Burnham L7248 manual Minimum Installation Clearances To Combustible Materials

Page 4

Figure 2: Minimum Installation Clearances To Combustible Materials

NOTE 1: Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of oil burning equipment.

NOTE 2: LE Series boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances can not be reduced for alcove or closet installations.

NOTE 3: For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31 standard.

3. PROVIDE COMBUSTION AND VENTILATION AIR. Local code provisions may apply and should be referenced.

WARNING

Adequate combustion and ventilation air must be provided to assure proper combustion.

A.Determine volume of space (boiler room). Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.

Volume(ft3) = Length(ft) x Width(ft) x Height(ft)

B.Determine total input of all appliances in the space.

Add inputs of all appliances in the space and round the result to the nearest 1000 BTU per hour.

C.Determine type of space. Divide Volume by total input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconfined space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a confined space.

D.For boiler located in an unconfined space of a conventionally constructed building, the fresh air infiltration through cracks around windows and doors normally provides adequate air for combus- tion and ventilation.

E.For boiler located in a confined space or an uncon- fined space in a building of unusually tight con- struction, provide outdoor air with the use of two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:

(1)Direct communication with outdoors. Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.

(2)Vertical ducts. Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

(3)Horizontal ducts. Minimum free area of 1 square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

Alternate method for boiler located within confined space. Use indoor air if two perma- nent openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.

F.Louvers and Grilles of Ventilation Ducts

(1)All outside openings should be screened and louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.

(2)Free area requirements need to consider the blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.

Image 4
Contents LE Series Important Information Please Read this page Carefully Table of Contents General InformationMinimum Installation Clearances To Combustible Materials Remove Crate II. Installation InstructionsRemoval of Boiler from Skid Page Page Install Electric Wiring Fuel Units and OIL LinesSINGLE-STAGE Units 3450 RPM TWO-PIPE Systems Sequence of Operation Wiring Diagram for LE Boilers with Riello Burner III. Operating and Service Instructions Press RED Reset ButtonDisplay Readout OperationRemove GUN Assembly Adjust OIL Burner Before StartingHigh Limit Controller Open ALL OIL Line ValvesAdjust OIL Pressure Other Adjustments Adjust the AIR Band AND/OR AIR SHUT- TERCAD Cell Location and Service Remove Flame Plug in Swing Door Start OIL BurnerCheck for Clean CUT OFF of Burner Test ControlsMake pH or Alkalinity Test Hints on CombustionAvoid Breathing Fiber Particulates and Dust High Altitude Installations Clean the Firetubes Close Boiler IV. Boiler CleaningAfter Cleaning Repair Parts Description Qty Part NumberLE Boiler Jacket & Insulation LE Bare Boiler Assembly Beckett AFG OIL Burner Repair Parts MOD E L LE1 LE2 Service Record VI. Low Water Cut Off Lwco WhenLimited Warranty

L7248 specifications

The Burnham L7248 is a notable model in the realm of heating solutions, designed specifically for residential and commercial use. Renowned for its efficiency and reliability, the L7248 embodies innovative technology combined with user-friendly features, catering to diverse heating needs.

One of the key features of the Burnham L7248 is its advanced heating technology. It employs a gas-fired system that provides both hot water and space heating. This dual-function capability ensures that homes remain warm and comfortable during the colder months while also supplying hot water for daily use. The integrated control system allows users to manage the heating effectively, ensuring maximum comfort with minimal energy expenditure.

The L7248 is designed with durability in mind. Constructed from high-quality materials, the boiler is built to withstand the rigors of regular use while maintaining peak performance. Its advanced heat exchanger design enhances efficiency by ensuring optimal heat transfer, which translates to lower energy costs and a reduced environmental footprint. Furthermore, the unit operates quietly, providing a peaceful environment without intrusive noise.

In terms of safety, the Burnham L7248 incorporates several features that protect both the system and the home. It is equipped with advanced safety controls that monitor pressure and temperature, preventing potential hazards. Additionally, the unit’s design allows for easy servicing and maintenance, ensuring that it remains in good working condition for many years.

Energy efficiency is another hallmark of the Burnham L7248. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the model significantly reduces fuel consumption, helping homeowners save on energy bills while promoting sustainability. The boiler is also compatible with various smart home technologies, allowing users to integrate it into their existing systems for enhanced control and efficiency.

Overall, the Burnham L7248 stands out for its combination of innovative technology, safety features, and energy efficiency. Whether for residential or commercial applications, it provides a solid, reliable heating solution that meets the demands of modern living. With its user-focused design and robust performance characteristics, the Burnham L7248 is an excellent investment for those seeking dependable and efficient heating.