Lochinvar Knight XL Boiler Manual: Service and Specifications

Page 6

Knight® XL Boiler Dimensions and Specifications

LOW VOLTAGE

ELECTRICAL

CONNECTIONS

GAS

J

FLUE

39-1/2"

I

13-3/4"

8"

B

BACK

HIGH VOLTAGE

K

 

ELECTRICAL

 

 

CONNECTIONS

 

 

 

 

AIR INLET

 

 

HEAT

 

 

EXCHANGER

INLET

OUTLET

DRAIN

 

 

3/4" NPT

38-3/4"

 

 

H

 

CONDENSATE

 

DRAIN

FLUE

 

 

 

18-3/4"

 

 

 

3-1/2"

9"

 

 

 

G

 

 

F

E

D

 

 

C

LEFT SIDE

 

 

Model Number Guide

 

 

KB

 

N

700

M13

 

 

 

 

 

Firing

 

Model

Natural

Btu/hr

 

 

 

 

 

 

 

 

 

 

Gas

Input

Controls

 

 

 

 

A

Knight XL Boiler,

 

 

 

 

 

 

 

 

Natural Gas,

 

 

 

 

700,000 Btu/hr input,

 

 

M13 firing controls

 

 

1/4" - 1-1/4"

 

 

 

 

 

 

ADJUSTABLE

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

Knight XL Heating Boiler

 

 

 

Dimensions and Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

Net

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Min

Max

Thermal

Output

I=B=R

 

A

B

C

D

E

F

G

H

I

J

K

Gas

Water

Air

Vent Shipping

 

Number

MBH

MBH

Efficiency

MBH

MBH

 

 

 

 

 

 

 

 

 

 

 

 

Conn. Conn.

Inlet

Size

Wt. (lbs.)

 

KBN399

80

399

93.3%

372

324

 

 

42-1/2”

15-1/2”

27-3/4”

3-3/4” 20-3/4”

21”

14”

34”

34”

2”

18-3/4”

1”

1-1/2”

4”

4”

280

 

KBN500

100

500

93.3%

467

406

 

 

42-1/2”

15-1/2”

31-1/4”

3-3/4” 25-1/2”

21”

14”

32-1/2”

36”

2”

18”

1”

1-1/2”

4”

4”

310

 

KBN600

120

600

94.6%

567

493

 

 

42-1/2”

15-1/2”

36-1/4”

3-3/4”

25”

21”

14”

36”

32-3/4”

5-1/2”

19-1/2”

1”

2”

4”

4”

340

 

KBN700

140

700

94.3%

660

574

 

 

42-1/2”

15-1/2”

40-1/4”

3-3/4”

29”

23”

17”

36”

32-3/4”

3-1/4”

23-1/2”

1”

2”

4”

6”

370

 

KBN800

160

800

94.0%

752

654

 

 

42-1/2”

15-1/2”

45-1/4”

3-3/4” 33-1/4”

23”

17”

36”

32-3/4”

3-1/4”

27-3/4”

1”

2”

4”

6”

405

 

Notes: Change ‘N’ to ‘L’ for L.P. Gas Model. No deration on L.P. models. Performance data based on manufacturer test results.

120 VAC /15 AMP circuit required.

 

 

All dimensions shown in inches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Features

 

Smart System Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>Up to 94.6% Thermal Efficiency

>Modulating Burner with 5:1 Turndown

>Direct-Spark Ignition

>Low NOx Operation

>Sealed Combustion

>Low Gas Pressure Operation

>Vertical & Horizontal Direct-Vent

>Category IV venting up to 100 feet

>PVC, CPVC or AL29-4C Venting up to 100 Feet

>Factory Supplied Sidewall Vent Termination

>ASME Stainless Steel Heat Exchanger

>ASME Certified, ”H” Stamped

>Gasketless Heat Exchanger

>160 psi Working Pressure

>Highly efficient, condensing design

>On/Off Switch

>Adjustable High Limit w/ Manual Reset

>Flow Switch

>Inlet & Outlet Temperature Sensors

>Flue Temperature Sensor

>Low Air Pressure Switch

>50 psi ASME Relief Valve

>Temperature & Pressure Gauge

>Adjustable Leveling Legs

>Condensate Trap

>Zero Clearances to Combustible Material

>10 Year Limited Warranty (See Warranty for Details)

>SMART SYSTEM Digital Operating Control

>2 line, 16 Character Display

>Dual Level Password Security

>Domestic Hot Water Prioritization

>Built in Cascading Sequencer for up to 8 Boilers

>Building Management System Integration

with 0-10 VDC Input

>Outdoor Reset Control with Outdoor Air Sensor

>Low Water Flow Safety Control & Indication

>Inlet & Outlet Temperature Readout

>Freeze Protection

>Service Reminder

>Time Clock

>Data Logging

>Hours Running, Space Heating

>Hours Running, Domestic Hot Water

>Ignition Attempts

>Last 10 Lockouts

>Programmable System Efficiency Optimizers

>Night Setback

>Anti-Cycling

>Outdoor Air Reset Curve

>Ramp Delay

>Boost Temperature & Time

>Three Pump Control

>System Pump

>Boiler Pump

>Domestic Hot Water Pump

>High Voltage Terminal Strip

>120 VAC / 50-60 Hertz / 1 Phase Power Supply

>Three sets of Pump Contacts with Pump Relays

Patent # 7,506,617

>Low Voltage Terminal Strip

>24 VAC Auxiliary Device Relay

>Auxiliary Proving Switch Contacts

>Flow Switch Contacts

>Alarm on Any Failure Contacts

>Runtime Contacts

>DHW Thermostat Contacts

>Room Thermostat Contacts

>System Sensor Contacts

>DHW Tank Sensor Contacts

>Outdoor Air Sensor Contacts

>Cascade Contacts

>0-10 VDC BMS External Control Contact

Optional Equipment

>Alarm Bell on Any Failure

>Condensate Neutralization Kit

>High & Low Gas Pressure Switches w/ Manual Reset (KB500-KB800)

>Low Water Cutoff w/Manual Reset & Test

>SMART SYSTEM PC Software

>Stainless Steel Vent Kits (KB700-KB800)

>Multi-Stack Frame

Firing Codes

> M9 Standard Construction

> M7 California Code

>M13 CSD1 / FM / GE Gap (KB500-KB800)

3 0 0 M a d d o x S i m p s o n P a r k w a y, L e b a n o n, T N 3 7 0 9 0 6 1 5 - 8 8 9 - 8 9 0 0 f a x : 6 1 5 - 5 4 7 - 1 0 0 0 w w w . l o c h i n v a r . c o m

KBX-03(Replaces KBX-02 6/08)

5M-4/09-Printed in U.S.A.

Image 6
Contents Up to 94.6% Thermal Efficiency Smartest Choice for Condensing Boiler Performance Knight XL Combustion SystemBrain That Drives Brilliant Performance 15-1/2Including Built-in Cascading SequencerEasy Access to Internal Components Easy Handling on the JobsiteKnight XL Boiler Dimensions and Specifications Back