Beckett AFII 150 Inspect/Prepare Installation Site, General Specification Burner Specifications

Page 5

General Information

General Specification

Table 1 – Burner Specifications

Capacity

‘HLX’ Heads

 

 

 

 

Firing rate:

-

0.40 – 1.50 GPH

 

Input: Min./Max

-

56,000 /210,000 Btu/h

 

 

 

 

 

 

‘FBX’ Heads

 

 

 

 

Firing rate:

-

0.40 – 1.35 GPH

 

Input: Min./Max. -

56,000/189,000 Btu/h

 

 

Certification/

UL certified to comply with ANSI/UL296 &

Approvals

tested to CSA B140.0

 

Fuels

U. S No. 1 or No. 2 heating oil only (ASTM

 

D396)

 

 

Canada No. 1 stove oil or No. 2 furnace oil

 

only

 

 

Electrical

Power supply - 120 volts AC, 60 Hz, single

 

phase

 

 

 

 

Operating load - 5.8 Amps max

 

Motor - 1/7 hp, 3450 rpm, NEMA 48M

 

frame PSC rotation CCW when

 

facing shaft end

 

Ignition - Continuous duty solid-state igniter

Fuel pump

Outlet pressure

-

Note 1

Air tube

ATC code - See Table 2

 

 

 

Dimensions

Height (maximum) -

13 inches

(with cover)

Width (maximum)

-

14 inches

 

Depth

 

-

6-11/16 inches

 

Air tube diameter

-

3-1/2 inches

*Note 1. See appliance manufacturer’s burner specifications for recommended outlet pressure.

Notice Special Requirements

For recommended installation practice in Canada, refer to the latest version of CSA Standard B139 & B140.

Concealed damage — If you discover damage to the burner or controls during unpacking, notify the carrier at once and file the appropriate claim.

When contacting Beckett for service information — Please record the burner serial number (and have available when calling or writing). You will find the serial number on the silver label located on the left rear of the burner. Refer to Figure 1.

Inspect/Prepare Installation Site

Clearances to Burner and Appliance

Provide space around burner and appliance for ease of service and maintenance. Check the mini- mum clearances against those shown by the ap- pliance manufacturer and by applicable building codes.

Table 2 – Air Tube Combinations (ATC) & Dimensions

 

 

ATC codes for usable air tube lengths dim. “A” (Figure 3)

Firing rate range (gph)Min-Max

 

 

3”

5”

7”

9”

ATC Code

Head

AFII 85

AFII 100

AFII 150

Adjustable

w/stop screwHead Design

HLX30

HLX50

HLX70

HLX90

HB

AF2-6

0.4-0.85 gph

0.65-1.00 gph

0.75-1.35 gph

HLX30

HLX50

HLX70

HLX90

HE

AF2-9

N/A

0.65-1.00 gph

0.75-1.35 gph

 

 

HLX30

HLX50

HLX70

HLX90

HC

AF2-9

N/A

0.65-1.00 gph

0.75-1.50 gph

 

 

HLX30

HLX50

HLX70

HLX90

HD

AF2-6

0.40-0.85 gph

0.65-1.00 gph

0.75-1.10 gph

 

 

 

 

 

 

 

 

 

 

 

DesignHead

 

FBX30

FBX50

FBX70

FBX90

HFXS

FB0

0.40-0.65 gph

0.55-0.75 gph

0.75-1.00 gph

Fixed-

FBX30

FBX50

FBX70

FBX90

HGXS

FB3

0.55-0.85 gph

0.55-1.10 gph

0.85-1.20 gph

 

 

 

 

FBX30

FBX50

FBX70

FBX90

HHXS

FB4

N/A

0.75-1.10 gph

1.10-1.25 gph

 

 

FBX30

FBX50

FBX70

FBX90

HIXS

FB6

N/A

0.85-1.15 gph

1.15-1.35 gph

 

 

 

 

 

 

 

 

 

 

 

 

 

HB 6 slot

 

HC 9 slot

 

HD 6 slot

HE 9 slot

RWB 6104 BAFII R01

Page 5

Image 5
Contents Model Afii Oil RWB 6104 Bafii R01 Information To Be Used Only By Qualified Service Technicians Table of ContentsGeneral Information General InformationTo the Owner Hazard DefinitionsGeneral Specification Burner Specifications Inspect/Prepare Installation SiteClearances to Burner and Appliance HB 6 slot HC 9 slot HD 6 slot HE 9 slotInspect Chimney or Direct Vent System Inspect/Prepare Installation SiteCombustion Air Supply Information Required Direct/Sidewall Venting ApplicationPrepare the Burner Fuel Line InstallationFuel Line Valves and Filter GeneralStart the Burner and Set Combustion Wiring Connections DiagramStart the Burner and Set Combustion Connect Fuel LinesControl System Features Typical Wiring, R7184 Primary ControlSet combustion with instruments Trained Service Technician’s Regular MaintenanceTrained Service Technician’s Regular Maintenance Nozzle Installation Removing Nozzle Line for ServiceBlower Wheel Re- Wheel Replacement Placement Check/Adjust ElectrodesHLX Firing Rate FBX Firing Rate FBX Air Dial SettingHLX Air Dial Setting Replacement Parts Diagram Description Kit No Replacement Parts ListLimited Warranty Information Warranty

FII 85, AFII 100, AFII 150 specifications

The Beckett AFII series, encompassing the AFII 150, AFII 100, and FII 85, represents a significant advancement in the realm of oil burners, particularly designed for residential and commercial heating applications. Around the heart of the AFII series lies a commitment to efficiency, reliability, and ease of installation, setting these models apart from traditional oil burner designs.

The AFII 150 model is particularly noteworthy for its impressive output capabilities, making it ideal for larger heating demands. It can produce up to 150,000 BTUs per hour, ensuring that even extensive spaces are heated effectively. The integrative SmartStart technology allows for quick ignition, enhancing energy efficiency and reducing fuel consumption. This model also features a robust construction that extends its lifespan and reduces maintenance needs, while its design minimizes carbon emissions, aligning with modern environmental standards.

The AFII 100 is designed for medium-sized applications, providing up to 100,000 BTUs per hour. Like the AFII 150, it incorporates SmartStart technology to enhance ignition performance and efficiency. Additionally, it boasts an advanced air-fuel ratio control system that optimizes combustion, providing better heating efficiency and environmental performance. Ease of installation is a key characteristic of the AFII 100, with components designed for straightforward integration into existing heating systems.

On the other hand, the FII 85 model serves the low-end heating sector effectively, with an output of up to 85,000 BTUs per hour. Its compact design is perfect for residential applications where space can be a constraint. The FII 85 also integrates Beckett’s patented CleanFire technology, which helps to maintain low emissions and reduce the likelihood of soot build-up. This feature not only prolongs the burner’s life but also enhances the air quality in the indoor environment.

Each model in the AFII series comes equipped with a range of diagnostic features that facilitate ease of use and maintenance, ensuring the systems are running efficiently over their lifespan. The reliability of the Beckett AFII series is further augmented by its adherence to industry standards, guaranteeing safety and performance.

In summary, the Beckett AFII 150, AFII 100, and FII 85 models showcase a thoughtful fusion of technology and engineering aimed at delivering superior heating solutions. Their advanced ignition systems, optimized combustion technologies, and robust designs make them ideal candidates for diverse heating needs, confirming Beckett's commitment to quality and sustainability in the oil burner market.