OPERATION
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1.Move fan switch to ON position. The blower should begin to operate.
2.Move fan switch to AUTO position. The blower should stop immediately.
Heating System
1.Move SYSTEM switch to HEAT position. If the auxiliary heating system has a standing pilot, be sure to light it.
2.Press to adjust thermostat setting to 1° above room temperature. The heating system should begin to operate.
3.Press to adjust temperature setting below room temperature. The heating system should stop operating.
Cooling System
!CAUTION
To prevent compressor and/or property damage, if the outdoor temperature is below 50oF, DO NOT operate the cooling system.
1.Move SYSTEM switch to COOL position.
2.Press to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. However, if the setpoint temperature is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
3.Press to adjust temperature setting above room temperature. The cooling system should stop operating.
!CAUTION
Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.