Mitsumi electronic PUHY-P-TGMU-A Specifications, Confirmation of parts attached, Lifting method

Page 8

3. Specifications

 

 

Model

 

PUHY-P72

PUHY-P96

PUHY-P108

PUHY-P126

PUHY-P144

 

 

Noise level (50/60 Hz)

56 dB<A>

57 dB<A>

60 dB<A>

61 dB<A>

61 dB<A>

 

 

External static pressure

 

 

0 Pa

 

 

 

 

Indoor units

Total capacity

 

 

50 ~130 %

 

 

 

 

 

Model

 

 

06 ~ 96

 

 

 

 

 

Quantity

1 ~ 13

1 ~ 16

1 ~ 19

1 ~ 20

1 ~ 22

 

 

Operation

Standard type

Cooling mode: – 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position)

 

 

temperature

 

Heating mode: – 20 °CWB ~ 15.5 °CWB [– 4 °FWB ~ 60 °FWB]

 

 

 

 

 

Fresh air intake

Cooling mode: 21 °CDB ~ 43 °CDB [70 °FDB ~ 109 °FDB]

 

 

 

 

 

type

Heating mode: – 12.5 °CWB ~ 20 °CWB [10 °FWB ~ 68 °FWB]

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

PUHY-P168

PUHY-P192

PUHY-P204

PUHY-P216

PUHY-P234

 

 

Noise level (50/60 Hz)

61 dB<A>

62 dB<A>

62 dB<A>

62.5 dB<A>

63 dB<A>

 

 

External static pressure

 

 

0 Pa

 

 

 

 

Indoor units

Total capacity

 

 

50 ~130 %

 

 

 

 

 

Model

 

 

06 ~ 96

 

 

 

 

 

Quantity

1 ~ 24

1 ~ 24

1 ~ 24

1 ~ 32

1 ~ 32

 

 

Operation

Standard type

Cooling mode: – 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position)

 

 

temperature

 

Heating mode: – 20 °CWB ~ 15.5 °CWB [– 4 °FWB ~ 60 °FWB]

 

 

 

 

 

Fresh air intake

Cooling mode: 21 °CDB ~ 43 °CDB [70 °FDB ~ 109 °FDB]

 

 

GB

 

 

 

 

 

 

type

Heating mode: – 12.5 °CWB ~ 20 °CWB [10 °FWB ~ 68 °FWB]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Confirmation of parts attached

 

 

 

 

 

(Unit : mm [in])

 

 

1 Conduit mounting plate (ø53 [2-3/32])

2 Conduit mounting plate (ø46 [1-13/16])

3 Conduit mounting plate (ø33 [1-5/16])

4 Conduit mounting plate (ø27 [1-3/32])

Model

P72

1 pc.

1 pc.

 

P96 ~ P108

1 pc.

1 pc.

 

P126 ~ P234

1 pcs.

1 pc.

 

 

5 Tapping screw M4

6 Connecting pipe (Flare)

7 Connecting pipe (Flange)

8 Packing (inside ø23 [29/32],

 

 

 

 

 

outsideø35 [1-13/32])

Model

P72

2 pcs.

1 pc.

 

P96 ~ P108

2 pcs.

1 pc.

1 pc.

 

P126 ~ P234

2 pcs.

1 pc.

1 pc.

5. Space required around unit

[Fig. 5.0.1] (P.2)

<A> Top view

 

 

<B> Side view

<C> When there is little space up to an obstruction

A Front

B No restrictions on wall height (left and right)

C Air outlet guide (Procured at the site)

D Must be open

E Wall height (H)

F No restrictions on wall height

 

(Unit : mm [in])

 

L1

L2

 

 

450 [17-23/32]

100 [3-15/16]

 

 

(4) When unit is surrounded by walls

Note:

Wall heights “H” of the front and the back sides shall be lower than either the front or the back panel.

If the panel height is exceeded, add the “h” dimension of the Fig. 5.0.1 to L1 and L2.

(Unit : mm [in])

L1L2

450 [17-23/32] 100 [3-15/16]

(1)Basic space required

(2)When there is an obstruction above the unit

(3)When inlet air enters from right and left sides of unit

Wall heights “H” of the front and the back sides shall be within total height of unit.

When wall height “H” exceeds total height of unit, add “h” dimension to L1 and L2 of the Fig. 5.0.1.

