Performance Data - Medium Temperature
Model
Compressor
Capacity BTUH @ 90°F Ambient Suction Temperature
25°F | 20°F | 15°F | 10°F | 5°F | 0°F |
BS*010M6 | 9,680 | 8,730 | 7,930 | 7,260 | 6,500 | 5,890 | 5,000 | |
BS*020M6 | 16,890 | 15,110 | 13,590 | 12,260 | 11,070 | 9,940 | 8,690 | |
BS*021M6 | 19,930 | 17,400 | 15,800 | 14,300 | 12,800 | 11,840 | 10,220 | |
BS*030M6 | 30,880 | 28,310 | 25,730 | 23,180 | 20,690 | 18,260 | 15,950 | |
BS*040M6 | 40,810 | 37,350 | 33,810 | 30,250 | 26,730 | 23,250 | 19,900 |
Compressor |
| Capacity BTUH @ 95°F Ambient Suction Temperature |
| ||||||
Model | 25°F | 20°F | 15°F | 10°F | 5°F | 0°F | |||
| |||||||||
BS*010M6 | 9,140 | 8,300 | 7,600 | 6,870 | 6,150 | 5,550 | 4,730 | ||
BS*020M6 | 16,240 | 14,530 | 13,070 | 11,790 | 10,640 | 9,560 | 8,360 | ||
BS*021M6 | 18,850 | 16,500 | 14,900 | 13,500 | 12,700 | 11,140 | 9,580 | ||
BS*030M6 | 29,690 | 27,220 | 24,740 | 22,290 | 19,890 | 17,560 | 15,340 | ||
BS*040M6 | 39,240 | 35,910 | 32,510 | 29,090 | 25,700 | 22,360 | 19,130 |
Model
Compressor
Capacity BTUH @ 100°F Ambient Suction Temperature
25°F | 20°F | 15°F | 10°F | 5°F | 0°F |
BS*010M6 | 8,680 | 7,950 | 7,110 | 6,410 | 5,780 | 5,220 | 4,450 | |
BS*020M6 | 15,590 | 13,950 | 12,550 | 11,320 | 10,210 | 9,180 | 8,030 | |
BS*021M6 | 17,840 | 16,280 | 14,870 | 13,440 | 11,970 | 10,450 | 8,940 | |
BS*030M6 | 28,500 | 26,130 | 23,750 | 21,400 | 19,090 | 16,860 | 14,730 | |
BS*040M6 | 37,670 | 34,470 | 31,210 | 27,930 | 24,670 | 21,470 | 18,360 |
Model
Compressor
Capacity BTUH @ 110°F Ambient Suction Temperature
25°F | 20°F | 15°F | 10°F | 5°F | 0°F |
BS*010M6 | 7,740 | 7,000 | 6,350 | 5,720 | 5,120 | 4,600 | 3,900 | |
BS*020M6 | 14,290 | 12,790 | 11,500 | 10,380 | 9,360 | 8,410 | 7,360 | |
BS*021M6 | 15,840 | 14,610 | 12,600 | 11,850 | 10,470 | 9,180 | 7,770 | |
BS*030M6 | 26,130 | 23,950 | 21,770 | 19,620 | 17,500 | 15,450 | 13,500 | |
BS*040M6 | 34,530 | 31,600 | 28,610 | 25,600 | 22,620 | 19,680 | 16,830 |
* = T for Outdoor, N for Indoor, B for Bohnmizer, S for Beacon II™