BRK electronic 7020B user manual Follow These Installation Steps, STAND-ALONE Alarm only

Page 3

FOLLOW THESE INSTALLATION STEPS

The basic installation of this Smoke Alarm is similar whether you want to install one Smoke Alarm, or interconnect more than one Smoke Alarm. If you are interconnecting more than one Smoke Alarm, you MUST read “Special Requirements For Interconnected Smoke Alarms” below before you begin installation.

ELECTRICAL SHOCK HAZARD. Turn off power to the area where you will install this unit at the circuit breaker or fuse box before beginning installation. Failure to turn off the power before installation may result in serious electrical shock, injury or death.

1.Remove the mounting bracket from the base, and attach it to the junction box.

Activate the battery back-up by removing the “Pull to Activate Battery Back-Up” tab. Or, install battery back-up. Battery back-up cannot work until you install the battery in the correct position (Match “+” to “+” and “-” to “-”).

Push and hold test button until the alarm sounds: 3 beeps, pause, 3 beeps, pause. The Escape Light® will turn on. LED flashes once every second.

2.Using wire nuts, connect the power connector to the household wiring.

STAND-ALONE ALARM ONLY:

Connect the white wire on the power connector to the neutral wire in the junction box.

Connect the black wire on the power connector to the hot wire in the junction box.

Tuck the orange wire inside the junction box. It is used for interconnect only.

INTERCONNECTED UNITS ONLY:

Strip off about 1/2” (12 mm) of the plastic coating on the orange wire on the power connector.

Connect the white wire on the power connector to the neutral wire in the junction box.

Connect the black wire on the power connector to the hot wire in the junction box.

Connect the orange wire on the power connector to the interconnect wire in the junction box. Repeat for each unit you are interconnecting. Never connect the hot or neutral wires in the junction box to the orange interconnect wire. Never cross hot and neutral wires between Alarms.

3.Plug the power connector into the back of the Smoke Alarm.

4.Position the base of the Smoke Alarm over the mounting bracket and turn. The Alarm can be positioned over the bracket every 90°. Turn the Smoke Alarm clockwise (right) until the unit is in place.

5.Check all connections.

Improper wiring of the power connector or the wiring leading to the power connector will cause damage to the Alarm and may lead to a non-functioning Alarm.

STAND-ALONE ALARM ONLY:

If you are only installing one Smoke Alarm, restore power to the junction box.

INTERCONNECTED UNITS ONLY:

If you are interconnecting multiple Smoke Alarms, repeat steps 1-5 for each Smoke Alarm in the series. When you are finished, restore power to the junction box.

ELECTRICAL SHOCK HAZARD. Do not restore power until all Smoke Alarms are completely installed. Restoring power before installation is complete may result in serious electrical shock, injury or death.

6.Make sure the Smoke Alarm is receiving AC power. Under normal operation, the Green power indicator light will shine continuously.

7.If the Green power indicator light does not light, TURN OFF POWER TO THE JUNCTION BOX and recheck all connections. If all connections are correct and the Green power indicator still does not light when you restore the power, the unit should be replaced immediately.

8.Test each Smoke Alarm. Press and hold the Test/Silence button until the unit alarms. When testing a series of interconnected units you must test each unit individually. Make sure all units alarm when each one is tested.

If any unit in the series does not alarm, TURN OFF POWER and recheck connections. If it does not alarm when you restore power, replace it immediately.

Special Requirements For Interconnected Smoke Alarms

Failure to meet any of the above requirements could damage the units and cause them to malfunction, removing your protection.

AC and AC/DC Smoke Alarms can be interconnected. Under AC power, all units will alarm when one senses smoke. When power is interrupted, only the AC/DC units in the series will continue to send and receive signals. AC powered Smoke Alarms will not operate.