“h” = wall height “H’” – total height of unit

Example: When the “h” dimension is 100 mm [3-15/16in],

the L1 dimension becomes 450 [17-23/32] + 100 [3-15/16] = 550 mm [21-21/32in].

(5) Collective installation and continuous installation

Space required for collective installation and continuous installation:

When installing several units, provide the space between each block consider- ing passage for air and people.

Open in two directions.

In case of wall height “H” exceeds total height of unit, add “h” dimension (h = wall height “H’” – total height of unit) to * marked dimension.

6. Lifting method

If there is a wall at both the front and the rear of the unit, install up to four units (Every three units in the case of P168 ~ P234.) consecutively in the side direc- tion and provide a space of 1000 mm [39-3/8in] or more as inlet space/pas- sage space for each four units (Every three units in the case of P168 ~ P234).

[Fig. 6.0.1] (P.2)

Caution:

Be very careful to carry product.

-Do not have only one person to carry product if it weighs more than 20 kg [46LBS].

-PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.

-Do not touch heat exchanger fins with your bare hands. Otherwise you may cut your hands.

-Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.

-When carrying outdoor unit, be sure to support it at four points. Carrying with 3-point support may make outdoor unit unstable, resulting in it falling.

8

Image 8
Contents PUHY-P-TGMU-A Unit mm B c No.1 No.2 No.3 No.4 No.5 No.1 No.2P96 Ø22.2 7/8SO S 10.2 10.310.4 ~208-230VContents Safety precautionsBefore installation Before installation electrical workAbout the product Before starting the test runSpecifications Collective installation and continuous installationConfirmation of parts attached Space required around unitInstallation of unit Refrigerant piping installationInstallation Refrigerant piping systemExampleFig .2.1 P.3 Additional refrigerant chargeCalculation of additional refrigerant charge Airtight test, evacuation, and refrigerant charging Thermal insulation of refrigerant pipingAirtight test Only use refrigerant R410AWiring transmission cables WiringControl box and connecting position of wiring Wiring of main power supply and equipment capacity Wiring examplesSchematic Drawing of Wiring Example Transmission boosterTest run Following phenomena do not represent trouble emergencyInformation on rating plate 222 237 279 463WT04551X01

PUHY-P-TGMU-A specifications

The Mitsumi Electronic PUHY-P-TGMU-A is a cutting-edge multi-split air conditioning system that adopts advanced technologies to enhance indoor comfort and energy efficiency. Designed for both residential and commercial use, this unit stands out due to its innovative features and remarkable performance capabilities.

One of the key characteristics of the PUHY-P-TGMU-A is its ability to effectively cool or heat multiple spaces simultaneously. With a capacity range that meets the demands of diverse environments, this system can seamlessly cater to larger installations. This makes it ideal for office buildings, retail spaces, or homes with multiple rooms requiring climate control.

The unit is equipped with inverter technology, which allows for variable speed operation of the compressor. This not only results in significant energy savings but also provides a stable temperature and optimal comfort levels. The inverter technology adjusts the power consumption based on the cooling or heating requirements in real-time, thereby reducing energy costs and increasing overall efficiency.

Another outstanding feature is the advanced air filtration system. The PUHY-P-TGMU-A incorporates a combination of pre-filters and HEPA filters that effectively reduce airborne particles, allergens, and pollutants. This ensures that the air circulated within the environment remains clean and healthy, making it an excellent choice for those with respiratory sensitivities.

In addition, the unit comes with smart connectivity options. Users can control the system remotely through a smartphone app, allowing for seamless adjustments to settings from anywhere at any time. This smart technology not only enhances convenience but also enables users to monitor energy consumption and adjust schedules to maximize efficiency when spaces are unoccupied.

Thermal management technologies integrated into the PUHY-P-TGMU-A ensure rapid and effective heat exchange, further improving performance. Its sleek design and compact dimensions allow for flexible installation, making it suitable for a variety of architectural styles.

The PUHY-P-TGMU-A is not only about performance; it emphasizes quiet operation too. The design minimizes noise levels, ensuring that the atmosphere remains tranquil even during peak operation.

In summary, the Mitsumi Electronic PUHY-P-TGMU-A combines sophisticated technology, energy efficiency, and user-friendly features to create a versatile and highly effective climate control solution. Whether for personal or business use, this multi-split air conditioning system proves to be an investment in comfort and innovation.