7800 SERIES EC7810A, EC7820A Relay Modules
SPECIFICATION DATA
FEATURES
GENERAL
The Honeywell EC7810/EC7820A Relay Module is a
The EC7810/EC7820 is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.
The basic functions of the EC7810/EC7820A include automatic burner sequencing, flame supervision, system status indication, system or
¥Safety features:
ÑInterlock check.
ÑDynamic
ÑClosed loop logic test.
ÑDynamic input check.
ÑDynamic safety relay test.
ÑDynamic
ÑExpanded
ÑInternal hardware status monitoring.
ÑLow Fire Start Switch test.
ÑTamper resistant timing and logic.
¥Ignition attempts: 1 or 5. Selectable by model number.
¥Access for external electrical voltage checks.
¥Application flexibility.
¥Dependable,
¥
¥Five sequence information light emitting diodes (LED)¾with symbols for Power, Pilot, Flame, Main and Alarm (see Fig. 1).
¥Interchangeable
¥Nonvolatile memory; EC7810/EC7820 retain history files and sequencing status after loss of power.
¥Remote reset (subject to application approval; optional).
¥Remote mounting of KDM (subject to application approval).
¥Burner control data available on the optional KDM:
ÑFlame signal strength.
ÑHold status.
ÑLockout/alarm status.
ÑSequence status.
ÑSequence time.
ÑTotal cycles of operation.
ÑTotal hours of operation.
ÑFault history providing the six most recent faults:
¥Cycles of operation at the time of the fault.
¥Fault message and code.
¥Hours of operation at the time of the fault.
¥Sequence status at the time of the fault.
¥Sequence time at the time of the fault.
ÑDiagnostic information:
¥Device type.
¥Flame amplifier type.
¥Flame failure response time (FFRT).
¥Manufacturing code.
¥On/off status of all digital inputs and outputs.
¥Selected prepurge time.
¥Software revision and version of relay module and optional KDM.
¥Status of configuration jumper.
¥Status of Run/Test Switch.
® U.S. Registered Trademark | |
Copyright © 1998 Honeywell Inc. • All Rights Reserved |