Interconnected units can provide earlier warning of fire than stand-alone units, especially if a fire starts in a remote area of the dwelling. If any unit in the series senses smoke, all units will alarm. To determine which Smoke Alarm initiated an alarm, see table:

On Initiating Alarms

Red LED flashes rapidly

On All Other Alarms

Red LED is Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interconnect units within a single family residence only. Otherwise all households will experience unwanted alarms when you test any unit in the series. Interconnected units will only work if they are wired to compatible units and all requirements are met. This unit is designed to be compatible with: First Alert® Smoke Alarm Model SA9120B and BRK Electronics® Smoke Alarm Models 100S, 9120, 9120B, 7010, 7010B; BRK Electronics® Heat Alarm Models HD6135F, HD6135FB; Smoke/CO Alarm Model SC9120B; Relay Module RM4.

Interconnected units must meet ALL of the following requirements:

A maximum of 18 compatible units may be interconnected (Maximum of 12 Smoke Alarms).

The same fuse or circuit breaker must power all interconnected units.

The total length of wire interconnecting the units should be less than 1000 feet (300 meters). This type of wire is commonly available at Hardware and Electrical Supply stores.

All wiring must conform to all local electrical codes and NFPA 70 (NEC). Refer to NFPA 72, NFPA 101, and/or your local building code for further connection requirements.

A }

 

876 } B

5

5

 

4

4

 

 

3

3

2

 

2

1

 

1

A. Unswitched 120VAC

B. To additional units; Maximum = 18 total

60 Hz source

(Maximum 12 Smoke Alarms)

1. Smoke Alarm

4. Wire Nut

7. Interconnect Wire

2. Ceiling or Wall

5. Junction Box

(Orange)

8. Hot Wire (Blk)

3. Power Connector

6. Neutral Wire (Wht)

 

3

Image 3
Contents USER’S Manual Table of ContentsFire Safety Tips Before YOU Install this Smoke AlarmMounting Bracket HOW to Install this Smoke AlarmParts of this Smoke Alarm Power ConnectorFollow These Installation Steps STAND-ALONE Alarm onlyInterconnected Units only To Lock the Mounting Bracket Optional Locking FeaturesTo Lock the Battery Compartment To Unlock the Battery CompartmentIf this Smoke Alarm Sounds If YOU Suspect a Problem Recommended Locations For Smoke AlarmsLocations to Avoid for Smoke Alarms Special Compliance Considerations About Smoke AlarmsLimitations of Smoke Alarms Limited Warranty

7020B specifications

The BRK electronic 7020B is an advanced smoke and carbon monoxide detector that combines modern technology with user-friendly features to enhance home safety. Designed for both residential and commercial use, it provides reliable protection against the dangers of smoke and carbon monoxide, two of the most common hazards in indoor environments.

One of the standout features of the BRK 7020B is its dual-sensor technology. It utilizes both photoelectric and ionization sensors, which ensures a comprehensive approach to smoke detection. The photoelectric sensor is effective in detecting smoldering fires, while the ionization sensor is better suited for fast-flaming fires. This dual-sensor setup results in quicker response times and greater reliability, providing users with early warnings to enhance their safety.

In addition to smoke detection, the BRK 7020B also includes a carbon monoxide sensor. Carbon monoxide is a silent killer, and this device helps to ensure that users are alerted to its presence promptly. The detector features a loud 85-decibel alarm that can be heard throughout the house, providing immediate notice in case of danger.

The design of the BRK 7020B is compact and unobtrusive, allowing it to blend seamlessly into any environment. It is equipped with a tamper-resistant battery compartment and is powered by a 9V battery, ensuring continuous operation even during power outages. The battery life is long-lasting, with a recommended replacement every six months to maintain peak performance.

Another feature worth noting is the test/reset button that allows users to test the functionality of the detector easily. This ensures users can check the detector's operational status and reset it after false alarms. Additionally, the device is certified by Underwriters Laboratories (UL), which signifies its compliance with rigorous safety standards.

The BRK electronic 7020B is also designed with a low battery indicator to alert users when it’s time to replace the battery, ensuring continuous protection. This simple yet effective feature prevents the risk of battery failure during critical moments.

In summary, the BRK electronic 7020B smoke and carbon monoxide detector is a dependable choice for anyone looking to enhance their home safety. With its dual-sensor technology, reliable alarms, and user-friendly design, it provides peace of mind to homeowners and renters alike, ensuring that they are protected against the threats posed by smoke and carbon monoxide in their living spaces.