American Power Conversion DX, FM manual Respond to Alarms

Page 62

Respond to Alarms

When an alarm is triggered, the Main Module alerts you through the display by the following methods:

Alarm beeper

Major or minor alarm LED

Active alarm screen

Alarm and event logs

Major or minor alarm LEDs

When an alarm is triggered, the Check Log LED and either the Minor Alarm LED or the Major Alarm LED activates. The Major and Minor Alarm LEDs cannot be deactivated manually; the alarm condition must be cleared to deactivate them.

Control beeper

Path: Main > Respond to Alarms

An active alarm creates a beeping sound from the display. This sound continues until you view the Respond to Alarms menu.

Beeper. To disable the beeper for all future alarms, set the Beeper setting to Disabled.

Beeper Volume. Set the volume of the beeper and key-click to high, medium, or low.

View active alarms

Path: Main > Respond to Alarms > View Active Alarms

The Active Alarms screen also appears on the scrolling status screens. It provides the number of the alarm (e.g., 1 of 2), a description of the condition, and a time-stamp indicating when the alarm occurred. Press the ENTER key to view details of the alarm, or press the arrow keys to view the rest of the list.

See “Entire Log” on page 51 for more information on the alarm/event details screens.

Clear active alarms

Path: Main > Respond to Alarms > Clear Active Alarms

Clears all active alarms. If the conditions that caused the alarm still exist, those conditions cause the alarm to be regenerated.

Clear System Alarms – Clear active alarms that apply to the Modules in this System.

Clear Group Alarms – Clear active alarms that apply to the Group.

Reset System failure

Path: Main > Respond to Alarms > Reset Sys Failure

Reset a System after a failure event has occurred. If the condition that caused the failure still exists, the System will fail again. A System will not restart after a failure until this command is executed.

Note: A System must be reset only if it is part of a Group. Stand-alone Systems will not go into the failure state.

52

NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting

Image 62
Contents Operation, Maintenance, and Troubleshooting Page American Power Conversion Legal Disclaimer Page Contents Commissioning Checklists Alarms Network Management Card Troubleshooting Warranty Page System Modules, Systems, and GroupsModule Group Cross-reference symbols used in this manual Symbols Used in this ManualSafety symbols that may be used in this manual Static discharge Safety HazardsLockout/tagout Electrical hazards Safe refrigerant handling Moving parts Tools and partsOperation Display InterfaceStatus Screen Name Status Information Displayed Using the Display InterfaceScrolling status screens Navigating the interface Password entryMain menu screen Start the System Change settingsFactory default settings Stop the SystemCommissioning Power off Power On/Off ProcedurePower on Commissioning Checklists Initial Inspection ChecklistEnsure that Electrical Inspection ChecklistMechanical and Refrigeration Inspection Checklist Mechanical Inspection Air-cooled Checklist User Interface Box Inspection ChecklistStart-up Inspection Checklist While the equipment is operating, ensure thatFinal Inspection Checklist Owner AcceptanceSystem Configuration System optionsPage Page System delays Sensor setup Building managementSettings for fluid-cooled options Fluid-Coil Type Applicable SettingsValve types Actuator typesEconomizer isolation valve optional Coil fluid temperature activation threshold and deadband Contacts and Relays Input contactsMap Description/Function Output relays Alarm detectors Module ConfigurationConfigure Module Calibrate airflow automatically Module ControlCalibrate airflow manually Set up humidifier Reset Variable Frequency DriveReset humidifier Control the Environment How the modes workPage Setpoints Deadbands Cool Deadband Compressor Allocation Return air relative humidity Modes Essential functionsHow to tune the PIDs PID controlsHumidification sensitivity Loop Behavior PID Tuning CorrectionControl Proportional Integral Derivative Method Humidity alarms AlarmsTemperature alarms Maintenance intervalsAlarm delay Group configuration GroupGroup settings Mode Range Share ifSystem failure events Display Password and time-outTemperature and pressure units Date and timeAdjust display How to update the firmwareReset to defaults Product dataNetwork Configuration Network configurationView Status Readings Module statusSystem status Group statusView Event Log View logRespond to Alarms Alarm messages and suggested actions Displayed Alarm Message Action RequiredDisplayed Alarm Message Action Required Path Main Setup System # System Config Valve Types Check that the # Systems setting Path Main Setup Group Group Module Module Alarm Occurred in Module Control Reset Comm Lost state, or Off Displayed Alarm Message Action Required Displayed Alarm Message Action Required Overview Quick ConfigurationTCP/IP configuration methods APC Device IP Configuration Wizard Bootp and Dhcp configurationOption 43 = 01 04 31 41 50 43 where Remote access to the control console Control console Choose Network from the Control Console menuTelnet/SSH Access a Configured UnitWeb interface Snmp Recover From a Lost Password Environment Monthly Preventive MaintenanceCleanliness Mechanical ElectricalQuarterly Preventive Maintenance  Record the amperages for the following componentsFunctional tests Semi-Annual Preventive Maintenance  Measure the refrigerant pressures Troubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective Action Problem Possible Cause Corrective Action Problem Possible Cause Corrective Action Problem Possible Cause Corrective Action Page Non-transferable warranty Exclusions One-Year Factory WarrantyTerms of warranty Warranty claims Parts Warranty ProceduresClaims Page Page 990-3127 10/2007

DX, FM specifications

The American Power Conversion (APC) DX,FM series represents a cutting-edge solution designed for critical power management and uninterruptible power supply (UPS) applications. Aimed at businesses and data centers that require robust power protection, this series balances high-performance capabilities with advanced technology features.

One of the key distinguishing features of the DX,FM series is its modular design. This allows users to scale their UPS system according to their needs, making it suitable for a variety of environments. Whether you're managing a small server room or a large data center, the modular architecture ensures that you can add or remove capacity with ease. This flexibility not only optimizes initial investments but also supports future growth seamlessly.

The series employs advanced battery technology, which extends battery life and enhances overall performance. With intelligent battery management systems, the DX,FM ensures that battery health is monitored in real-time, preventing premature failures and unnecessary replacements. This leads to reduced maintenance costs and maximizes uptime.

Additionally, the DX,FM series features innovative cooling solutions that enhance performance in high-density situations. Efficient thermal management reduces the risk of overheating, keeping valuable equipment operating optimally. This is particularly crucial in data centers where heat generated by servers can create potential disruptions.

Another significant characteristic of the DX,FM series is its sophisticated monitoring and management capabilities. Integrated with state-of-the-art software, users can gain remote access to their UPS units, enabling real-time tracking of performance metrics. This remote monitoring capability allows administrators to proactively manage power usage and ensure that systems are operating within safe parameters.

Furthermore, the DX,FM series is designed with a high level of redundancy. This built-in reliability feature ensures that if one unit fails, others can seamlessly take over, maintaining power supply continuity. This is critical for mission-critical environments where power outages could result in substantial financial losses or data loss.

In summary, the American Power Conversion DX,FM series incorporates modularity, advanced battery technology, effective cooling solutions, and sophisticated monitoring features to deliver an ideal power management solution for various organizations. Its design prioritizes flexibility, reliability, and efficiency, making it an essential investment for any business looking to safeguard its operations against power disruptions.