Trion 75 manual Trion Equipment Losses Inches H20, ESP Section, Media Section, Initial Final

Page 12
Trion Equipment Losses Inches H20

Trion Equipment Losses Inches H20

ESP Section

0.14”

40% open perforated prefilter or after filter

0.15”

Metal mesh prefilter or after filter

0.10”

2” impinger

1.25”

Media Section

0.11”

 

Initial Final

4” pleated prefilter, 40% efficient

0.17” - 1.00”

10 pocket bag, 65% efficient

0.40” - 1.20”

HEPA, 99.97% efficient

1.00” - 1.50”

Adsorber Section

0.28”

1” trays

0.26”

2” trays

0.28”

4” modules

0.36”

Fan Transition

0.11”

 

 

The ESP section must have both an internal prefilter and an after filter, select and add for each.

External losses for ductwork, exhaust hoods, manufacturing equipment with associated entry losses, kitchen hoods, etc., must be added with the above Trion internal equipment losses to calculate total fan static pressure required.

10

Image 12
Contents Page Engineered Solutions for Clean Air Numerous applications. One solutionThere are certain things you expect from an air purification systemFeature/Benefits Design Efficiencies & Operational ReliabilityModel 75 Applications Typical System ArrangementsThe Electrostatic Air Cleaner Section Revolutionary Technology for the New MillenniumDurable, compact cabinetry Prefilter/ImpingerSide Access Filter Housing Standard Blower PackageOptional UpBlast Blower Principle of OperationPage Page Page Page Model Selection Guidelines BAG HOUSING CARBON HOUSING1.50 FLANGE 6.25Trion Equipment Losses Inches H20 ESP SectionMedia Section Initial FinalProviding Clean, Comfortable & Safe IAQ Solutions for More Than Half a CenturyLeading Technology for Cleaner Exhaust Air Since A i r P u r i f i c a t i o n S y s t e m sHeadquartered in Sanford, North Carolina