Operation

The Ei144 is a Heat Alarm that runs on 230V AC mains power, and has a 9V alkaline battery back up in the event of mains failure. The 9V battery will last for up to 4 years in standby mode, and capable of powering the heat detector for up to 2 years in the event of mains failure.

The Ei144 is supplied with the Easi-Fit base that allows very quick and simple installation of the heat alarm. The Easi-Fit base automatically connects both mains power and battery as the detector head slides on to the Easi-Fit base.

The Ei144 has the ability to interconnect up to twelve alarms to allow all alarms to sound if just one of the interconnected alarms should be triggered.

The Ei144 has built in circuitry to aid suppression of voltage transients and RF interference to further reduce the chances of false alarms under such conditions.

The Ei144 heat alarm gives a fire warning when the temperature at the unit reaches 580C. Heat alarms are ideal for use in kitchens and garages, where the use of optical or ionisation alarms would lead to unwanted nuisance alarms.

On escape routes this alarm must be interconnected with smoke alarms.

The green indicator will illuminate to show mains power is present

The red indicator will flash every 40 seconds to show that the detector has performed an automatic self test

The red indicator will flash rapidly to show an alarm condition for the heat detector

The “Test/Hush” button will either silence false alarms or perform a unit self test

In “Test” mode the alarm will perform a self test and sound the horn

In “Hush” mode the alarm enters a ten minute period of reduced sensitivity to overcome false alarm conditions, and will then automatically reset itself

When interconnected to other Ei mains powered alarms, an alarm on one detector will trigger all other interconnected alarms within one second (only the triggered alarm will flash a red indicator)

The heat detector will emit a beep every 40 seconds to indicate that the battery back up is depleted and needs replacing

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.+353 61 471277 Fx.+353 61 471053

Email. eielectronics@eiltd.ie

Web: www.eielectronics.com

E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice.

Ei144 DataSht RevA

Image 1
Contents 9V Alkaline Battery Back-Up Mains Powered 230V~Model Ei144 Heat Product Description OperationInstallation & Placement Technical Specification