Lochinvar 399 - 800 Check Air Vents, Operate relief valve, Test low water cutoff if installed

Page 8

2Maintenance schedule

Check Air Vents

1.Reference FIG. 3 below.

2.Visually inspect vent to make sure that no leaks are present.

3.If there is leaking, tighten the needle valve.

4.If the leak continues, replace the air vent.

Figure 2-3 Air Vent

NEEDLE

VALVE

User’s Information Manual

￿WARNING Have leaks fixed at once by a qualified service technician. Failure to comply could

result in severe personal injury, death, or substantial property damage.

3.Replace the front access door.

Operate relief valve

1.Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water.

Test low water cutoff (if installed)

1. If the system is equipped with a low water cutoff, test the

low water cutoff periodically during the heating season,

following the low water cutoff manufacturer’s

￿WARNING

To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to the relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Knight XL Installation and Operation Manual. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge.

instructions.

Reset button (low water cutoff)

1.Testing the low water cutoff shuts the unit off. Press the RESET button on the low water cutoff to turn the unit back on.

Check boiler piping (gas and water)

1.Remove the boiler front access door and perform a gas leak inspection per steps 1 through 7 of the Operating Instructions on page 9. If gas odor or leak is detected, immediately shut down the boiler following the procedure on page 9. Call a qualified service technician.

2.Visually inspect for leaks around water piping.

Also inspect the circulators, relief valve, and fittings. Immediately call a qualified service technician to repair any leaks.

8

2.Read the boiler pressure/temperature gauge to make sure the system is pressurized. Lift the relief valve top lever slightly, allowing water to relieve through the valve and discharge piping.

3.If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system.

4.If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shut down the boiler, following the operating instructions on page 9 of this manual. Call your qualified service technician to inspect the boiler and system.

Shut boiler down (unless boiler is used for Domestic Water)

1.Follow “To Turn Off Gas to Appliance” on page 9 of this manual.

2.Do not drain the system unless exposure to freezing temperatures will occur.

3.Do not drain the system if it is filled with an antifreeze solution.

4.DO NOT shut down boilers used for domestic water heating, they must operate year-round.

Image 8
Contents User’s Information Manual Models 399 Save this manual for future referenceContents Boiler service and maintenance Please read before proceedingAreas likely to have contaminants Prevent combustion air contaminationProducts to avoid Maintenance schedule Service technician Owner maintenanceMaintenance schedule 1Condensate Trap Condensate disposalTest low water cutoff if installed Reset button low water cutoffCheck Air Vents Operate relief valveFor Your Safety Read Before Operating Operating instructionsSmart System control module Knight XL control moduleAccess modes InstallerUser To save parameters and exit programmingParameter table Data logging Temperature settingsGeneral DHW settings Service StandbySet Point Met PrepurgeSYS ***.*F Control will display the actual fan motor RPMDelay 10V in **.VdcOperation of the cascade User’s Information Manual
Related manuals
Manual 44 pages 18.95 Kb

399 - 800 specifications

Lochinvar is known for its cutting-edge water heating and boiler systems, and the Lochinvar 399 - 800 series is no exception. Specifically designed for commercial applications, this series brings advanced technology and engineering to the forefront of hydronic heating solutions.

One of the standout features of the Lochinvar 399 - 800 series is its impressive efficiency. Equipped with a condensing design, these boilers utilize high-efficiency stainless steel heat exchangers that allow for maximum heat transfer while minimizing energy consumption. With an impressive thermal efficiency of up to 96%, the Lochinvar 399 - 800 series stands out in its class, offering significant energy savings and reduced operational costs over time.

Another key characteristic of this series is its robust construction. Designed with longevity in mind, the boilers are built using high-quality materials that withstand extreme temperatures and pressures. The stainless steel design not only enhances durability but also combats corrosion, ensuring a long service life and reduced maintenance costs for users.

The Lochinvar 399 - 800 series also incorporates advanced control technologies. With its intuitive control system, users can easily adjust and monitor heating parameters, ensuring optimal performance and comfort. The integrated Control Wizard feature simplifies the setup process, allowing for quick commissioning and troubleshooting. Additionally, the optional Lochinvar SMART CONTROL technology provides remote monitoring capabilities, allowing operators to keep track of system performance from anywhere.

Versatility is another hallmark of the Lochinvar 399 - 800 series. These boilers come in a range of sizes, with the ability to modulate output based on real-time heating demands. This flexibility ensures that systems can operate efficiently under varying load conditions, making them ideal for schools, hospitals, and commercial buildings requiring consistent hot water availability.

In summary, the Lochinvar 399 - 800 series exemplifies modern boiler technology, combining energy efficiency, durability, advanced controls, and versatility. As businesses and facilities seek to enhance their heating systems, the Lochinvar 399 - 800 offers a reliable and forward-thinking solution for today's energy-conscious environment. Investing in this state-of-the-art boiler system not only improves comfort but also fosters sustainability and cost-effectiveness in commercial heating applications.