Lochinvar 1.5, 1.3 manual Maintenance schedule Service technician, Owner maintenance

Page 5

User’s Information Manual

2Maintenance schedule

Service technician

(see the SYNC Service Manual)

General:

Address reported problems, if any

Inspect interior; clean and vacuum if necessary;

Clean condensate trap and fill with fresh water

•Check for leaks (water, gas, flue, condensate)

Verify flue and air lines in good condition and sealed tight

•Check system water pressure/system piping/expansion tank

 

• Check control settings

 

UP

• Check ignition and flame sense

 

electrodes (sand off any deposits; clean

 

START-

and reposition)

 

 

• Check wiring and connections

 

 

 

 

• Perform start-up

checkout

and

ANNUAL

performance verification per Section 9.

• Flame inspection (stable, uniform)

 

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

• Clean the heat

exchanger

if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

 

 

• Test low water flow conditions.

 

If combustion or performance indicate need:

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see pages 6 - 8 for detailed instructions)

• Check boiler area

Daily

• Check pressure/temperature

 

 

gauge

 

 

 

• Check vent piping

 

• Check air piping

Monthly

• Check air and vent termination

 

screens

 

• Check relief valve

 

• Check condensate drain system

 

• Check automatic air vents

 

 

 

• Test low water cutoff

Every

• Reset button (low water cutoff)

6 months

 

 

• Check boiler piping (gas and

 

water) for leaks

 

• Operate relief valve

 

 

End

•Shut boiler down (unless boiler

of season

used for domestic hot water)

months

 

￿WARNING

Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting in severe personal injury, death, or substantial property damage.

5

Image 5
Contents User’s Information Manual Models 1.0 1.3 Contents Please read before proceeding Boiler service and maintenanceProducts to avoid Prevent combustion air contaminationOwner maintenance Maintenance schedule Service technicianMaintenance procedures Maintenance scheduleCondensate disposal Check automatic air vents Operating instructions For Your Safety Read Before OperatingSync control module Smart Touch control moduleSmart Touch control module 2Details Screen Smart Touch control module 3Main Menu Screen
Related manuals
Manual 16 pages 3.68 Kb Manual 12 pages 30.87 Kb Manual 56 pages 20.39 Kb Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 56 pages 40.75 Kb Manual 80 pages 59.46 Kb Manual 56 pages 36.01 Kb

1.5, 1.3, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.