Allied Air Enterprises 506271-01 Gas piping recommendations, Gas Connection, Typical Field Wiring

Page 6

Gas piping recommendations:

A drip leg and a ground joint union must be installed in the gas piping. A ground joint union is recommended by the manifold/valve.

When required by local codes, a manual shutoff valve may have to be installed outside of the unit.

Use pipe thread sealing compound resistant to propane gas sparingly on male threads.

The gas supply should be a separate line and installed in accordance with all safety codes listed on page 1. After the gas connections have been completed, open the main shutoff valve admitting normal gas pressure to the mains. Check all joints for leaks with soapy solution or other material suitable for the purpose.

WARNING

Never use a flame to check for gas leaks. Explosion causing injury or death may occur.

The furnace and its individual manual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.48kPa).

A 1/8" N.P.T. plugged tapping, accessible for test gauge connections, must be installed immediately upstream of the gas supply connection to the furnace.

Gas Connection

The gas supply line should be routed through the grommet on the side of the unit.

WARNING

The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1/2 psig or 14" w.c. If the piping system is to be tested at pressures in excess of 1/2 psig, the furnace and its individual shutoff valve must be disconnected from the gas supply piping system.

Typical Field Wiring

 

Thermostat

Weatherproof

 

Disconnect Switch

To

 

Power

 

Supply

48" Overhead

 

Clearance

NEC Class 1 Wiring

 

NEC Class 2 Wiring

To Unit Power Entry

To Low Voltage Entry

 

 

 

Vent Cover

 

 

 

 

12" Clearance

2" Clearance Rear

 

 

(Both Sides)

 

 

 

 

 

24" Clearance

 

15" Clearance

 

 

 

To Vent Cover

 

 

From Front

 

 

 

 

 

 

 

 

 

Power Entry

NOTE: All outdoor wiring must be weatherproof.

 

Gas Entry

 

 

Low Voltage Entry

 

 

 

 

 

 

Figure 4

Page 6 of 14

Issue 0921

506271-01

Image 6 Contents
Table of Contents RPGE/RGE Series Installation State of Massachusetts Location Clearances Roof Curb InstallationService Access Corner BracketsInstalling the Vent Cover Removal of Unit from Common Venting SystemCondensate Drain DuctworkFilters Typical Condensate Drain ConnectionTypical Field Wiring Gas piping recommendationsGas Connection LPG/Propane Units, Tanks, and Piping Electrical Wiring See Figures 4Power Wiring Line Voltage 208/230 Volts ThermostatSTART-UP # Seconds Per Revolution Value Manifold Gas Pressure Adjustment Regulator Natural GasManifold Gas Pressure Adjustment Regulator LPG/Propane GasOperation Maintenance Blower Delay HeatingVent Outlet Fault CodesBurners Heat ExchangerWiring Diagram Single Phase Issue 506271-01