Lochinvar 1.3 service manual Setup Screen

Page 18

Service Manual

1 Service

CAUTION

Before changing parameters, note the settings so that the unit can be returned to its original operating parameters.

Setup Screen:

The Setup Screen allows access to seven (7) other screens for adjusting control parameters.

These screens are as follows:

Service / Setup - Allows access to change service notification parameters, LCD backlight parameters, and temperature units.

Night Setback - Allows access to change the date and time and ON/OFF times for night setback.

Setpoints - Allows access to change the system heat set point, hot water generation set point, and ON/OFF differentials.

Cascade - Allows access to change the cascade parameters.

Outdoor Reset - Allows access to change the reset curve parameters.

Pumps - Allows access to change pump delay timing.

BMS - Allows access to change the 0 - 10Vdc BMS parameters.

To change a parameter, press one of the seven screen buttons. A list of parameters and their corresponding location are located on pages 11 and 12, Table 1B. Once a Screen button is pressed a list of adjustable parameters will appear.

Select the parameter to be adjusted by pressing the SELECT button next to the parameter. The first time the parameters are accessed, you will be required to enter the service password. The service password is 5309. Using the keypad, enter the password and then press the OK button. If the password is not entered correctly, the screen will revert to the Parameter List Screen and you will not be able to adjust the parameters. If a digit has been entered incorrectly, press the left arrow key on the keypad to back the digit up.

18

If the password has been entered correctly, the Parameter Change Screen will appear. The Parameter Change Screen will display the parameter being changed, the previous setting of the parameter, and adjustment buttons.

To adjust the parameter, press the + or - buttons to change the value being displayed. Once the parameter has been adjusted to the desired setting, press the APPLY button to change the parameter and return to the Parameter List Screen. If no further changes are necessary, press the BACK button to return to the Parameter List Screen. Once all the necessary adjustments have been made, press the BACK button to return to the Setup Screen. Repeat this procedure to adjust the parameters in other screens.

Press the SAVE button to program all changes made to the control parameters and return to the Status Screen. Leaving the Setup Screen without pressing the SAVE button will erase the changes made to the control parameters and revert them back to their previous settings.

Time - The time is displayed in the upper right-hand corner of the display. It is displayed in 24 hour format. Reference the night setback parameters on page 24 for information regarding adjusting the date and time.

Main button - Pressing this button brings up the Main Screen. From this screen navigation to eight (8) other screens is possible. Reference the Main Screen section on page 17 of this manual for more information regarding this screen.

Save button - Pressing this button will save all changes made to the control parameters.

Status button - Pressing this button displays the Status Screen. This screen shows the current status of the SYNC boiler. Reference pages 13 - 14 for more information regarding this screen.

Image 18
Contents Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidService MaintenanceTroubleshooting Service Near boiler pipingSync display Control inputs BoardSecondary Smart Touch Control Module Primary Control outputsHow the control module operates General OperationHow the boiler operates Sequence of operationSequence of operation Sequence of operation space heating and HWThis table lists the parameters and where to access them Parameter tableOutdoor Reset Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Outdoor Reset Parameters Screen Service Night Setback Parameters Screen Cascade Parameters Screen Cascade OperationPumps Parameters Screen 10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Inspect boiler area Address reported problemsClean condensate trap Inspect boiler interiorFlue vent system and air piping Check water systemCheck expansion tank Check boiler relief valve Check control settings Check ignition ground wiringCheck all boiler wiring Inspect ignition and flame sense electrodesCheck flame signal Cleaning boiler heat exchangerReview with owner Test procedure Test low water flow conditionsTroubleshooting Alarm ScreenBefore troubleshooting Check the followingCheck control module fuses Operation No DisplayNo Burner Unit DoesChecking temperature sensors Temperature ResistanceOperation Boiler Pump NoisyNo Pump System PumpDrain Blocked Flow SwitchCondensate Flame outLight cont’d Flame LostWhile Running Troubleshooting Temp SW Automatic ResetHigh Limit / HEX Blower RPM’sSensor Open Louver Proving SwitchToo High Sensor ShortedLow Resets Try LaterAir Flow Too Flap ValveWriting to Internal FaultNo Error Stored MemosOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureGas valve adjustment procedure ModelModels 1.3
Related manuals
Manual 16 pages 3.68 Kb Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 80 pages 59.46 Kb Manual 56 pages 36.01 Kb

1.3, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.