Nortec 380V installation manual Condensate Return Lines, Primary Voltage Connection

Page 8

(8)For electric humidifiers (NHTC & NHPC only) using a small size blower pack (<30 lbs/hr), steam lines require 7/8” O.D. (Nominal ¾”) copper tubing. For steam runs longer than 20 ft, use insulated nominal 1” copper to ensure draining of condensate.

(9)When using the GS, SE, or NHRS Humidifiers with a RO / DI water supply, all steam lines should be in stainless steel.

(10)Do not use plastic pipe for steam distribution or hose other than NORTEC supplied. Substitution will void warranty.

(11)If steam line is routed below the blower pack, or if the blower pack is lower than the humidifier, a condensate trap “tee” will be required to remove water at this low point. Run the condensate from the trap to the nearest drain lower than the blower pack. See Figure 5 Condensate Removal.

(12)Do not run the steam line more than 1 foot per lb/hr output. Example, 10 lbs/hr should not have a steam run longer than 10 feet. If long runs are unavoidable, the humidifier should be sized larger to compensate for condensate losses and insulated stainless steel or copper must be used.

D.CONDENSATE RETURN LINES

(1)NORTEC blower packs have built-in connections for draining off condensate. These condensate lines must be connected to the nearest floor drain, back to the unit (NHTC & NHPC, NHRS only) or a condensate pump when using short condensate runs.

(2)Always incorporate a trap in routing of condensate return lines. Condensate that accumulates in trap will prevent possibility of steam escaping. Depth of the trap must be equal or more than 3” (76 mm) See Figure 6 Condensate Return Line Trap.

(3)Ensure the trap is at least 3 feet (1 m) below the blower pack and as close to the floor drain as possible.

E.PRIMARY VOLTAGE CONNECTION

(1)All blower packs for SE and GS unit are wired by others to be powered by an independent circuit. Follow all codes.

(2)A control thermostat, mounted on the blower pack, automatically starts the fans when steam is detected.

(3)NH Series remote mounted blower packs wired to a humidifier or independent circuit require field wiring between two primary voltage terminal blocks and two low voltage control (class 1 circuit wiring required) terminal strips; one of each located in humidifier and remote blower pack cabinet. Knock-outs are provided on the humidifier to facilitate this. To connect the primary and control (class 1 circuit wiring required) wiring, the wiring is fed through the grommet provided in the bottom of the blower pack.

(4)Field wiring of remote blower packs must conform to national and local electrical codes. Refer to wiring diagram supplied at the back of this manual (See page 9).

10-00

Page 5 2008-04-28

Image 8
Contents Blower Packs Proprietary Notice Liability Notice List of Figures Overview Overview Blower PackRemote Mounted Blower Packs Wall Mounting Remote Mounted Blower Packs Steam LineSteam Line Installation Condensate Return Lines Primary Voltage Connection10-00 Physical Data Dimensions Rmbp Blower Pack Spare Parts & Exploded View Rev. C April 17 Part Number Description Qty Wiring Diagram 2524117 Rev. B March 26 This page Intentionally Left Blank Warranty Authorized Agent

380V specifications

Nortec 380V is a high-performance industrial solution designed to optimize power distribution and management in various applications. This technology stands out due to its robust features, advanced functionalities, and versatility, making it a preferred choice among industries looking for efficient energy solutions.

One of the main features of Nortec 380V is its ability to handle high voltage and current levels while maintaining safety and reliability. With a three-phase system, it ensures a balanced load distribution, reducing the risk of overload and enhancing the overall performance of connected equipment. The system is engineered to provide consistent power quality, minimizing voltage drops and harmonics, which are critical for sensitive loads often found in manufacturing environments.

Nortec 380V employs modern technologies to improve efficiency and reliability. The integration of smart monitoring systems allows operators to track real-time performance metrics, enabling proactive maintenance and minimizing downtime. This technology not only extends equipment lifespan but also helps businesses reduce operating costs significantly.

Additionally, Nortec 380V features advanced protection mechanisms that safeguard against various electrical faults. These include overvoltage, undervoltage, short circuits, and phase imbalances, ensuring that equipment is protected and operational continuity is maintained.

The modular design of the Nortec 380V makes it highly adaptable to different industrial settings. It can be easily integrated into existing infrastructure, allowing for scalability as production needs grow. Furthermore, its compact footprint means it can fit into tight spaces without compromising performance.

Another notable characteristic of Nortec 380V is its environmental sustainability. The system is designed to operate efficiently, thereby reducing energy consumption and lowering carbon footprints. This aligns with the growing emphasis on eco-friendly practices within the industrial sector.

In conclusion, Nortec 380V represents a significant advancement in industrial power solutions. By combining high voltage handling capabilities, smart monitoring, robust protection features, and sustainability considerations, it addresses the critical needs of modern industries. As energy demands grow and technology evolves, Nortec 380V stands out as a reliable and efficient choice for power management, ensuring that businesses can operate smoothly and sustainably.