FMI FMH26TP Connecting to GAS Supply, Extension Cord, Attaching Wood Base to Solid Floor

Page 14

PROPANE/LP VENT-FREE FIREPLACE SYSTEM

INSTALLATION

Continued

Extension Cord

Use extension cord if needed. The cord must have a three-prong, grounding plug and a three-hole receptacle. Make sure cord is in good shape. It must be heavy enough to carry the current needed. An undersized cord will cause a drop in line voltage. This will result in loss of power and overheating. Use a No. 16 AWG cord for lengths less than 50 feet.

Attaching Wood Base to Solid Floor

For attaching base to solid floors (concrete or masonry)

Note: Floor anchors and mounting screws are in hardware package. The hardware pack- age is provided with fireplace.

1.Drill holes at marked locations using 5/16" drill bit. For solid floors (concrete or masonry), drill at least 1" deep.

2.Fold floor anchor as shown in Figure 22.

3.Insert floor anchor (wings first) into hole. Tap anchor flush to floor.

4.Insert mounting screws through base and into floor anchors.

5.Tighten screws until base is firmly fas- tened to floor.

Figure 22 - Folding Anchor

CONNECTING TO GAS SUPPLY

WARNING: This appliance re- quires a 45° male flare fitting 5/8"- 18 UNF (Unified National Fine Thread) inlet connection and the flexible gas line provided.

WARNING: A qualified ser- vice person must connect fire- place to gas supply. Follow all local codes.

CAUTION: Never connect fire- place directly to the propane/LP supply. This fireplace requires an external regulator (not sup- plied). Install the external regula- tor between the fireplace and pro- pane/LP supply.

The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regu- lator with the vent pointing down as shown in Figure 23. Pointing the vent down pro- tects it from freezing rain or sleet.

External Regulator

Propane/LP

Supply Tank

Vent Pointing Down

Figure 23 - External Regulator with Vent Pointing Down

CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" or greater diameter to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 24).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

CSA Design-Certified

Equipment Shutoff Valve

With 1/8" NPT Tap*

 

From

 

External

 

Regulator

 

(11" W.C. to

3" Minimum

14" W.C.

Pressure)

Pipe Nipple Cap Tee Joint

Sediment Trap

Figure 24 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 27.

14

107106

Image 14
Contents Compact Heat Majic What to do if YOU Smell GASSafety Information PROPANE/LP VENT-FREE Fireplace SystemProduct Identification Product FeaturesLocal Codes UnpackingAssembling Fireplace AssemblyInstalling Log Assembling HoodUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Check GAS Type InstallationInstallation Items Locating FireplaceBUILT-IN Fireplace Installation Rough Opening for Installing in WallOptional Mantel Installation Mantel Clearances for Built-In InstallationInstalling Blower Assembly Installing Blower Accessory GA3450TRemoving Upper Louver Assembly Assembling Brass Trim Brass trim shipped with mantelPlug fan kit into 120-Volt For Built-In Installation Wiring Diagram For Blower Accessory Built-In InstallationAttaching Wood Base to Solid Floor Connecting to GAS SupplyExtension Cord Connecting Equipment Shutoff Valve to Heater Control Installation Items NeededChecking GAS Connections Pressure Testing Fireplace GAS ConnectionsPressure Testing Gas Supply Piping System Lighting Instructions For Your Safety Read Before LightingOperating Fireplace Inspecting Burner Burner Flame Pattern Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole CabinetTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Service Hints SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown FMH26TPParts List Description QTYAccessories 107106 Warranty Information