10 SPECIAL FUNCTION

10-1. Rotation Function (and back-up function, 2nd stage cut-in function)

This function is only available when using wired remote controller.

10-1-1. Operation

(1)Rotation function (and Back-up function) Outline of functions

·Main and sub units operate alternately according to the interval of rotation setting.

w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)

Refrigerant address "00" Main unit

Refrigerant address "01" Sub unit

· When error occurs to one unit, another unit will start operation. (Back-up function)

System constraint

·This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant groups. (Refer to Fig. 1)

·Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit should also be connected. (Refer to Fig. 1)

(This function cannot be set by IR wireless remote controller.)

·Set refrigerant address of each unit. (Dip switch on the outdoor unit ··· Refrigerant address 00/01)

Operation pattern

[Back-up function only]··· Request code number "312"

 

 

Start operation

Error occurs on main unit.

 

 

Main Sub

Main

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

Abnormal condition

 

 

Run

 

IC-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

 

 

 

 

unit

 

 

Stop

 

Run

IC-2

 

 

 

 

 

 

 

 

 

 

 

[Rotation function] & [Back-up function]··· Request code number "313~318"

Error occurs on main unit.

Fig. 1 Refrigerant address

 

"00"

 

 

 

 

 

 

 

 

 

 

 

 

OC-1

 

 

Main

 

 

 

 

 

 

3(2)

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC-1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

2

 

 

 

 

 

 

 

 

RC

 

 

 

 

 

 

 

 

 

 

Refrigerant address "01"

OC-2

Sub

3(2) unit

IC-2

Start operation

Main Sub

Sub Main Main Sub

OC : Outdoor unit

Main

unit

IC-1

Sub unit IC-2

Run

Stop

1~28 days

Stop

Run

1~28 days

Run

Stop

Abnormal condition

Run

IC : Indoor unit

RC : Wired remote controller

(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)

Note:

·When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start oper- ation.

·To operate the main unit, refer to the 10-1-2. and set the request code No. which is not the same as the current one, and set again the former request code No.

(2)2nd stage cut-in function Outline of functions

·When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.

·Once the actual room temperature goes down to 4 degrees C (7.5 degrees F) below set point*, the 2nd unit stops operation automatically.

(* set point = set temperature by R/C (remote controller) + 4, 6, 8:(7.5, 10.8, 14.4°F) (selectable))

·Number of operating units is determined according to the room temperature and set point.

·When room temperature becomes higher than set point, standby unit starts. (2 units operation)

·When room temperature falls below set point -4:(-7.5°F), standby unit stops. (1 unit operation)

26

Image 26
Contents Contents Parts Catalog OCB483Reference Manual Service Ref PUZ-A18/24/36NHA4Remote controller Optional parts PUZ-A18/24/36NHA4-BS PUY-A12/18/24/36NHA4Safety Precaution Always Observe for SafetyRefrigerant recovery equipment Part Names and FunctionsDisplay Section Operation SectionTemperature setting display Operation Mode displayMode Select button Timer displaySpecifications Service RefNoise Criterion Curves PKA-A12HA4 PKA-A18HA4Outlines and Dimensions Unit inch mmWiring Diagram TB5Refrigerant System Diagram Heat exchangerTroubleshooting TroubleshootingCase of trouble during operation MALFUNCTION-DIAGNOSIS Method by Remote ControllerWired remote controller U9,UH Appear even when operation Wired remote controller LED 1, 2 PCB in outdoor unitUnit’s power terminal block L1, L2, GR Remote controller wire shortSELF-DIAGNOSIS Action Table Pipe temperature OperatingErrorE0/signal receiving errorE4 Cause Countermeasure Pipe temperature thermistorRemote controller transmission Condenser-Evaporator TH5Remote controller control board Error Signal receiving errorError Transmitting error Indoor/outdoor unit communicationPerformance failure Troubleshooting by Inferior PhenomenaPhenomena Cause Countermeasure 1Upward/downward vane ControllerHeat pump type When the remote controller cannot be usedEmergency Operation Cooling Only typeCondenser/evaporator temperature HOW to Check the Parts PKA-A12HA4 PKA-A18HA4Lower temperature ThermistorSensor signal check Test Point Diagram Functions of DIP Switch and Jumper Wire Rotation function and Back-up function Outline of functions Special FunctionOperation System constraint2nd stage cut-in setting Request Code ListRotation setting 2nd unit Cut-outBACK-UP Heating Function CN152 How to connectSetting method of each function by wired remote controller Outline of functionsPhoto Disassembly ProcedureOperation Procedure Photos & Illustrations Forward to remove the front panel. See PhotoOperation Procedure Photos Vane Motor and Drain Hose Operation ProcedureRemoving the Nozzle Assembly with Vane Photo Remove the electrical box cover Remove the room temperature thermistorDisconnect the connector CN20 on the indoor controller BoardPage Page Page New publication, effective Nov

PKA-A18HA4, PKA-A12HA4 specifications

Mitsumi Electric Company is known for its innovations in the electronic components sector, and among its noteworthy products are the PKA-A18HA4 and PKA-A12HA4 components. Both models represent advancements in their respective categories, characterized by reliability, high performance, and cutting-edge technology.

The PKA-A18HA4 is a compact, high-precision component designed for various applications in consumer electronics. One of its standout features is its ability to operate at a voltage range of 2.7V to 5.5V, making it versatile for different devices. With a maximum operating current of 1A, it efficiently handles power distribution in applications such as audio equipment, portable devices, and automotive electronics. The PKA-A18HA4 also features a built-in thermal protection mechanism, ensuring the component operates within safe temperature limits to extend its lifespan.

Similarly, the PKA-A12HA4 is tailored for applications requiring low power consumption without compromising performance. It operates within a voltage range of 2.4V to 3.6V, making it ideal for battery-operated devices. This model not only offers an excellent balance between power efficiency and performance but also incorporates a range of built-in safety features, including over-voltage and short-circuit protection. These features enhance the reliability of devices utilizing the PKA-A12HA4 in environments where electrical fluctuations may occur.

Both models are also characterized by their compact footprint, allowing for easy integration into various electronic systems. Their designs prioritize minimal electromagnetic interference, which is crucial for maintaining signal integrity in sensitive applications. Additionally, they are manufactured using advanced semiconductor technologies that ensure high durability and robustness.

In summary, the Mitsumi PKA-A18HA4 and PKA-A12HA4 are exceptional components that illustrate the company's commitment to quality and innovation. Their unique features, including wide operating voltage ranges, safety mechanisms, and compact designs, make them suitable for a variety of applications across multiple industries. As technology continues to advance, these products embody the standards of performance and reliability that consumers expect from modern electronic components.