Crown Boiler 32-380ECS, 32-475ECS manual XI Control System Wiring

Page 5

XI Control System Wiring

WARNING

All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such

Wire the boiler in accordance with the following instructions rather than those in the installation manual. Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit must be 15A. Wire the boiler using the appropriate wiring diagram shown in Figures A-C in this supplement. In addition, note the following:

1)Steam boiler wiring is shown in Figure A. The junction box, transformer, and thermostat relay are prewired with all low voltage wire harnesses, except the damper harness (if used).

a)Mount the junction box assembly to the side jacket panel as shown in Figure D using two #10 x 1/2” sheet metal screws.

b)Connect the gray limit harness to terminals R and B on the L404 pressure limit.

c)Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal screws. Route the red BVS harness along the side of the boiler as shown in Figure D and connect the pair of fully insulated quick connects to the BVS.

d)Route the other end of the BVS harness to the ignition module . Connect the fully insulted quick connect to the “24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS harness to the jacket with the nylon clips provided as shown in Figure D.

e)If a damper is installed, remove the red jumper wire inside the junction box that is indicated by Note #2 in Figure A. Connect the damper harness to the wiring in the junction box as shown in Figure A. Route the damper harness to the damper as shown in Figure D, using care to make sure that it does not come in contact with the draft hood or steam piping.

f)If a redundant LWCO and/or pressure limit are used, wire them so that they interrupt 120VAC power to the boiler.

2)Water Boiler wiring is shown in Figure B for boilers without a tankless heater and in Figure C for boilers with a tankless heater. The blocked vent switch (BVS) wire harness is factory wired to B1 and B2 on the “aquastat” (L8148E or L8124E).

a)Mount the aquastat to the control well.

b)Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal screws. Route the red BVS harness along the side of the boiler as shown in Figure F and connect the pair of fully insulated quick connects to the BVS.

c)Route the other end of the BVS harness to the ignition module . Connect the fully insulated quick connect to the “24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS harness to the jacket with the nylon clips provided as shown in Figure F.

d)A vent damper cannot be used on boilers equipped with tankless heater. If a damper is installed on a boiler without the tankless heater, remove the jumper plug inside the L8148E aquastat. Plug the 6-pole end of the damper harness into the aquastat. Plug the 4-pole end of the harness into the damper. Route the damper harness to the damper as shown in Figure F, using care to make sure that it does not come in contact with the draft hood.

e)If a LWCO and/or redundant temperature limit are used, wire them so that they interrupt 120VAC power to the boiler.

3)Provide a Class II circuit between the boiler and the thermostat. Make thermostat connections to the boiler in accordance with Figure A-C.

4)Make 120VAC connections to the boiler in accordance with Figure A-C.

CAUTION

Make sure that damper and BVS harnesses are secured so that they do not come in contact with draft hood or steam piping.

3

Image 5
Contents Series 32ECS Page 32-380ECS Specifications 32-380ECS Dimensional Data Refer to in Installation ManualVII Venting XI Control System Wiring Figure a Steam Boiler Wiring Sequence of Operation Steam Boiler Safety Control Operation Steam BoilersFigure C Water Boiler Wiring With Tankless Heater Sequence of Operation Water Boiler, Less Tankless Heater Figure E Blocked Vent Switch Installation Safety Control Operation Water Boilers Series 32 Master Parts List for 32-380ECS & 32-475ECS ECS Water Trim Carton Less Tankless Heater ECS Steam Trim Carton Page PN 980895 05/10

32-380ECS, 32-475ECS specifications

Crown Boiler is renowned for its innovative and reliable heating solutions, and its models 32-475ECS and 32-380ECS are prime examples of the company’s commitment to performance and efficiency. These residential and light commercial steam boilers are designed to deliver warmth and comfort while minimizing energy consumption, all within a robust and durable framework.

One of the standout features of the Crown Boiler 32-475ECS and 32-380ECS is their adaptability to various heating applications. These boilers are sized appropriately for numerous residential settings, providing heating solutions for homes of different dimensions and layouts. Their large heating capacities, rated at 475,000 BTUs/hour for the 32-475ECS and 380,000 BTUs/hour for the 32-380ECS, are suitable for larger spaces or buildings requiring significant heat output.

Both models utilize a fire-tube design, which promotes efficient heat transfer and helps conserve fuel. This design leads to improved thermal efficiency compared to traditional designs, making them an environmentally-friendly choice for homeowners concerned about carbon footprints. Additionally, the units feature advanced natural gas burners that enhance combustion efficiency, ensuring that less fuel is consumed to achieve the desired heating level.

The Crown Boiler models also come equipped with various safety features, including a pressure relief valve and low water cutoff, which help to ensure safe and reliable operation during the boiler's lifecycle. The combination of these safety mechanisms with robust construction materials ensures long-lasting performance even under demanding conditions.

Furthermore, the 32-475ECS and 32-380ECS are designed for ease of installation and maintenance. They feature a user-friendly control system, allowing homeowners and technicians to monitor performance and make necessary adjustments easily. The serviceability of these units is enhanced by their compact design, which can save space in mechanical rooms and facilitate troubleshooting.

In summary, the Crown Boiler 32-475ECS and 32-380ECS represent an exceptional choice for those seeking efficient, reliable, and safe heating solutions. With their powerful heating capacities, advanced technology, and thoughtful design, these models exemplify Crown Boiler's dedication to quality and innovation in the heating industry. Whether for residential or light commercial use, these boilers provide the performance and efficiency that modern buildings demand.