Glass Doors REMOVING/REPLACING Glass DoorRemoving Louver Panels Cleaning Glass Door Installing Rear Brick PanelInstalling LOGS, Lava Rock and Glowing Embers Installing Log No Installing Log NoFor Your Safety Read Before Lighting Manual Lighting ProcedureOperating Fireplace Lighting InstructionsON/OFF Series Models Ghrcb and Cghrctb Optional HAND-HELDRemote Operation Cghrctb Operating Optional Blower Accessory Pilot AssemblyInspecting Burners Operating Optional GWMT1 Wall Mounted ThermostatCleaning and Maintenance Glass DoorPilot and Burners LogsTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Illustrated Parts Breakdown Parts List CHDV36NRA Description QTY#56 KEY Part Number Description QTY Replacement Parts Service HintsTechnical Service SpecificationsOwners Registration Form Postage Required Accessories Warranty Information