Reliance Water Heaters D85500NE, D85500PE instruction manual Contaminated Air, Air Requirements

Page 14

No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

CAUTION

Water Damage Hazard

Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain.

T&P Valve Discharge Pipe Requirements:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall not be exposed to freezing temperatures.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe.

Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.

Shall not have any valve or other obstruction between the relief valve and the drain.

If you do not understand these instructions or have any questions regarding the Temperature-Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance.

Contaminated Air

Breathing Hazard - Carbon Monoxide Gas

Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.

To avoid injury, combustion and ventilation air must be taken from outdoors.

Do not place chemical vapor emitting products near water heater.

Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.

Corrosion of the flue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation.

Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage.

Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).

Burn hazard.

Hot water discharge.

Keep clear of Temperature- Pressure Relief Valve discharge outlet.

The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature- Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature-Pressure Relief Valve with a properly rated/sized new one.

NOTE: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 13.

Air Requirements

Breathing Hazard - Carbon Monoxide Gas

Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.

To avoid injury, combustion and ventilation air must be taken from outdoors.

Do not place chemical vapor emitting products near water heater.

Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.

For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.

An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation.

Do not install the water heater in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows.

14

Image 14
Contents Commercial gas water heaters Table Of Contents Safe Installation, Use and Service Asme CRNGeneral Safety Information Fire and Explosion HazardHydrogen Gas Flammable PrecautionsGrounding Instructions Qualifications IntroductionAbbreviations Used Features and components 2 NPT Installation considerationsRough In Dimensions Model Right Left Back Ceiling Side Locating the Water HeaterClearances Hard Water Installation On Combustible FlooringInsulation Blanket Circulation PumpsNatural Gas Installations Propane InstallationsHigh Altitude Installations Water Temperature Controland Mixing Valves Installation RequirementsPower Supply Gas Pressure RequirementsClosed Water Systems Temperature-Pressure Relief ValveDishwashing Machines Thermal ExpansionContaminated Air Air RequirementsConfined Space VENTING InstallationUnconfined Space Vent AdapterOutdoor Air Through Two Openings Multiple Heater ManifoldFresh Air Openings For Confined Spaces Outdoor Air Through One OpeningOutdoor Air Through Two Vertical Ducts Air From Other Indoor SpacesTechnical Data Venting Multiple Gas Fired Tank-Type HeatersValve Discharge Pipe Water heater installationWater Line Connections Installation Diagrams Top Inlet/Outlet Usage Code RestrictionsHeater Wiring Gas Pressure Regulator Gas PipingPurging GAS Supply Pipe Length FeetFilling AdjustmentsGeneral For Your Safety Read Before Operating Lighting & Operation LabelCheck Venting Check the Igniter AssemblyIgniter Assembly Main BurnerTemperature-Pressure Relief Valve Test MAINTENANCERemote Storage Tank Temperature Control Checking the InputDraining and Flushing Hot Water OdorAnode Rod Inspection To Drain the Water Heater Storage TankDeliming Solvents Tank Cleanout ProcedureDeliming Using Flo-Jug Method Chemical Hazard For your information High Water Temperature Shut OFF System AIR in HOT Water FaucetsSequence of Operation Flow Chart Operational checklist Complaint Cause Remedy User Service AgentDiagrams Water PipingTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Manifold Kits Limited Warranty

D85500PE, D85500NE specifications

Reliance Water Heaters offers a diverse range of high-performance water heaters, with the D85500NE and D85500PE models standing out for their exceptional features and innovative technologies. Designed to meet the needs of modern households, these water heaters are engineered for efficiency, reliability, and ease of use.

The D85500NE is a natural gas water heater that boasts a 50-gallon capacity, making it an excellent choice for medium to large households. One of its main features is the Energy Factor (EF) rating, which ensures efficient operation and reduces energy costs. With a recovery rate of approximately 41 gallons per hour, it's capable of delivering a steady supply of hot water without delays, ensuring that families can enjoy uninterrupted use during peak demands.

The D85500PE model, on the other hand, operates using propane, catering to households with propane systems. Like its natural gas counterpart, the D85500PE also has a 50-gallon capacity and delivers a comparable recovery rate. Both models feature a glass-lined tank, providing corrosion resistance and extending the lifespan of the water heater. This protective lining is crucial for maintaining water quality and ensuring durability over time.

In terms of technology, both the D85500NE and D85500PE are equipped with advanced thermostat and burner systems that allow for precise temperature control. The integrated piezo ignition allows for easy start-up, enabling users to ignite the burner with a simple push of a button. Additionally, the water heaters are designed with safety features such as a pressure relief valve, which prevents excessive pressure build-up.

Another notable characteristic of these models is their user-friendly accessibility. Maintenance access is made simple with installation features that enable straightforward servicing and repairs. The compact design of the units also allows for versatile installation options, whether in a basement, garage, or utility closet.

Finally, both the D85500NE and D85500PE are backed by a solid warranty, providing peace of mind for consumers. With their combination of efficiency, reliability, and advanced features, these water heaters from Reliance Water Heaters are an outstanding choice for anyone looking to enhance their home’s hot water system.