Kidde I5000 Architectural and Engineering Specifications, Technical Specifications, Upc, Led

Page 2

120V AC Wire-In Smoke Alarm

Model i5000

Slide Load Front Battery Door

 

 

 

Architectural and Engineering Specifications

The smoke alarm shall be Kidde Model i5000 or approved equal. It shall be powered by a 120VAC, 60Hz source along with a 9V alkaline battery backup. The unit shall incorporate an ionization sensor with nominal sensitivity of 0.50 to .92%/ft. The temperature operating range shall be between 40°F and 100°F (4°C and 38°C) and the humidity operating range shall be up to 85% relative humidity.

The smoke alarm can be installed on any standard single gang electri- cal box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a plug-in connector. A maximum of 24 Kidde devices can be interconnected in a multiple station arrangement. The interconnect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices, of which 12 can be smoke alarms. With 18 initiating devices (Smoke, heat, CO, etc), interconnected, it is still possible to interconnect 6 strobe lights and/or relay modules. The alarm shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling. No additional pieces shall be required to activate this feature.

The alarm shall include an easy access battery compartment that is opened and closed by sliding the battery door. The 9V battery carrier will ensure proper battery backup protection by not allowing the battery door to close if the battery is placed in the unit incorrectly or if a battery is not present.

The unit shall include a piezoelectric horn that is rated at 85 decibels at 10 feet. The unit shall include the Smart HushTM feature that silences the unit for approximately 8 minutes if a nuisance condition occurs.

The unit shall incorporate red and green LED indicators. The green LED (when illuminated) indicates the presence of AC power. The red LED (located under the TEST/Hush button) has four modes of operation:

Standby Condition: The red LED will flash every 30-40 seconds to indi- cate that the smoke alarm is operating properly. Alarm Condition: When the alarm senses products of combustion and goes into alarm the red LED will flash one flash per second. The flashing LED and pulsating alarm will continue until the air is cleared. When units are interconnected, only the red LED of the alarm that senses the smoke or is being tested (the originating unit) will flash. All other units in the interconnected system will sound an alarm but their red LED’s will NOT flash. Alarm Memory: This smoke alarm is equipped with an alarm memory, which provides a visual indication when an alarm has been activated. The red LED will illuminate for about 1.5 seconds every 16 seconds to indicate the memory condition. Smart HushTM Mode: The red LED will illuminate for 1.5 seconds every 8 seconds, indicating the smoke alarm is in the Smart HushTM Mode.

The unit shall at a minimum meet the requirements of UL217, NFPA72, and (chapter 11), The State of California Fire Marshall, NFPA101 (0ne and two family dwellings), Federal Housing Authority (FHA), Housing and Urban Development (HUD).

Ordering Information

Installation of Smoke Alarm

The smoke alarm should be installed to comply with all local codes having jurisdiction in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maxi- mum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household wire as required by code.

FUSE OR CIRCUIT BREAKER

L

N

 

BLACK

RED

 

WHITE

 

 

First

Additional

 

Alarm

Alarms

Technical Specifications

Model:

i5000

 

UPC:

0-47871-07582-9

Power Source:

120VAC (80mA Max)

Sensor:

Ionization

Audio Alarm:

85dB at 10ft

Temperature Range:

40˚F (4.4˚C) to 100˚F (37.8˚C)

Humidity Range:

Up to 85% relative humidity (RH)

Size:

5.6” in diameter x 1.8” depth

Weight:

.5lbs

 

Interconnects:

Up to 24 Kidde devices

LED:

Green, receiving ac power

 

Red, 4 modes of operation

Warranty:

10 year limited

5.6”

 

1.8”

 

Ordering

 

 

 

Dimensions

 

 

 

Number

UPC

I2F5

Pack Quantity

(w x d x h inches)

Weight

Skid

 

 

 

 

 

 

 

 

i5000 21007582

0-47871-07582-9

100-47871-07582-6

Cut Case (6 units)

6.63 x 13.25 x 6.25

3 lbs

1008

 

 

 

 

 

 

 

 

Not for sale by individual unit

1016 Corporate Park Drive Mebane NC 27302 1-800-880-6788 www.Kidde.com

Distributed by:

P/N: KL-i5000 sheet

rev. 01-2009